Arbeids-Currenttrigger 12V AC/DC S800 (2CCS800900R0201)

ABB · Electrical Components · Circuit Breaker Accessories · Switzerland · abb.com
Part Number
2CCS800900R0201  ·  HS 8538.90
Arbeids-Currenttrigger 12V AC/DC S800 (2CCS800900R0201)

ABB 2CCS800900R0201 — The S800-SOR12 is a 12V shunt opening release is for remote release of the S800 High Performance MCB using an electrical impulse. Operation of the trigger is guaranteed at a voltage between 70% and 110% of the rated voltage Un - both for AC and DC. The S800-SOR12 can be mounted by the user at the left side of S800 High Performance MCB.

Technical Specifications

Manufacturer part number (MPN)2CCS800900R0201
EAN / GTIN7612271212070
Sales unitpcs
Voltage12 V
Suitable ForS800P; S800S; S800N; S800C; S800B; S800HV; S800U; S800PV-SP; S800PV-SD; S800PV-M-H
Tightening Torque3.5 N·m
Actuator MarkingI / O
Recommended Screw DriverPozidriv 2
Connecting CapacityFlexible 1 ... 25 mm²; Stranded 1 ... 35 mm²
Terminal TypeScrew Terminals
Rated Operational Voltage12 V AC/DC
Rated Insulation Voltage (U i )690 V AC
Rated Control Supply Voltage (U s )(50 Hz) 12...12 V; (50 Hz) 12...12 V; (60 Hz) 12...12 V; (60 Hz) 12...12 V; (DC) 12...12 V; (DC) 12...12 V
Rated Frequency (f)50...60 Hz
Power LossTotal 15.5 W
Number of Contacts CO0
Number of Contacts NC0
Number of Contacts NO1
Ambient Air TemperatureOperation -25 ... +60 °C; Storage -40 ... +70 °C
Degree of Protectionacc. to IEC 60529 IP20
Environmental Information2CCY413207D0203
Product Net Width27 mm
Product Net Height95 mm
Product Net Depth / Length82.5 mm
Dimension Diagram2CCC413003C0201
EPLAN Data9AAC212941_EPLAN
Declaration of Conformity - CE9AKK108472A2536
Instructions and Manuals9AKK106930A3418
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715; TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting PositionAny
ETIM 9EC001023 - Shunt release (for power circuit breaker)
UNSPSC39121601
eClassV11.0 : 27370418
IDEA Granular Category Code (IGCC)4879 >> Shunt release (for power circuit breaker)
Object Classification CodeF
StandardsIEC/EN 60947-2
Suitable for off-load switchNo
Suitable for overload relayYes
Type of electric connectionScrew connection
Rated control supply voltage AC 50 Hz12 V
Rated control supply voltage AC 60 Hz12 V
Rated control supply voltage DC12 V
Suitable for motor safety switchNo
Suitable for power circuit breakerYes
Voltage type for actuatingAC/DC
Number of contacts as normally open contact1
Country of originSwitzerland

Properties

MOQ1

Cross-References

Attached Documents