Low-Voltage Circuit Breaker Coordination and Selectivity

Design guide compiled by cBallast. 4-page PDF; the full content is on this page.
Compiled by
cBallast
Subject
MCB, MCCB, ACB — low-voltage protection
Document type
Design guide
Reference
IEC 60364-5-53 : 2020
Issued
2026-07-14
Pages
4
Format
Web page and PDF

Circuit breaker coordination and selectivity for low-voltage industrial installations. Covers the three coordination strategies — full selectivity, partial selectivity, and cascading — and how to read manufacturer selectivity tables. Includes worked examples for MCB-MCB, MCCB-MCB, and ACB-MCCB combinations at prospective short-circuit currents up to 50 kA.

Why coordination matters

In a low-voltage distribution board, several breakers stand in series between the incoming supply and the final load. A fault at any point should trip only the nearest upstream breaker, isolating the smallest possible portion of the installation. If instead the upstream breaker trips before the downstream one, the fault has cascaded and every load fed through the upstream breaker goes dark unnecessarily. Coordinated selectivity is the design discipline that prevents cascading.

The three coordination strategies

StrategyMeaningUse when
Full selectivityDownstream breaker always trips first, at any current up to its own Icn. Upstream stays closed.Critical loads, hospital IT panels, data centres
Partial (limited) selectivitySelectivity holds up to a defined limit current (Is). Above Is both breakers trip.General industrial, where a rare severe fault can be tolerated
Cascading (back-up protection)Downstream breaker has lower Icn than the prospective short-circuit current at its terminals. Upstream breaker helps interrupt, but both trip.Cost-driven design where selectivity is not required; supply protection to a small sub-panel

Coordination principles

Reading a manufacturer selectivity table

Each major OEM (Schneider, ABB, Siemens, Eaton, Hager) publishes selectivity tables listing every pairing of their own breakers as (Is) selectivity-limit currents. The buyer picks the upstream breaker on the left column and the downstream on the top row; the cell entry is the maximum fault current up to which selectivity is preserved. "T" or "∞" indicates total selectivity to the upstream's Icu.

Worked example — ACB-MCCB-MCB three-level

LevelBreakerRatingIcu (kA)Setting
Main incomer (ACB)ABB Emax E2.2N2000 A65Ir = 1.0 × In, Isd = 5 × In, tsd = 200 ms
Sub-distribution (MCCB)ABB Tmax XT4 250250 A36Ir = 0.8 × In, Isd = 8 × Ir, instantaneous
Final circuit (MCB)ABB S203 C6363 A10C curve (5-10 × In magnetic)

At a fault of 5 kA on the final circuit: MCB clears in < 10 ms. The MCCB sees 5 kA in its magnetic band but the intentional 40 ms delay from the MCCB's zone-selective interlock (ZSI) with the MCB prevents it tripping. The ACB sees 5 kA well below its 200 ms short-time delay window and holds. Only the S203 trips. Full selectivity achieved.

Common cascading examples

UpstreamDownstreamIcu of downstreamEnhanced Icu with cascading
Schneider iC60N 63 ASchneider iC60H 20 A10 kA50 kA (back-up)
ABB S203 32 AABB S201 6 A6 kA25 kA (back-up)
ABB Tmax XT2 160ABB S203 63 A10 kA36 kA (back-up)

Related on cBallast

Frequently asked questions

What is selectivity between circuit breakers?
Selectivity (discrimination) means that for a fault anywhere in the installation, only the breaker immediately upstream of the fault opens, and all breakers closer to the source stay closed.
What is the difference between total and partial selectivity?
Total selectivity holds for every fault current up to the downstream breaker's breaking capacity; partial selectivity holds only up to a stated limit current, above which both devices may trip.
What is back-up (cascading) protection?
The opposite trade: an upstream breaker helps clear faults beyond the downstream breaker's own rating — for example a 10 kA MCB backed to 50 kA by the upstream device per the manufacturer's coordination tables. It raises fault withstand but sacrifices selectivity at high currents.
How is selectivity verified?
With the manufacturers' published selectivity and let-through tables (or software), never by comparing catalogue trip curves alone — dynamic let-through below 0.1 s does not show on time–current curves.
Open / Download PDF

Compiled by cBallast for identification and cross-reference. Part numbers, designations and trademarks belong to their respective manufacturers. Confirm ratings and dimensions against the manufacturer's current documentation and the nameplate of the installed equipment before ordering or installation.