Contactor B 6-40-00F 380/50 (GJL1211203R8005)

ABB Automasjon · Electrical Components · Contactors
Part Number
GJL1211203R8005  ·  HS 8536.90
Contactor B 6-40-00F 380/50 (GJL1211203R8005)

ABB GJL1211203R8005 — The B6-40-00-F mini contactor is a compact 4 pole contactor with flat pin connection. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors are used in residential buldings, commercial buildings and industrial applications for the control of single or three-phase loads up to 4 kW (AC-3) and 20 A (AC-1) or switching of control signals. Further features are the silent coil, a switch position indication and the integrated possibility for rail or wall mounting.

Technical Specifications

Manufacturer part number (MPN)GJL1211203R8005
EAN / GTIN4013614189296
HS code8536.90
Sales unitpcs
Product Net Width52.5 mm
Product Net Depth / Length46.7 mm
Product Net Height57.5 mm
Dimension DiagramGJL1200437F0001
Number of Main Contacts NO4
Number of Main Contacts NC0
Number of Auxiliary Contacts NO0
Number of Auxiliary Contacts NC0
Number of Poles4P
StandardsIEC/EN 60947-1; IEC/EN 60947-4-1; IEC/EN 60947-5-1; UL 60947-1; UL 60947-4-1; IEC 60335-2-40 A2L
Rated Operational VoltageMain Circuit 690 V AC; Main Circuit 220 V DC
Rated Frequency (f)Control Circuit 400 Hz; Control Circuit 50 Hz; Control Circuit 60 Hz; Main Circuit 60 Hz; Main Circuit 50 Hz; Main Circuit DC
Conventional Free-air Thermal Current (I th )Main Circuit 20 A
Rated Operational Current AC-1 (I e )(220 / 240 V) 40 °C 20 A; (220 / 240 V) 55 °C 16 A; (380 / 440 V) 40 °C 20 A; (380 / 440 V) 55 °C 16 A; (690 V) 40 °C 6 A; (690 V) 55 °C 6 A
Rated Operational Current AC-3 (I e )(230 V) 55°C 9 A; (400 V) 55 °C 9 A; (500 V) 55 °C 6.5 A; (690 V) NO 55°C 3.5 A
Rated Operational Power AC-3 (P e )(230 V) Three Phase 2.2 kW; (400 V) Three Phase 4 kW; (500 V) Three Phase 4 kW; (690 V) Three Phase, NO 3 kW
Rated Breaking Capacity AC-38 x Ie / AC-3
Rated Making Capacity AC-310 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (I cw )at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 64 A
Rated Insulation Voltage (U i )690 V; acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour; (AC-3) 600 cycles per hour; (DC-1) 600 cycles per hour; (DC-3) 600 cycles per hour
Mechanical DurabilityNr. Operations 10000000 cycle
Coil Operating Limits(acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (U c )380 ... 415 V AC
Coil ConsumptionAverage Holding Value 50 Hz 3.5 V·A; Average Pull-in Value 50 Hz 3.5 V·A
Power Lossat Rated Operating Conditions AC-1 per Pole 1 W
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715; TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Degree of ProtectionControl Circuit Terminals IP20; Main Circuit Terminals IP20
Terminal TypeFlat-Pin Connections
Mini Contactor TypeMini Contactor
Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
General Use Rating UL/CSA(300 V AC) 12 A
Horsepower Rating UL/CSA(115 V AC) Single Phase 0.25 Hp; (200 V AC) Three Phase 1 Hp; (220 ... 240 V AC) Three Phase 2 Hp; (230 V AC) Single Phase 0.5 Hp; (440 ... 480 V AC) Three Phase 3 Hp; (550 ... 600 V AC) Three Phase 1 Hp
Full Load Amps Motor Use(115 V AC) Single Phase 5.8 A; (200 V AC) Three Phase 4.8 A; (220 ... 240 V AC) Three Phase 6.8 A; (230 V AC) Single Phase 4.9 A; (440 ... 480 V AC) Three Phase 4.8 A; (550 ... 600 V AC) Three Phase 1.7 A
Ambient Air TemperatureOperation -20 ... +55 °C; Storage -40 ... +80 °C
Maximum Operating Altitude Permissible2000 m
Resistance to Shock acc. to IEC 60068-2-2711 ms Pulse 15g
Resistance to Vibrations5g 5 ... 150 Hz
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetNo non-hazardous waste is sent to a landfill; UL 2799 Zero Waste To Landfill Validation available
EcoSolutions Profile1SFC100125C0354
End Of Life Disassembling Instructions1SBC100156C0270
Environmental Product Declaration - EPD1SAC200409H0001
Improved Energy Efficiency for CustomersProduct Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 87.4 %
A2L Certificate – IEC1SAA938000-4601
BV Certificate1SAA920000-0204
CB Certificate1SAA938000-2002
CCC Certificate2024010304658943
cURus CertificatecUL_E191658
Declaration of Conformity - CE1SAD101100-3101
Declaration of Conformity - UKCA1SAD201100-3101
DNV GL Certificate1SAA938000-0306
LR Certificate1SAA938000-0504
RMRS Certificate1SAA938000-0704
UL CertificateE191658-19880915
Object Classification CodeQ
ETIM 7EC000066 - Power contactor, AC switching
eClassV11.0 : 27371003
UNSPSC39121529
E-Number (Norway)4184012
EAN4013614413315

Properties

MOQ1