Danfoss FJV self-acting temperature limiter, OEM P/N 003N8218. Direct-acting proportional temperature controller used to limit the temperature of circulation water in district heating and cooling circuits; the bellows element senses the medium temperature and throttles the valve. DN 20, PN 16, internal thread Rp 3/4 in (ISO 7/1). Kvs 3.4 m³/h; temperature setting range 50 – 90 °C, linear characteristic. Brass body (CuZn40Pb2, W.-Nr. 2.0402), NBR valve cone, Cr Ni steel valve seat (W.-Nr. 1.4301). Max differential pressure 10 bar; media temperature 2 – 130 °C. Approved to ETA VA 1.54/18952. Confirm the setting range and code against the datasheet before ordering.
| Brand | Danfoss |
| Part number | 003N8218 |
| Model | FJV self-acting temperature limiter |
| Category | HVAC & Refrigeration — Water Regulating Valves |
| Version | direct-acting proportional temperature limiter, internal thread |
| Function | temperature limiter; senses medium temperature via bellows element and throttles the valve to hold the set limit |
| Nominal size | DN 20 |
| Pressure class | PN 16 |
| Connection | internal thread Rp 3/4 in (ISO 7/1) |
| Kvs | 3.4 m³/h |
| Temperature setting range | 50 – 90 °C |
| Flow characteristic | linear |
| Max differential pressure | 10 bar |
| Media temperature range | 2 °C to 130 °C |
| Ambient temperature range | 0 °C to 70 °C |
| Cavitation factor | 0.4 |
| Body material | brass CuZn40Pb2 (W.-Nr. 2.0402) |
| Valve cone material | NBR rubber |
| Valve seat material | Cr Ni steel (W.-Nr. 1.4301) |
| Application | district heating / cooling circulation water; glycolic water up to 30% |
| Packing | Single pack |
| EAN | 5702421100875 |
| Approvals | ETA VA 1.54/18952, EAC, PED, EU RoHS, China RoHS |
| Material | Body brass CuZn40Pb2 (W.-Nr. 2.0402); valve cone NBR rubber; valve seat Cr Ni steel (W.-Nr. 1.4301) |
| Pressure rating | PN 16; max differential pressure 10 bar |
| Temperature range | 2 °C to 130 °C (media) |
| Standard size | DN 20 |
| Thread standard | ISO 7/1 (Rp) |
| MOQ | 1 |
Fit in the water line with the flow arrow in the direction of flow. Self-acting (no external power). Set the temperature limit on the adjustment spindle. Confirm code and setting range before ordering.