Danfoss ICAD 1200B electric actuator (code number 027H0491) for the larger ICM motor-operated valves (ICM 40 to ICM 150), with Bluetooth, onboard OLED display and Ethernet (Modbus TCP/IP) communication. 24 V DC, IP67. Drives the ICM function module via a magnet coupling with continuous position feedback for pressure and temperature regulation in industrial refrigeration. Supplied without cables.
| Brand | Danfoss |
| Type | ICAD 1200B electric actuator (ICAD), without cables |
| Code number | 027H0491 |
| Supply voltage | 24 V DC |
| Communication interface | Bluetooth; onboard display (OLED); Ethernet |
| Enclosure rating | IP67 (~NEMA 6) |
| Electrical connection | M12 connectors |
| Used for | ICM 40, ICM 50, ICM 65, ICM 100, ICM 125, ICM 150, CVE |
| Ambient temperature range | -30 to 50 °C (-22 to 122 °F) |
| Housing material | aluminium; top part PBT thermoplastic |
| EAN | 5715162513668 |
| Net weight | 2.295 kg; gross weight: 2.675 kg |
| EU RoHS / China RoHS | compliant (with exemptions) |
| Approvals | CE, UL, RED (EU Radio Equipment Directive) |
| Product group | Press. and temp. regul. valves |
| Ambient temperature range [°C] [max] | 50 °C |
| Ambient temperature range [°C] [min] | -30 °C |
| Ambient temperature range [°F] [max] | 122 °F |
| Ambient temperature range [°F] [min] | -22 °F |
| Analog input current opt. [mA] [max] | 20 mA |
| Analog input current opt. [mA] [min] | 4 mA |
| Analog input Volt opt. [V] d.c [max] | 10 V |
| Analog input Volt opt. [V] d.c [min] | 2 V |
| Analog output options [mA] [max] | 20 mA |
| Analog output options [mA] [min] | 4 mA |
| Approval | CE |
| Approval document | FCC ID: Y82-DA14531MOD |
| CE mark | Yes |
| China RoHS compliance | Yes with exemptions |
| China RoHS exemption clause | 7.1 |
| Communication type | Bluetooth |
| Dig. Output-Ext supply [V] d.c [max] | 24 V |
| Dig. Output-Ext supply [V] d.c [min] | 5 V |
| Digital Output-Load [Ohm] | 60 Ohm |
| Digital Output-Max Load [mA] | 50 mA |
| Digital outputs (DO) [pc] | 3 pc |
| Display type | OLED |
| Electrical connector | M12 |
| Enclosure rating IP | IP67 |
| Enclosure rating Nema (~) | 6 |
| EU RoHS compliance | Yes with exemptions |
| EU RoHS exemption clause | 6(a) |
| Function | Digital output |
| Load Analog input Current[Ohm] | 250 Ohm |
| Load Analog input Voltage[Ohm] | 10 Ohm |
| Load Analog output max [Ohm] | 500 Ohm |
| Output configuration | Open drain |
| Power supply | Class 2 |
| Product version | 01 |
| REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
| Supply voltage [V] DC | 24 V |
| Supply voltage load [A] | 2 A |
| Supply voltage tolerance [%] [max] | 10 % |
| Supply voltage tolerance [%] [min] | -15 % |
| Temperature range [°C] [max] | 120 °C |
| Temperature range [°C] [min] | -60 °C |
| Temperature range [°F] [max] | 248 °F |
| Temperature range [°F] [min] | -76 °F |
| UL mark | Yes |
| Used for product | CVE |
| Temperature range | -30 to 50 °C |
| IP rating | IP67 |
| MOQ | 1 |
Fits ICM 40, ICM 50, ICM 65, ICM 100, ICM 125, ICM 150 and CVE. Ethernet communication variant with Bluetooth and onboard display. Connect via M12 (order cable set separately). Confirm ICM size and the required communication interface before ordering.