| Manufacturer part number (MPN) | ZBE201 |
| EAN / GTIN | 3389110177442 |
| Sales unit | pcs |
| Package quantity | 5 pcs |
| Contact configuration | 1 NO |
| Range of product | Harmony XB4; Harmony XB5 |
| Product or component type | Contact block |
| Device short name | ZBE |
| Sale per indivisible quantity | 5 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Contact operation | Early make |
| Contact block type | Single |
| Contacts usage | Staggered contacts |
| Connections - terminals | Screw clamp terminals, = 1 x 0.22 mm² without cable end conforming to IEC 60947-1 |
| Product weight | 0.011 kg |
| Contacts type and composition | 1 NO |
| Positive opening | Without |
| Operating travel | 2.6 mm (NO changing electrical state); 4.3 mm (total travel) |
| Operating force | 2.3 N NO changing electrical state |
| Mechanical durability | 10000000 cycles |
| Tightening torque | 0.8…1.2 N.m conforming to IEC 60947-1 |
| Shape of screw head | Cross compatible with pozidriv No 1 screwdriver; Slotted compatible with flat Ø 4 mm screwdriver; Slotted compatible with flat Ø 5.5 mm screwdriver |
| Contacts material | Silver alloy (Ag/Ni) |
| Short-circuit protection | 10 A cartridge fuse type gG conforming to IEC 60947-5-1 |
| [Ith] conventional free air thermal current | 10 A conforming to IEC 60947-5-1 |
| [Ui] rated insulation voltage | 600 V (pollution degree 3) conforming to IEC 60947-1 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-1 |
| [Ie] rated operational current | 3 A at 240 V, AC-15, A300 conforming to IEC 60947-5-1; 6 A at 120 V, AC-15, A300 conforming to IEC 60947-5-1; 0.1 A at 600 V, DC-13, Q300 conforming to IEC 60947-5-1; 0.27 A at 250 V, DC-13, Q300 conforming to IEC 60947-5-1; 0.55 A at 125 V, DC-13, Q300 conforming to IEC 60947-5-1 |
| Electrical durability | 1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C; 1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C; 1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C; 1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C; 1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C |
| Mounting of block | Front mounting |
| Electrical composition code | C1 (quantity <= 9); C2 (quantity <= 7); C3 (quantity <= 6); C4 (quantity <= 4); C5 (quantity <= 5); C6 (quantity <= 3); C7 (quantity <= 4); C8 (quantity <= 2); C9 (quantity <= 3); C12 (quantity <= 6); M1 (quantity <= 6); M2 (quantity <= 4); M3 (quantity <= 4); M5 (quantity <= 2); M6 (quantity <= 2); M7 (quantity <= 6); M8 (quantity <= 4); M9 (quantity <= 2); SF1 (quantity <= 3); SF2 (quantity <= 2); MF1 (quantity <= 2); MF2 (quantity <= 2); C10 (quantity <= 2); M4 (quantity <= 2); C13 (quantity <= 1) |
| Protective treatment | TH |
| Ambient air temperature for storage | -40…70 °C |
| Ambient air temperature for operation | -40…70 °C |
| Standards | UL 508; IEC 60947-5-4; IEC 60947-1; JIS C8201-5-1; IEC 60947-5-1; CSA C22.2 No 14; JIS C8201-1 |
| Product certifications | DNV; GOST; BV; UL; CCC; CSA; LROS (Lloyds register of shipping) |
| Vibration resistance | 5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 30 gn (duration = 18 ms) for half its wave acceleration conforming to IEC 60068-2-27; 50 gn (duration = 11 ms) for half its wave acceleration conforming to IEC 60068-2-27 |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 5 |
| Number of Units in Package 3 | 800 |
| Country of origin | FR |
| Warranty (in months) | 18 |