cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Contactor AF140-40-11B-13

ABB · Electrical Components · Contactors · Switzerland · abb.com
Part Number
AF140-40-11B-13  ·  HS 8536.90
Contactor AF140-40-11B-13

ABB AF140-40-11B-13 — The AF140-40-11B-13 is a 4 pole - 690 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 75 kW / 400 V AC (AC-3) / and switching power circuits up to 200 A (AC-1) or 175 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.

Technical Specifications

Manufacturer part number (MPN)AF140-40-11B-13
EAN / GTIN7320500505205
HS code8536.90
Sales unitpcs
Product Net Width120 mm
Product Net Depth / Length128 mm
Product Net Height150 mm
Dimension Diagram1SFB535001G1121
Number of Main Contacts NO4
Number of Main Contacts NC0
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC1
Number of Poles4P
Rated Operational VoltageMain Circuit 690 V
Rated Frequency (f)Main Circuit 60 Hz; Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (I th )acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 200 A
Rated Operational Current AC-1 (I e )(690 V) 40 °C 200 A; (690 V) 60 °C 175 A; (690 V) 70 °C 160 A
Rated Operational Current AC-3 (I e )(415 V) 55 °C 140 A; (440 V) 55 °C 140 A; (380 / 400 V) 55 °C 140 A; (220 / 230 / 240 V) 55 °C 140 A
Rated Operational Power AC-3 (P e )(415 V) 75 kW; (440 V) 90 kW; (380 / 400 V) 75 kW; (220 / 230 / 240 V) 37 kW
Rated Breaking Capacity AC-38 x Ie AC-3
Rated Breaking Capacity AC-3e8.5 x Ie AC-3e
Rated Making Capacity AC-310 x Ie AC-3
Rated Making Capacity AC-3e12 x Ie AC-3e
Short-Circuit Protective DevicesgG Type Fuses 250 A
Rated Short-time Withstand Current Low Voltage (I cw )at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 200 A; at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 674 A; at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 1460 A; at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1168 A; at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 477 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 A
Rated Insulation Voltage (U i )acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V; acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (U imp )Main Circuit 8 kV
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour; (AC-3) 300 cycles per hour
Mechanical Durability5 million
Maximum Mechanical Switching Frequency300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (U c )50 Hz 100 ... 250 V; 60 Hz 100 ... 250 V; DC Operation 100 ... 250 V
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 30.7 V·A; Holding at Max. Rated Control Circuit Voltage 60 Hz 30.7 V·A; Holding at Max. Rated Control Circuit Voltage DC 2.8 V·A; Holding at Max. Rated Control Circuit Voltage DC 2.8 W; Pull-in at Max. Rated Control Circuit Voltage 50 Hz 220 V·A; Pull-in at Max. Rated Control Circuit Voltage 60 Hz 220 V·A; Pull-in at Max. Rated Control Circuit Voltage DC 275 V·A; Pull-in at Max. Rated Control Circuit Voltage DC 275 W
Power Lossat Rated Operating Conditions per Pole 18 W
Operate TimeBetween Coil De-energization and NO Contact Opening 40 ... 70 ms; Between Coil Energization and NO Contact Closing 20 ... 55 ms
Connecting Capacity Main CircuitFlexible 2 x 10 ... 70 mm²; Rigid Cu-Cable 1 x 10 ... 95 mm²; Rigid Cu-Cable 2 x 10 ... 95 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 2x 0.75 ... 2.5 mm²; Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²; Flexible 2x0.75 ... 2.5 mm²; Solid 2 x 1 ... 4 mm²; Stranded 2 x 1 .... 4 mm²
Connecting CapacityFlexible 2 x 10 ... 70 mm²; Rigid Cu-Cable 2 x 10 ... 95 mm²
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40; acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20; acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Tightening TorqueCable Lug 9 N·m; Main Circuit 8 N·m
Terminal TypeMain Circuit: Bars
NEMA Size4
Horsepower Rating NEMA(200 V AC) Three Phase 40 Hp; (230 V AC) Three Phase 50 Hp; (460 V AC) Three Phase 100 Hp; (575 V AC) Three Phase 100 Hp
Maximum Operating Voltage UL/CSAMain Circuit 600 V
General Use Rating UL/CSA(600 V AC) 175 A
Horsepower Rating UL/CSA(200 ... 208 V AC) Three Phase 15 Hp; (200 V AC) Three Phase 40 hp; (208 V AC) Three Phase 40 hp; (220 ... 240 V AC) Three Phase 20 Hp; (220 ... 240 V AC) Three Phase 50 hp; (440 ... 480 V AC) Three Phase 40 Hp; (440 ... 480 V AC) Three Phase 100 hp; (550 ... 600 V AC) Three Phase 50 Hp; (550 ... 600 V AC) Three Phase 125 hp
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C; Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C; Close to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude PermissibleWithout Derating 3000 m
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetNon-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility; UL 2799 Zero Waste To Landfill Validation available
EcoSolutions Profile1SFC100125C0366
End Of Life Disassembling Instructions1SFC100112M0001
Environmental Product Declaration - EPD1SFC100092D0201
Improved Energy Efficiency for CustomersProduct Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line; Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 87.8 %
ABS Certificate14-LD1092198-PDA; 14-LD1092198-1-PDA-DUP
BV CertificateBV_36353_A0BV
CB CertificateSEMKO_SE-77317
CCS CertificateGB14T00030
CQC CertificateCQC2013010304604055
cULus CertificateE73397_20140710
Declaration of Conformity - CE2CMT2015-005439
Declaration of Conformity - UKCA2CMT2020-006118
DNV CertificateDNV_E-14043
LR Certificate16-20064
PRS CertificateTE_2092_880423_16
RINA CertificateELE060313XG_002
Object Classification CodeQ
ETIM 7EC000066 - Power contactor, AC switching
eClassV11.0 : 27371003
UNSPSC39121529
IDEA Granular Category Code (IGCC)4758 >> Iec Contactors
E-Number (Finland)3707174
E-Number (Norway)4117781
E-Number (Sweden)3210323

Properties

MOQ1

Cross-References

Attached Documents