cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

16-Channel digital output; 24 VDC; 0.5 A (750-1504)

WAGO · Control & Automation · I/O Modules
Part Number
750-1504  ·  HS 8537.10
16-Channel digital output; 24 VDC; 0.5 A (750-1504)

WAGO 750-1504 Manufacturer description: 16-channel digital output; 24 VDC; 0.5 A. 16-channel digital output; 24 V DC; 0,5 A.

Technical Specifications

Manufacturer part number (MPN)750-1504
EAN / GTIN4045454905576
Sales unitpcs
Number of digital outputs16
Total number of channels (module)16
Signal typeDigital
Signal type (voltage)24 VDC
Actuator connection16 x (1-wire)
Output characteristichigh-side switching
Output current per channel0.5 A
Output currentshort-circuit-protected
Load typeResistive, inductive, lamp load
Switching frequency (max.)1 kHz
Output data width (internal) max.16 Bit
Supply voltage (system)5 VDC; via data contacts
Current consumption (system supply)40 mA
Supply voltage (field)24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact)
Current consumption, field supply (module with no external load)29 mA
Isolation500 V system/field
IndicatorsLED (1-16) green: Status DO 1 … DO 16
Number of incoming power jumper contacts2
Number of outgoing power jumper contacts2
Current carrying capacity (power jumper contacts)10 A
Connection technologyI/O: 16 x Push-in CAGE CLAMP® (outputs)
Connectable conductor materialsCopper
Connection typeOutput
Solid conductor0.08 … 1.5 mm² / 28 … 16 AWG
Fine-stranded conductor0.25 … 1.5 mm² / 22 … 16 AWG
Strip length8 … 9 mm / 0.31 … 0.35 inches
Width12 mm / 0.472 inches
Height100 mm / 3.937 inches
Depth69 mm / 2.717 inches
Depth from upper-edge of DIN-rail61.8 mm / 2.433 inches
Mounting typeDIN-35 rail
Pluggable connectorfixed
Colorlight gray
Housing materialPolycarbonate; polyamide 6.6
Fire load1.039 MJ
Weight49.9 g
Conformity markingCE
Ambient temperature (operation)0 … +55 °C
Ambient temperature (storage)-40 … +85 °C
Protection typeIP20
Pollution degree2 per IEC 61131-2
Operating altitude0 … 2000 m / 0 … 6562 ft
Mounting positionHorizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Relative humidity (without condensation)95 %
Vibration resistance4g per IEC 60068-2-6
Shock resistance15g per IEC 60068-2-27
EMC immunity to interferenceper EN 61000-6-2, marine applications
EMC emission of interferenceper EN 61000-6-3, marine applications
Exposure to pollutantsper IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 %10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 %25 ppm
Product Group15 (I/O System)
PU (SPU)1 pcs
Packaging typeBox
Country of originDE
Customs tariff number85371098990
UNSPSC32,151,705
eCl@ss 10.027-24-26-04
eCl@ss 9.027-24-26-04
ETIM 9.0EC001599
ETIM 10.0EC001599
ECCNNO US CLASSIFICATION
CAS-No.1303-86-2 | 1317-36-8 | 7439-92-1 | 75980-60-8
REACH Candidate Strip SubstanceDiboron trioxide | Lead | Lead monoxide | Phosphine oxide, diphenyl(2,4,6-trimethylbenzoyl)-
RoHS Compliance StatusCompliant,With Exemption
RoHS Exemption7(a) | 7(c)-I | 7(c)-II
SCIP notification number (Austria)b0f045e7-d178-4dff-b357-d4b87e122ddc
SCIP notification number (Belgium)8fdf9103-120e-41da-962e-8a4778a35cb8
SCIP notification number (Bulgaria)ccf699ac-4477-4350-b857-2039b462633f
SCIP notification number (Czech Republic)4bff8e53-ecae-4fd6-b3a4-cdc43fd20f6c
SCIP notification number (Denmark)3c965ddd-cfc2-420e-a09f-5a4d8781b588
SCIP notification number (Finland)a21bd430-05dc-4484-9a0f-df5b014b19c7
SCIP notification number (France)2cb79c20-e6f8-4390-bfa3-116908b95fbd
SCIP notification number (Germany)4aa764fe-e251-4558-a80d-978e6aab38f6
SCIP notification number (Hungary)3f3aaf6d-4879-494c-a3d5-dcc0fceeed75
SCIP notification number (Italy)acf1ab18-af25-4b22-8f12-099a85a225ed
SCIP notification number (Netherlands)d5ef9f95-5357-4bda-9d79-c6f6f8a5b219
SCIP notification number (Poland)0a5ecd33-c7b9-47f4-b94d-70c567167514
SCIP notification number (Romania)1cba2f0c-edbb-4944-b423-d60e0bc174c7
SCIP notification number (Sweden)c0209038-643d-44c6-8b33-8c198fb02536
Certified for UL hazardous location division 1Yes
Certified for UL hazardous location division 2No
Certified for UL hazardous location group A (acetylene)Yes
Certified for UL hazardous location group B (hydrogen)Yes
Certified for UL hazardous location group C (ethylene)Yes
Certified for UL hazardous location group D (propane)Yes
Certified for UL hazardous location group E (metal dusts)No
Certified for UL hazardous location class IYes
Certified for UL hazardous location class IINo
Certified for UL hazardous location class IIINo
Supporting protocol for EtherCATNo
Supply voltage DC24 V
Voltage type (supply voltage)DC
Number of digital inputs16
Digital inputs configurableNo
Digital outputs configurableNo
Permitted voltage at input24 V
Type of voltage (input voltage)DC
Type of digital outputTransistor
Permitted voltage at output24 V
Type of output voltageDC
Short-circuit protection, outputs availableYes
With optical interfaceNo
Supporting protocol for TCP/IPNo
Supporting protocol for PROFIBUSNo
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for ASINo
Supporting protocol for KNXNo
Supporting protocol for ModbusNo
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for LONNo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFINET CBANo
Supporting protocol for SERCOSNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for EtherNet/IPNo
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for INTERBUS-SafetyNo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Supporting protocol for other bus systemsNo
Radio standard BluetoothNo
Radio standard WLAN 802.11No
Radio standard GPRSNo
Radio standard GSMNo
Mobile communications standard 3G (UMTS)No
IO link masterNo
System accessoryNo
Degree of protection (IP)IP20
Type of electric connectionSpring clamp connection
Time delay at signal change3 ms
Fieldbus connection over separate bus coupler possibleYes
Suitable for rail mountingYes
Wall mounting/direct mountingNo
Front built-in possibleNo
Rack-assembly possibleNo
Suitable for safety functionsNo
SIL according to IEC 61508None
Performance level according to EN ISO 13849-1None
Appendant operation agent (Ex ia)No
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustATEX dust-ex-protection, Cat. 3D

Properties

MOQ1

Cross-References

Attached Documents