cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

48-130V AC/DC NF22E-12

ABB · Control & Automation · Relays & Timers · Switzerland · abb.com
Part Number
NF22E-12  ·  HS 8536.49
48-130V AC/DC NF22E-12

ABB NF22E-12 — The NF22E-12 is a 690 V IEC or 600 UL 4-pole contactor relay with screw terminals, used for switching auxiliary and control circuits.Thanks to the AF technology, the contactor relay has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. NF contactor relays have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.These contactor relays include mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1 and are side-marked with the Mechanically Linked symbol.

Technical Specifications

Manufacturer part number (MPN)NF22E-12
EAN / GTIN3471523100121
Sales unitpcs
Package quantity54 pcs
Configuration OnlyNo
Country of OriginSwitzerland
CriticalityNo
Lead Time57 day
NoteNo
Product Availability ClassOn Request, Both availability and price will be quoted case by case. Check the replacement/alternative part
Product Sales StatusActive
Storage Location4001
Product Net Width45 mm
Product Net Depth / Length77 mm
Product Net Height86 mm
Number of Auxiliary Contacts NO2
Number of Auxiliary Contacts NC2
Number of Poles4P
StandardsIEC/EN 60947-1, IEC/EN 60947-5-1, UL 60335-2-40 LZGH2 A2L, UL 508, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 14-13
Rated Operational VoltageAuxiliary Circuit 690 V
Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz; Control Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (I th )acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-15 (I e )(500 V) 2 A; (690 V) 2 A; (24 / 127 V) 6 A; (220 / 240 V) 4 A; (400 / 440 V) 3 A
Rated Operational Current DC-13 (I e )(24 V) 6 A / 144 W; (48 V) 2.8 A / 134 W; (72 V) 1 A / 72 W; (110 V) 0.55 A / 60 W; (125 V) 0.55 A / 69 W; (220 V) 0.27 A / 60 W; (250 V) 0.27 A / 68 W; (400 V) 0.15 A / 60 W; (500 V) 0.13 A / 65 W; (600 V) 0.1 A / 60 W
Rated Short-time Withstand Current Low Voltage (I cw )for 0.1 s 140 A; for 1 s 100 A
Rated Insulation Voltage (U i )acc. to IEC 60947-5-1 690 V; acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (U imp )6 kV
Maximum Electrical Switching Frequency(AC-15) 1200 cycles per hour; (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency6000 cycles per hour
Rated Control Circuit Voltage (U c )50 Hz 48 ... 130 V; 60 Hz 48 ... 130 V; DC Operation 48 ... 130 V
Power Lossat 6 A per Pole 0.1 W
Operate TimeBetween Coil De-energization and NC Contact Closing 13 ... 98 ms; Between Coil De-energization and NO Contact Opening 11 ... 95 ms; Between Coil Energization and NC Contact Opening 38 ... 90 ms; Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715; TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)2 x M4 Screws Placed Diagonally
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²; Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²; Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²; Rigid Solid 1/2x 1 ... 2.5 mm²; Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²; Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²; Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²; Rigid Solid 1/2x 1 ... 2.5 mm²; Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping LengthAuxiliary Circuit 10 mm; Control Circuit 10 mm
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20; acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Tightening TorqueAuxiliary Circuit 1.2 N·m; Control Circuit 1.2 N·m
Terminal TypeScrew Terminals
Connecting Capacity Auxiliary Circuit UL/CSARigid Solid 1/2x 18-14 AWG; Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSAAuxiliary Circuit 11 in·lb; Control Circuit 11 in·lb
Ambient Air TemperatureClose to Contactor for Storage -60 ... +80 °C; Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic WithstandCategory B according to IEC 60947-1 Annex Q
Maximum Operating Altitude PermissibleWithout Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27Closed
Shock DirectionB1 25 g; Open
Shock DirectionB1 5 g; Shock Direction: A 30 g; Shock Direction: B2 15 g; Shock Direction: C1 25 g; Shock Direction: C2 25 g
Resistance to Vibrations4g Closed Position & 2g Open position 5 ... 300 Hz
Pollution Degree3
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetNo non-hazardous waste is sent to a landfill
EcoSolutions Profile1SBC100156C0308
End Of Life Disassembling Instructions1SBC101080M6801
Environmental Product Declaration - EPD1SBD250584E3000
Improved Energy Efficiency for CustomersProduct Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 92.7 %
A2L Certificate – UL9AKK108469A4900; 9AKK108469A4902
ABS CertificateABS_26-0348269-PDA_FR; ABS_26-0348269-PDA-DUP_CN
BV CertificateBV_2634H24899C1
CB CertificateCB_SE-117902
CCC CertificateCCC_2024010303656666
Declaration of Conformity - CCCCQC2011010303465426
Declaration of Conformity - CE1SBD250005U1000
Declaration of Conformity - UKCA1SBD250036U1000
DNV CertificateDNV_TAE00001BV-5
LR CertificateLRS_LR2003684TA-02
RINA CertificateRINA_ELE142224XG
RMRS CertificateRMRS_1802702280
UL CertificateUL_20180227_E252354_2_1
UL Listing CardUL_E252354
Object Classification CodeK
ETIM 7EC000196 - Contactor relay
eClassV11.0 : 27371001
UNSPSC39121529
IDEA Granular Category Code (IGCC)4763 >> Power contactor, DC switching
E-Number (Finland)3706400
E-Number (Sweden)3211447

Properties

MOQ1

Cross-References