| Manufacturer part number (MPN) | GJL1211203R8005 |
| EAN / GTIN | 4013614189296 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Product Net Width | 52.5 mm |
| Product Net Depth / Length | 46.7 mm |
| Product Net Height | 57.5 mm |
| Dimension Diagram | GJL1200437F0001 |
| Number of Main Contacts NO | 4 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Standards | IEC/EN 60947-1; IEC/EN 60947-4-1; IEC/EN 60947-5-1; UL 60947-1; UL 60947-4-1; IEC 60335-2-40 A2L |
| Rated Operational Voltage | Main Circuit 690 V AC; Main Circuit 220 V DC |
| Rated Frequency (f) | Control Circuit 400 Hz; Control Circuit 50 Hz; Control Circuit 60 Hz; Main Circuit 60 Hz; Main Circuit 50 Hz; Main Circuit DC |
| Conventional Free-air Thermal Current (I th ) | Main Circuit 20 A |
| Rated Operational Current AC-1 (I e ) | (220 / 240 V) 40 °C 20 A; (220 / 240 V) 55 °C 16 A; (380 / 440 V) 40 °C 20 A; (380 / 440 V) 55 °C 16 A; (690 V) 40 °C 6 A; (690 V) 55 °C 6 A |
| Rated Operational Current AC-3 (I e ) | (230 V) 55°C 9 A; (400 V) 55 °C 9 A; (500 V) 55 °C 6.5 A; (690 V) NO 55°C 3.5 A |
| Rated Operational Power AC-3 (P e ) | (230 V) Three Phase 2.2 kW; (400 V) Three Phase 4 kW; (500 V) Three Phase 4 kW; (690 V) Three Phase, NO 3 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 64 A |
| Rated Insulation Voltage (U i ) | 690 V; acc. to UL/CSA 600 V |
| Rated Impulse Withstand Voltage (U imp ) | Main Circuit 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour; (AC-3) 600 cycles per hour; (DC-1) 600 cycles per hour; (DC-3) 600 cycles per hour |
| Mechanical Durability | Nr. Operations 10000000 cycle |
| Coil Operating Limits | (acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 380 ... 415 V AC |
| Coil Consumption | Average Holding Value 50 Hz 3.5 V·A; Average Pull-in Value 50 Hz 3.5 V·A |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 1 W |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715; TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Degree of Protection | Control Circuit Terminals IP20; Main Circuit Terminals IP20 |
| Terminal Type | Flat-Pin Connections |
| Mini Contactor Type | Mini Contactor |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| General Use Rating UL/CSA | (300 V AC) 12 A |
| Horsepower Rating UL/CSA | (115 V AC) Single Phase 0.25 Hp; (200 V AC) Three Phase 1 Hp; (220 ... 240 V AC) Three Phase 2 Hp; (230 V AC) Single Phase 0.5 Hp; (440 ... 480 V AC) Three Phase 3 Hp; (550 ... 600 V AC) Three Phase 1 Hp |
| Full Load Amps Motor Use | (115 V AC) Single Phase 5.8 A; (200 V AC) Three Phase 4.8 A; (220 ... 240 V AC) Three Phase 6.8 A; (230 V AC) Single Phase 4.9 A; (440 ... 480 V AC) Three Phase 4.8 A; (550 ... 600 V AC) Three Phase 1.7 A |
| Ambient Air Temperature | Operation -20 ... +55 °C; Storage -40 ... +80 °C |
| Maximum Operating Altitude Permissible | 2000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | 11 ms Pulse 15g |
| Resistance to Vibrations | 5g 5 ... 150 Hz |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill; UL 2799 Zero Waste To Landfill Validation available |
| EcoSolutions Profile | 1SFC100125C0354 |
| End Of Life Disassembling Instructions | 1SBC100156C0270 |
| Environmental Product Declaration - EPD | 1SAC200409H0001 |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 87.4 % |
| A2L Certificate – IEC | 1SAA938000-4601 |
| BV Certificate | 1SAA920000-0204 |
| CB Certificate | 1SAA938000-2002 |
| CCC Certificate | 2024010304658943 |
| cURus Certificate | cUL_E191658 |
| Declaration of Conformity - CE | 1SAD101100-3101 |
| Declaration of Conformity - UKCA | 1SAD201100-3101 |
| DNV GL Certificate | 1SAA938000-0306 |
| LR Certificate | 1SAA938000-0504 |
| RMRS Certificate | 1SAA938000-0704 |
| UL Certificate | E191658-19880915 |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| E-Number (Norway) | 4184012 |
| EAN | 4013614413315 |