Siemens SIMATIC S7 automation module 6ES7531-7KF00-0AB0

Siemens · Control & Automation · PLCs · Germany · siemens.com
Part Number
6ES7531-7KF00-0AB0  ·  HS 8538.90
Image not available for this product

Siemens 6ES7531-7KF00-0AB0 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform. Simatic S7 1500 AI 8 X U/In/RTD/TC, 8 channels in group on 8.

Technical Specifications

Manufacturer part number (MPN)6ES7531-7KF00-0AB0
EAN / GTIN4025515079514
Sales unitpcs
Product type designationAI 8xU/I/RTD/TC ST
Product familySM 531 analog input module
HW functional statusFS04
Firmware versionV2.0.0
Engineering with STEP 7 TIA Portal fromV12
Supply voltage rated value (DC)24 V
Supply voltage permissible range19.2 ... 28.8 V
Reverse polarity protectionYes
Current consumption, max.255 mA at 19.2 V
24 V encoder supply output current, max.20 mA
Power consumption from backplane bus0.7 W
Power loss, typ.2.7 W
Address space inputs16 byte
Number of analog inputs8
Analog inputs for current measurement8
Analog inputs for voltage measurement8
Analog inputs for RTD measurement4
Analog inputs for thermocouple measurement8
Resolution incl. sign, max.16 bit
Measurement principleintegrating
Voltage input ranges±10 V, ±5 V, ±2.5 V, ±1 V, 1–5 V, ±80/250/500 mV
Current input ranges0–20 mA, ±20 mA, 4–20 mA
Thermocouple typesB, E, J, K, N, R, S, T
RTD typesPt100/200/500/1000, Ni100/1000, LG-Ni1000
Resistance ranges0–150/300/600/6000 Ω, PTC
Permissible input voltage (destruction limit), max.28.8 V
Permissible input current (destruction limit), max.40 mA
Integration time2.5 / 16.67 / 20 / 100 ms
Interference frequency suppression400 / 60 / 50 / 10 Hz
Basic conversion time incl. integration9 / 23 / 27 / 107 ms
Smoothing levels4
Cable length shielded, max.800 m (U/I), 200 m (R/RTD), 50 m (TC)
Linearity error (rel. to input range)±0.02 %
Operational error limit voltage/current/resistance±0.3 %
Basic error limit at 25 °C±0.1 %
Common mode voltage, max.10 V
Common mode interference, min.60 dB
Crosstalk between inputs, max.-80 dB
Diagnosticsdiagnostic alarm, limit value alarm, wire break, overflow/underflow
Diagnostics LEDsRUN (green), ERROR (red), channel status
Isolation tested with707 V DC (type test)
Permissible potential difference inputs to MANA (UCM)10 V DC
Suitable per AMS 2750 / CQI-9Yes
Ambient temperature during operation, horizontal-25 ... +60 °C
Ambient temperature during operation, vertical, max.40 °C
Installation altitude above sea level, max.5 000 m
Dimensions width × height × depth35 × 147 × 129 mm
Weight, approx.310 g
Number of analogue inputs8
Analogue outputs configurableNo
Resolution of the analogue inputs16 Bit
Output, currentNo
Output, voltageNo
Output signal configurableNo
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustNone
Width35 mm
Height147 mm
Depth129 mm
Country of originGermany

Properties

MOQ1

Cross-References