| Manufacturer part number (MPN) | 6ED1052-1MD08-0BA2 |
| EAN / GTIN | 4034106034474 |
| Sales unit | pcs |
| with display | Yes |
| Mounting | on 35 mm DIN rail, 4 spacing units wide |
| Rated value (DC) 12 V DC | Yes |
| Rated value (DC) 24 V DC | Yes |
| permissible supply range, lower limit (DC) | 10.8 V |
| permissible supply range, upper limit (DC) | 28.8 V |
| Time switching clocks Number | 400; Max. 400, function-specific |
| Time switching clocks Power reserve | 480 h |
| Number of digital inputs | 8; Of which 4 can be used in analog mode (0 to 10 V) |
| Number of digital outputs | 4; Relays |
| Short-circuit protection | No; external fusing necessary |
| Output current for signal "1" permissible range for 0 to 55 °C, max. | 10 A |
| Switching capacity of contacts with inductive load, max. | 3 A |
| Switching capacity of contacts with resistive load, max. | 10 A |
| Emission of radio interference acc. to EN 55011 Limit class B, for use in residential areas | Yes |
| CE mark | Yes |
| CSA approval | Yes; covered by UL cert |
| UL approval | Yes |
| FM approval | Yes |
| developed in accordance with IEC 61131 | Yes |
| according to VDE 0631 | Yes |
| Marine approval | Yes |
| Ambient temperature during operation min. | -20 °C; No condensation |
| Ambient temperature during operation max. | 55 °C |
| Ambient temperature during storage/transportation min. | -40 °C |
| Ambient temperature during storage/transportation max. | 70 °C |
| Width | 71.5 mm; 4 modular widths (MW) |
| Height | 90 mm |
| Depth | 60 mm |
| Supporting protocol for EtherCAT | No |
| Supply voltage DC | 10.8–28.8 V |
| Voltage type (supply voltage) | DC |
| Switching current | 10 A |
| Number of analogue inputs | 4 |
| With relay output | Yes |
| Number of HW-interfaces industrial Ethernet | 1 |
| With optical interface | No |
| Supporting protocol for TCP/IP | Yes |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | No |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for ASI | No |
| Supporting protocol for KNX | No |
| Supporting protocol for Modbus | No |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for LON | Yes |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for SERCOS | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for EtherNet/IP | No |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for INTERBUS-Safety | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Supporting protocol for other bus systems | No |
| Radio standard Bluetooth | No |
| Radio standard WLAN 802.11 | No |
| Radio standard GPRS | No |
| Radio standard GSM | No |
| Mobile communications standard 3G (UMTS) | No |
| IO link master | No |
| Redundancy | No |
| Degree of protection (IP) | IP20 |
| Basic device | Yes |
| Expandable | Yes |
| Expansion device | No |
| With time switch clock | Yes |
| Suitable for rail mounting | Yes |
| Wall mounting/direct mounting | Yes |
| Front built-in possible | Yes |
| Rack-assembly possible | No |
| Suitable for safety functions | No |
| Appendant operation agent (Ex ia) | No |
| Explosion safety category for gas | None |
| Explosion safety category for dust | None |
| Country of origin | China |