Siemens SIMATIC, electronic module for ET200ISP, 4 AO HART, 4 - 20 mA, for connecting HART field devices (6ES7135-7TD00-0AB0)

Siemens · Control & Automation · PLCs & Industrial Networking · Germany · siemens.com
Part Number
6ES7135-7TD00-0AB0  ·  HS 8538.90
Siemens SIMATIC, electronic module for ET200ISP, 4 AO HART, 4 - 20 mA, for connecting HART field devices (6ES7135-7TD00-0AB0)

Siemens 6ES7135-7TD00-0AB0 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform.

Technical Specifications

Manufacturer part number (MPN)6ES7135-7TD00-0AB0
EAN / GTIN4019169131681
Sales unitpcs
Product type designation4AQ I HART
HW functional status17
Firmware versionV3.0.4
Rack mountingNo
Front mountingYes
Rail mountingYes
Wall mounting/direct mountingNo
Type of supply voltageDC
Permissible range, lower limit (DC)20.4 V
Permissible range, upper limit (DC)28.8 V
Current consumption, typ.295 mA
From load voltage (power bus), max.330 mA
Power loss, typ.2.7 W
Fieldbus connection via separate transceiverYes
Number of analog outputs4
Cycle time (all channels) max.3.6 ms
Voltage signal at analog outputNo
Current signal at analog outputYes
Output ranges, current — 0 to 20 mAYes
Output ranges, current — 4 mA to 20 mAYes
Load impedance (in rated range of output) — with current outputs, max.750 Ω
Cable length — shielded, max.500 m
Integration and conversion time/resolution per channel — Resolution with overrange (bit including sign), max.14 bit
Settling time — for resistive load4 ms
Settling time — for capacitive load40 ms
Settling time — for inductive load40 ms
Linearity error (relative to output range), (+/-)0.015 %
Temperature error (relative to output range), (+/-)0.005 %/K
Crosstalk between the outputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.01 %
Operational error limit in overall temperature range — Current, relative to output range, (+/-)0.15 %
Basic error limit (operational limit at 25 °C) — Current, relative to output range, (+/-)0.1 %
Number of PROFINET interfaces0
Diagnoses — Wire breakYes; I load > 1 mA
Diagnoses — Short-circuitYes; I load > 1 mA
Module for Ex(i) protectionYes; for more Co/Lo combinations, see certificate IECEx KEM 05.0012
Maximum values for connecting terminals for gas group IIC — Uo (no-load voltage), max.27.6 V
Maximum values for connecting terminals for gas group IIC — Io (short-circuit current), max.88.2 mA
Maximum values for connecting terminals for gas group IIC — Po (power output), max.0.61 mW
Maximum values for connecting terminals for gas group IIC — Co (permissible external capacity), max.83 nF
Maximum values for connecting terminals for gas group IIC — Lo (permissible external inductivity), max.3 mH
IP degree of protectionIP30
CE markCE 0344
UKCA markDEKRA 21UKEX0091 Importer UK: Siemens plc Manchester M20 2UR
CULusLISTED E334384
FM approvalCLASSIFIED 3025852
INMETRO certificateUL-BR 12.0070
Use in hazardous areas — ATEX markingII 2 G (1) G Ex ib [ia Ga] IIC T4 Gb II 2 G (1) D Ex ib [ia IIIC Da] IIC T4 Gb I M2 Ex ib [ia] I Mb
Use in hazardous areas — ATEX certificateKEMA 04 ATEX 1250
Use in hazardous areas — IECExIECEx KEM 05.0012
Use in hazardous areas — CCC Ex2020322316002946
Use in hazardous areas — EAC ExPB Ex ib [ia] I Mb 1Ex ib [ia Ga] IIC T4 Gb [Ex ia Da] IIIC
Use in hazardous areas — FM markingClass I, Zone 1 AEx ib [ia] IIC T4 Ex ib IIC T4 NI, Class I, DIV.2, GP. A,B,C,D T4 AIS, Class I, DIV.1, GP. A,B,C,D T4 DIP Class II, III, GP. E,F,G
Use in hazardous areas — Explosion protection category for gasATEX gas explosion protection, Zone 1
Use in hazardous areas — Explosion protection category for dustATEX dust explosion protection, Zone 21 always install in corresponding enclosure
Design of electrical connectionScrew/spring-type terminal
Dimensions — Width30 mm
Dimensions — Height129 mm
Dimensions — Depth136.5 mm
Weight, approx.265 g
Voltage type (supply voltage)DC
Resolution of the analogue outputs14 Bit
Number of analogue outputs4
Degree of protection (IP)IP30
Type of electric connectionScrew-/spring clamp connection
Explosion safety category for gasATEX gas-ex-protection, Cat. 2G
Explosion safety category for dustATEX dust-ex-protection, Cat. 2D
Width30 mm
Height129 mm
Depth136.5 mm
Country of originGermany

Properties

MOQ1

Cross-References