cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

ABB RD2 Residual Current Monitor (RCM) — Type A, 48 … 150 V AC/DC, External Toroidal Transformer (2CSM242120R1201)

ABB · Electrical Components · RCDs & RCBOs · Switzerland · abb.com
Part Number
2CSM242120R1201  ·  HS 8536.41
ABB RD2 Residual Current Monitor (RCM) — Type A, 48 … 150 V AC/DC, External Toroidal Transformer (2CSM242120R1201)

The ABB 2CSM242120R1201 is an RD2 residual current monitor (RCM). Unlike an RCD, it does not break the circuit itself: it measures the leakage current flowing through an external toroidal transformer and signals through its output contact, so the tripping is done by a separate breaker or contactor — or not at all, where the requirement is to warn about deteriorating insulation while keeping a process running. Sensitivity and intervention time are set with the minidip switches on the front. This makes it the usual choice for monitoring large or continuous-process installations, and for retrofitting earth-fault monitoring where the existing breaker cannot be changed. It is a Type A device, so it detects sinusoidal AC and pulsating DC residual currents. Sensitivity and tripping delay are both set on the device, which is what lets one part number cover a range of installations and lets discrimination be arranged with the devices downstream. Supply voltage is 48 … 150 V AC/DC. Supplied by cBallast on quote-to-invoice terms; lead time and freight are quoted per RFQ against the destination Incoterm.

Technical Specifications

Manufacturer part number (MPN)2CSM242120R1201
EAN / GTIN8012542537809
Sales unitpcs
Country of OriginRomania
Lead Time0 day
Product Sales StatusActive
Type of Residual CurrentType A
FunctionFor AC-current system
Current RatingResponse value amperage 1 2000 ... 2000 mA
Number of Contacts1 Delay Time ( τ ): Delay-On Energization, Maximum, Permitted 5 s; Delay-On Energization, minimum, Adjustable 0.3 s
Filter Optionno frequency filter
Options ProvidedPre-alarm threshold: no Rated Voltage (U r ): 400...400 V
Rated Operational Voltage48 ... 150 V AC/DC Rated Control Supply Voltage (U s ): (DC) 120...150 V; (DC) 120...150 V; (50 Hz) 150...150 V; (50 Hz) 150...150 V; (60 Hz) 150...150 V; (60 Hz) 150...150 V Rated Frequency (f): 50 … 60 Hz
Power LossTotal 3.4 W
Number of Contacts CO1
Number of Contacts NC0
Number of Contacts NO0
Product Net
Width35 mm
Product Net
Height0.085 m
Product Net Depth / Length65 mm
Declaration of Conformity - CE9AKK106713A5627
Instructions and Manuals0400 - 9924
Mounting TypeDIN-Rail
ETIM 9EC001445 - Residual current monitoring relay
UNSPSC39121601
eClassV11.0 : 27371809
Object Classification CodeF
StandardsIEC EN 62020
Type of electric connectionScrew connection Rated control supply voltage AC 50 Hz: 150 V Rated control supply voltage AC 60 Hz: 150 V Rated control supply voltage DC: 120–150 V Voltage type for actuating: AC/DC With detachable clamps: No Response value amperage 1: 2000 mA Response value amperage 2: 2000 mA Min. adjustable delay-on energization time: 0.3 s Max. permitted delay-on energization time: 5 s Indication of difference current: No Error registration possible: No Number of contacts as change-over contact: 1
Width35 mm
Height85 mm
Depth65 mm
Product familyABB RD2 residual current monitor
ModelRD2
Device typeResidual current monitor (RCM), external toroidal transformer
Supply voltage48 … 150 V AC/DC
ResetManual
Pre-alarm thresholdNot fitted
Frequency filterNot fitted
LED bar indicatorNot fitted

Properties

MOQ1

Cross-References