Danfoss FJVA 25 thermostatically operated cooling-water valve, OEM P/N 003N8216. Self-acting valve that regulates the flow of condenser cooling water from the water temperature — the entire filled bellows element acts as the temperature sensor, so no separate capillary bulb is required. Opens on rising sensor temperature; fit in the cooling-water return line. Brass body, G (ISO 228-1) 1 in connection. Kv 5.5 m³/h; orifice 25 mm. Sensor temperature range 25 – 65 °C. Max working pressure 16 bar; media temperature -25 °C to 130 °C. Media: Fresh water, neutral brine. Confirm the setting range and code against the datasheet before ordering.
| Brand | Danfoss |
| Part number | 003N8216 |
| Model | FJVA 25 thermostatically operated water valve |
| Category | HVAC & Refrigeration — Water Regulating Valves |
| Version | without capillary sensor (bellows acts as the sensor), G (ISO 228-1) connection |
| Function | self-acting cooling-water valve; opens on rising sensor (cooling-water) temperature; throttles condenser cooling water by temperature |
| Nominal size | FJVA 25 (DN 25) |
| Water-side connection | G 1 in, ISO 228-1 (inlet and outlet) |
| Kv | 5.5 m³/h (Cv 6.4 gal/min) |
| Orifice | 25 mm |
| Bypass diameter | 2.5 mm |
| Sensor temperature range | 25 – 65 °C |
| Max working pressure (MWP) | 16 bar (232 psig) water side |
| Differential pressure (max) | 10 bar |
| Media temperature range | -25 °C to 130 °C |
| Body material | brass |
| Media | Fresh water, neutral brine |
| Packing | Single pack |
| EAN | 5702423035779 |
| Materials | Valve housing hot-pressed brass; bellows and regulating parts stainless steel; adjustment spring steel |
| Approvals | EAC, PED, EU RoHS, China RoHS |
| Material | Valve housing hot-pressed brass; bellows and regulating parts stainless steel; adjustment spring steel |
| Pressure rating | 16 bar (232 psig) water side max working pressure |
| Temperature range | -25 °C to 130 °C |
| Standard size | FJVA 25 |
| Thread standard | ISO 228-1 |
| MOQ | 1 |
Fit in the cooling-water return line with the flow arrow in the direction of flow; the bellows senses the water temperature directly (no separate bulb). Opens on rising temperature. Confirm code, water connection and setting range before ordering.