Danfoss EVM solenoid pilot valve, NC, thread connection, 65 bar max working pressure. Used as the pilot stage on servo-operated refrigeration solenoid and main valves. OEM P/N 032F3054. Coil ordered separately. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.
| Type | EVM pilot valve |
| Function | NC (normally closed) |
| Connection | Thread |
| Kv value | 0.28 m³/h |
| Max working pressure | 65 bar |
| Media | R134a, R22, R401A, R402A, R404A, R407A, R407B, R407C, R407F, R409A, R410A, R421A, R502, R717, R744, R507A |
| Medium temperature | -60 to 120 °C |
| Ambient temperature | -40 to 80 °C |
| Packing | Multi pack, 20 pc |
| Net weight | 0.246 kg |
| Gross weight | 0.25 kg |
| EAN | 5702422085423 |
| MPN | 032F3054 |
| Product group | Press. and temp. regul. valves |
| Actuator system [mm] | 13.5 mm |
| Ambient temperature range [°F] [max] | 176 °F |
| Ambient temperature range [°F] [min] | -40 °F |
| Approval | LLC CDC TYSK |
| Body material | Steel |
| China RoHS compliance | Yes |
| Coil | No |
| Cv value [gal/min] | 0.323 gal/min |
| Direction | None |
| EU RoHS compliance | Yes |
| Inlet connection type | Thread |
| Kv value [m³/h] | 0.28 m³/h |
| Manual operation option | No |
| Max. Working Pressure [bar] | 65 bar |
| Max. Working Pressure [psig] | 943 psig |
| MaxOPD[bar] 10W AC | 21 bar |
| MaxOPD[bar] 20W DC | 12 bar |
| MaxOPD[psi] 10W AC | 305 psi |
| Medium temperature range [°C] [max] | 120 °C |
| Medium temperature range [°C] [min] | -60 °C |
| Medium temperature range [°F] [max] | 248 °F |
| Medium temperature range [°F] [min] | -76 °F |
| Orifice size [mm] | 3.3 mm |
| REACH Candidate List substances | No |
| Refrigerants | R134a |
| Type designation | Solenoid valve |
| UL mark | Yes |
| Valve operation | Servo-piston |
| Pressure rating | 65 bar |
| Temperature range | Medium -60 to 120 °C; ambient -40 to 80 °C |
| MOQ | 1 |
Solenoid pilot valve for servo-operated valves. Verify main-valve compatibility, media and coil voltage before ordering. Coil ordered separately.