| Manufacturer part number (MPN) | 2CDH784010R0802 |
| EAN / GTIN | 4016779879842 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 45.9 % |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| Extended Product Lifetime | Product Durability |
| End Of Life Disassembling Instructions | 9AKK108469A4877 |
| Environmental Product Declaration - EPD | 9AKK108468A5768 |
| Suitable for Isolation | Yes |
| Dielectric Test Voltage | 50 / 60 Hz - 1 min 2 kV |
| Rated Ultimate Short-Circuit Breaking Capacity (I cu ) | (400 V AC) 25 kA |
| Rated Service Short-Circuit Breaking Capacity (I cs ) | (400 V AC) 12.5 kA |
| Power Supply Connection | Arbitrary |
| Contact Position Indication | Red ON / Green OFF |
| Number of Poles | 4P |
| Tightening Torque | 2.5 ... 3 N·m |
| Screw Terminal Type | Cable Clamp |
| Actuator Marking | I / O |
| Recommended Screw Driver | Cross Recess Pozidriv 2; Slotted 1 x 5.5 |
| Accessories Available | Yes |
| Connecting Capacity | Flexible with Ferrule 2.5 ... 50 mm²; Flexible 2.5 ... 50 mm²; Rigid 2.5 ... 50 mm²; Stranded 2.5 ... 50 mm² |
| Installation Size | acc. to DIN 43880 3 |
| Terminal Type | Screw Terminals |
| Tripping Characteristic | E (Selective) |
| Rated Operational Voltage | 400 V AC; acc. to IEC 60947-2 400 V AC |
| Rated Insulation Voltage (U i ) | acc. to IEC/EN 60664-1 690 V |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV; at 2000 m 8 kV; at Sea Level 9.8 kV |
| Input Voltage Type | AC |
| Rated Current (I n ) | 80 A |
| Rated Short-Circuit Capacity | (400 V AC) 25 kA |
| Rated Frequency (f) | 50 / 60 Hz |
| Power Loss | at Rated Operating Conditions per Pole 10.5 W |
| Overvoltage Category | IV |
| I²t Characteristic | 9AKK108466A4490 |
| Ambient Air Temperature | Operation -25 ... +55 °C; Storage -40 ... +70 °C |
| Degree of Protection | IP20; Enclosure with Cover IP40 |
| Pollution Degree | 3 |
| Environmental Conditions | 28 cycles; with 55 °C / 90-96 %; and 25 °C / 95-100 % |
| Resistance to Vibrations | 20 Cycles with Load 0.8 In: 2g 5 ... 150 ... 5 Hz |
| Resistance to Shock acc. to IEC 60068-2-27 | 30g 3 shocks 11 ms |
| Product Net Width | 116 mm |
| Product Net Height | 130 mm |
| Product Net Depth / Length | 96 mm |
| Dimension Diagram | 9AKK108466A4497 |
| Declaration of Conformity - CE | 2CDK400633D2701 |
| Instructions and Manuals | 2CDS707001P0004 |
| Mounting Type | DIN-Rail |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715; TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Mounting Position | any |
| ETIM 9 | EC001047 - Selective main line circuit breaker |
| UNSPSC | 39121614 |
| eClass | V11.0 : 27141903 |
| Object Classification Code | F |
| Standards | IEC/EN 60947-2 |
| Certification Agency | EN; IEC |