cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Siemens SIMATIC, electronic module for ET200ISP, 4 AI HART, 2-Wire transducer, for connecting HART 2-Wire transmitters (6ES7134-7TD00-0AB0)

Siemens · Control & Automation · PLCs & Industrial Networking · Germany · siemens.com
Part Number
6ES7134-7TD00-0AB0  ·  HS 8544.42
Siemens SIMATIC, electronic module for ET200ISP, 4 AI HART, 2-Wire transducer, for connecting HART 2-Wire transmitters (6ES7134-7TD00-0AB0)

Siemens 6ES7134-7TD00-0AB0 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform.

Technical Specifications

Manufacturer part number (MPN)6ES7134-7TD00-0AB0
EAN / GTIN4019169131667
HS code8544.42
Sales unitpcs
Product type designation4AI I 2WIRE HART
HW functional status17
Firmware versionV3.0.4
Rack mountingNo
Front mountingYes
Rail mountingYes
Wall mounting/direct mountingNo
Type of supply voltageDC
Permissible range, lower limit (DC)20.4 V
Permissible range, upper limit (DC)28.8 V
Current consumption, typ.280 mA
From load voltage (power bus), max.320 mA
Power supply to the transmitters — short-circuit proofYes
Power supply to the transmitters — Supply current, max.23 mA; per channel
Power loss, typ.2.7 W
Number of analog inputs4
Permissible input current for current input (destruction limit), max.90 mA
Cycle time (all channels) max.120 ms; 30 ms basic conversion time x4 channels with 60 Hz, 50 Hz interference frequency suppression
Cable length — shielded, max.500 m
Integration and conversion time/resolution per channel — Resolution with overrange (bit including sign), max.13 bit
Smoothing of measured values — ParameterizableYes; in 4 stages
Smoothing of measured values — StepNone: Yes; 1x cycle time
Connection of signal encoders — Burden of 2-wire transmitter, max.750 Ω
Linearity error (relative to input range), (+/-)0.015 %
Temperature error (relative to input range), (+/-)0.005 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.01 %
Operational error limit in overall temperature range — Current, relative to input range, (+/-)0.15 %
Basic error limit (operational limit at 25 °C) — Current, relative to input range, (+/-)0.1 %
Number of PROFINET interfaces0
Diagnoses — Wire breakYes; I load < 3.6 mA
Diagnoses — Short-circuitYes; I load > 25 mA
Module for Ex(i) protectionYes; for more Co/Lo combinations, see certificate IECEx KEM 05.0006
Maximum values for connecting terminals for gas group IIC — Uo (no-load voltage), max.27.6 V
Maximum values for connecting terminals for gas group IIC — Io (short-circuit current), max.88.2 mA
Maximum values for connecting terminals for gas group IIC — Po (power output), max.610 mW
Maximum values for connecting terminals for gas group IIC — Co (permissible external capacity), max.83 nF
Maximum values for connecting terminals for gas group IIC — Lo (permissible external inductivity), max.3 mH
IP degree of protectionIP30
CE markCE 0344
UKCA markDEKRA 21UKEX0089 Importer UK: Siemens plc Manchester M20 2UR
CULusLISTED E334384
FM approvalCLASSIFIED 3025852
INMETRO certificateUL-BR 12.0072
Use in hazardous areas — ATEX markingII 2 G (1) G Ex ib [ia Ga] IIC T4 Gb II 2 G (1) D Ex ib [ia IIIC Da] IIC T4 Gb I M2 Ex ib [ia] I Mb
Use in hazardous areas — ATEX certificateKEMA 04 ATEX 1244
Use in hazardous areas — IECExIECEx KEM 05.0006
Use in hazardous areas — CCC Ex2020322316002941
Use in hazardous areas — EAC ExPB Ex ib [ia] I Mb 1Ex ib [ia Ga] IIC T4 Gb [Ex ia Da] IIIC
Use in hazardous areas — FM markingClass I, Zone 1 AEx ib [ia] IIC T4 Ex ib IIC T4 NI, Class I, DIV.2, GP. A,B,C,D T4 AIS, Class I, DIV.1, GP. A,B,C,D T4 DIP Class II, III, GP. E,F,G
Use in hazardous areas — Explosion protection category for gasATEX gas explosion protection, Zone 1
Use in hazardous areas — Explosion protection category for dustATEX dust explosion protection, Zone 21 always install in corresponding enclosure
Design of electrical connectionScrew/spring-type terminal
Dimensions — Width30 mm
Dimensions — Height129 mm
Dimensions — Depth136.5 mm
Weight, approx.230 g

Properties

MOQ1

Cross-References

Attached Documents