Telemecanique RM17TE00 The relay detects all possible faults that may occur in a three-phase system (phase loss, phase sequence, overvoltage and undervoltage).
| Manufacturer part number (MPN) | RM17TE00 EAN / GTIN: 3389119405058 HS code: 8536.90 Sales unit: pcs Package quantity: 48 pcs Voltage: 208-480 V AC Rated current: 5 A Range of product: Harmony Control Relays Relay type: Multifunction control relay Relay name: RM17TE Product or component type: 3-phase control relay Relay monitored parameters: Undervoltage and overvoltage in window mode; Asymmetry; Phase sequence; Phase failure detection Control type: Without test button Contacts type and composition: 1 C/O [Uc] control circuit voltage: 208...480 V Product specific application: For 3-phase supply [Us] rated supply voltage: self-powered Supply voltage limits: 183…528 V AC Supply frequency: 50/60 Hz +/- 10 % Power consumption in VA: 0…22 VA at 400 V AC 50 Hz Measurement range: 208...480 V AC Measurement voltage limits: 183…528 V AC Maximum measuring cycle: 150 ms measurement cycle as true rms value Threshold adjustment voltage: 2...20 % of Un selected; -2...-17 % in the range 220 V AC; +2.. |
| MOQ | 1 |