| Manufacturer part number (MPN) | 6ES7132-6FD00-2BB1 |
| EAN / GTIN | 4047623406792 |
| Sales unit | pcs |
| Package quantity | 10 pcs |
| Product type designation | DQ 4x24 ... 230 V AC/2 A ST |
| HW functional status | From FS05 |
| Firmware version | V1.0 |
| Usable BaseUnits | BU type B1 |
| Color code for module-specific color-coded label | CC41 |
| Product function — I&M data | Yes; I&M0 to I&M3 |
| Engineering with — STEP 7 TIA Portal configurable/integrated from version | V13 / V13 |
| Engineering with — STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| Engineering with — PROFIBUS from GSD version/GSD revision | GSD Revision 5 |
| Engineering with — PROFINET from GSD version/GSD revision | GSDML V2.3 |
| Rated value (AC) | 230 V |
| Permissible range, lower limit (AC) | 20.4 V |
| Permissible range, upper limit (AC) | 264 V |
| Current consumption (rated value) | 11.5 mA |
| Power loss, typ. | 9 W; Active power, load voltage 230 V, all outputs loaded with 2 A, 50 Hz |
| Address space per module — Address space per module, max. | 1 byte; + 1 byte for QI information |
| Address space per module — Inputs | 1 byte; With QI |
| Address space per module — Outputs | 1 byte |
| Selection of BaseUnit for connection variants — 1-wire connection | BU type B1 |
| Selection of BaseUnit for connection variants — 2-wire connection | BU type B1 |
| Selection of BaseUnit for connection variants — 3-wire connection | BU type B1 |
| Selection of BaseUnit for connection variants — 4-wire connection | BU type B1 + potential distributor module |
| Type of digital output | Triac with zero point detection |
| Number of digital outputs | 4 |
| Short-circuit protection | No; When using BU type B1, a miniature, quick-response fuse with 10 A tripping current must be provided |
| Size of motor starters according to NEMA, max. | 5 |
| Switching capacity of the outputs — with resistive load, max. | 2 A |
| Switching capacity of the outputs — on lamp load, max. | 100 W |
| Output voltage — for signal "1", min. | 20.4 V |
| Output current — for signal "1" rated value | 2 A |
| Output current — for signal "1" permissible range, min. | 10 mA |
| Output current — for signal "1" permissible range, max. | 2 A |
| Output current — for signal "0" residual current, max. | 460 µA |
| Output delay with resistive load — "0" to "1", max. | 10 ms |
| Output delay with resistive load — "1" to "0", max. | 10 ms |
| Switching frequency — with resistive load, max. | 10 Hz |
| Switching frequency — with inductive load, max. | 0.5 Hz; Higher frequencies are possible, see Equipment Manual / Product Information |
| Switching frequency — on lamp load, max. | 1 Hz |
| Total current of the outputs — Current per channel, max. | 2 A |
| Total current of the outputs — Current per module, max. | 8 A |
| Horizontal installation — up to 40 °C, max. | 8 A |
| Horizontal installation — up to 50 °C, max. | 6 A |
| Horizontal installation — up to 60 °C, max. | 4 A |
| Vertical installation — up to 30 °C, max. | 8 A |
| Vertical installation — up to 40 °C, max. | 6 A |
| Vertical installation — up to 50 °C, max. | 4 A |
| Cable length — shielded, max. | 1 000 m |
| Cable length — unshielded, max. | 600 m |
| Diagnostics indication LED — Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| Diagnostics indication LED — Channel status display | Yes; green LED |
| Isolation tested with | 2 545 V DC/2 s (routine test) |
| Ambient temperature during operation — horizontal installation, min. | -30 °C |
| Ambient temperature during operation — horizontal installation, max. | 60 °C |
| Ambient temperature during operation — vertical installation, min. | -30 °C |
| Ambient temperature during operation — vertical installation, max. | 60 °C |
| Altitude during operation relating to sea level — Installation altitude above sea level, max. | 2 000 m; On request: Installation altitudes greater than 2 000 m |
| Dimensions — Width | 20 mm |
| Dimensions — Height | 73 mm |
| Dimensions — Depth | 58 mm |
| Weight, approx. | 50 g |
| Voltage type (supply voltage) | AC |
| Type of voltage (input voltage) | AC |
| Output current | 2 A |
| Type of output voltage | AC |
| Degree of protection (IP) | IP20 |
| Explosion safety category for gas | ATEX gas-ex-protection, Cat. 3G |
| Explosion safety category for dust | None |
| Width | 20 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Country of origin | Germany |