| Manufacturer part number (MPN) | 6AV2128-3KB06-0AX1 |
| EAN / GTIN | 4047623411918 |
| Sales unit | pcs |
| Product type designation | MTP1000 Unified Comfort |
| Screen diagonal | 10.1 in |
| Display width | 217 mm |
| Display height | 135.6 mm |
| Number of colors | 16 777 216 |
| Backlighting — MTBF backlighting (at 25 °C) | 50 000 h; At 25°C |
| Backlighting — Backlight dimmable | Yes; 5-100 % |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 19.2 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Current consumption (rated value) | 0.5 A |
| Current consumption, max. | 1.1 A |
| Starting current inrush I²t | 0.5 A²·s |
| Number of industrial Ethernet interfaces | 2; 2 ports (switch) + independent port |
| Number of RS 485 interfaces | 1; RS 422 / 485 combined |
| Number of RS 422 interfaces | 0; together with RS 485 |
| Number of USB interfaces | 4; USB 3.1 Gen. 1 (type A) |
| Number of SD card slots | 2 |
| Industrial Ethernet — Number of ports of the integrated switch | 2 |
| Operation (vertical installation) — For vertical installation, min. | 0 °C |
| Operation (vertical installation) — For vertical installation, max. | 50 °C |
| Operation (max. tilt angle) — At maximum tilt angle, min. | 0 °C |
| Operation (max. tilt angle) — At maximum tilt angle, max. | 40 °C |
| Operation (vertical installation, portrait format) — For vertical installation, min. | 0 °C |
| Operation (vertical installation, portrait format) — For vertical installation, max. | 40 °C |
| Operation (max. tilt angle, portrait format) — At maximum tilt angle, min. | 0 °C |
| Operation (max. tilt angle, portrait format) — At maximum tilt angle, max. | 35 °C |
| Ambient temperature during storage/transportation — min. | -20 °C |
| Ambient temperature during storage/transportation — max. | 60 °C |
| Relative humidity — Operation, max. | 90 %; no condensation |
| Online languages — Number of online/runtime languages | 32 |
| Help system — Number of characters per info text | 70 |
| Help system — Number of message texts per message | 10 |
| Message system — Number of alarm classes | 32 |
| Bit messages — Number of bit messages | 9 000 |
| Analog messages — Number of analog messages | 300 |
| Analog messages — Number of characters per message | 512 |
| Analog messages — Number of process values per message | 10 |
| Parameter set management (recipes) — Number of parameter set types | 750 |
| Parameter set management (recipes) — Size of internal parameter set memory | 12 Mbyte |
| Variables — Number of variables per device | 8 000 |
| Variables — Number of variables per screen | 600 |
| Images — Number of configurable images | 1 200 |
| Image objects — Number of objects per image | 800 |
| Complex image objects — Number of complex objects per screen | 40 |
| Lists — Number of text lists per project | 750 |
| Lists — Number of entries per text strip | 750 |
| Lists — Number of graphics lists per project | 750 |
| Lists — Number of entries per graphics strip | 750 |
| Archiving — Number of archives per device | 50 |
| Archiving — Number of entries per archive | 500 000 |
| Security — Number of roles | 50 |
| Security — Number of function rights | 20; number of predefined function rights |
| Security — Number of users | 200 |
| Process coupling — Number of S7 connections | 16 |
| Width of the housing front | 280 mm |
| Height of housing front | 205 mm |
| Mounting cutout, width | 264.6 mm |
| Mounting cutout, height | 189.1 mm |
| Mounting depth | 63.6 mm |
| Supporting protocol for EtherCAT | No |
| Supply voltage DC | 19.2–28.8 V |
| Voltage type (supply voltage) | DC |
| Number of HW-interfaces industrial Ethernet | 2 |
| Number of HW-interfaces RS-485 | 1 |
| Number of HW-interfaces USB | 4 |
| Supporting protocol for TCP/IP | Yes |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | No |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for ASI | No |
| Supporting protocol for KNX | No |
| Supporting protocol for Modbus | Yes |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for LON | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for SERCOS | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for EtherNet/IP | Yes |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for INTERBUS-Safety | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Supporting protocol for other bus systems | Yes |
| Radio standard Bluetooth | No |
| Radio standard WLAN 802.11 | No |
| Radio standard GPRS | No |
| Radio standard GSM | No |
| Mobile communications standard 3G (UMTS) | No |
| IO link master | No |
| Type of display | TFT |
| Colour display | Yes |
| Number of colours of the display | 16777216 |
| Number of pixels, horizontal | 1280 |
| Number of pixels, vertical | 800 |
| With numeric keyboard | Yes |
| With alpha numeric keyboard | Yes |
| Touch technology | Capacitive multitouch |
| With message indication | Yes |
| With message system (incl. buffer and confirmation) | Yes |
| Process value representation (output) possible | Yes |
| Process default value (input) possible | Yes |
| With recipes | Yes |
| With printer output | Yes |
| Number of online languages | 32 |
| Additional software components, loadable | Yes |
| Degree of protection (IP), front side | IP65 |
| Operating temperature | 0–50 °C |
| Suitable for rail mounting | No |
| Wall mounting/direct mounting | No |
| Suitable for safety functions | No |
| Width of the front | 280 mm |
| Height of the front | 205 mm |
| Built-in depth | 63.6 mm |
| Country of origin | Germany |