| Manufacturer part number (MPN) | 6ES7134-7TD00-0AB0 |
| EAN / GTIN | 4019169131667 |
| HS code | 8544.42 |
| Sales unit | pcs |
| Product type designation | 4AI I 2WIRE HART |
| HW functional status | 17 |
| Firmware version | V3.0.4 |
| Rack mounting | No |
| Front mounting | Yes |
| Rail mounting | Yes |
| Wall mounting/direct mounting | No |
| Type of supply voltage | DC |
| Permissible range, lower limit (DC) | 20.4 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Current consumption, typ. | 280 mA |
| From load voltage (power bus), max. | 320 mA |
| Power supply to the transmitters — short-circuit proof | Yes |
| Power supply to the transmitters — Supply current, max. | 23 mA; per channel |
| Power loss, typ. | 2.7 W |
| Number of analog inputs | 4 |
| Permissible input current for current input (destruction limit), max. | 90 mA |
| Cycle time (all channels) max. | 120 ms; 30 ms basic conversion time x4 channels with 60 Hz, 50 Hz interference frequency suppression |
| Cable length — shielded, max. | 500 m |
| Integration and conversion time/resolution per channel — Resolution with overrange (bit including sign), max. | 13 bit |
| Smoothing of measured values — Parameterizable | Yes; in 4 stages |
| Smoothing of measured values — Step | None: Yes; 1x cycle time |
| Connection of signal encoders — Burden of 2-wire transmitter, max. | 750 Ω |
| Linearity error (relative to input range), (+/-) | 0.015 % |
| Temperature error (relative to input range), (+/-) | 0.005 %/K |
| Crosstalk between the inputs, min. | -50 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.01 % |
| Operational error limit in overall temperature range — Current, relative to input range, (+/-) | 0.15 % |
| Basic error limit (operational limit at 25 °C) — Current, relative to input range, (+/-) | 0.1 % |
| Number of PROFINET interfaces | 0 |
| Diagnoses — Wire break | Yes; I load < 3.6 mA |
| Diagnoses — Short-circuit | Yes; I load > 25 mA |
| Module for Ex(i) protection | Yes; for more Co/Lo combinations, see certificate IECEx KEM 05.0006 |
| Maximum values for connecting terminals for gas group IIC — Uo (no-load voltage), max. | 27.6 V |
| Maximum values for connecting terminals for gas group IIC — Io (short-circuit current), max. | 88.2 mA |
| Maximum values for connecting terminals for gas group IIC — Po (power output), max. | 610 mW |
| Maximum values for connecting terminals for gas group IIC — Co (permissible external capacity), max. | 83 nF |
| Maximum values for connecting terminals for gas group IIC — Lo (permissible external inductivity), max. | 3 mH |
| IP degree of protection | IP30 |
| CE mark | CE 0344 |
| UKCA mark | DEKRA 21UKEX0089 Importer UK: Siemens plc Manchester M20 2UR |
| CULus | LISTED E334384 |
| FM approval | CLASSIFIED 3025852 |
| INMETRO certificate | UL-BR 12.0072 |
| Use in hazardous areas — ATEX marking | II 2 G (1) G Ex ib [ia Ga] IIC T4 Gb II 2 G (1) D Ex ib [ia IIIC Da] IIC T4 Gb I M2 Ex ib [ia] I Mb |
| Use in hazardous areas — ATEX certificate | KEMA 04 ATEX 1244 |
| Use in hazardous areas — IECEx | IECEx KEM 05.0006 |
| Use in hazardous areas — CCC Ex | 2020322316002941 |
| Use in hazardous areas — EAC Ex | PB Ex ib [ia] I Mb 1Ex ib [ia Ga] IIC T4 Gb [Ex ia Da] IIIC |
| Use in hazardous areas — FM marking | Class I, Zone 1 AEx ib [ia] IIC T4 Ex ib IIC T4 NI, Class I, DIV.2, GP. A,B,C,D T4 AIS, Class I, DIV.1, GP. A,B,C,D T4 DIP Class II, III, GP. E,F,G |
| Use in hazardous areas — Explosion protection category for gas | ATEX gas explosion protection, Zone 1 |
| Use in hazardous areas — Explosion protection category for dust | ATEX dust explosion protection, Zone 21 always install in corresponding enclosure |
| Design of electrical connection | Screw/spring-type terminal |
| Dimensions — Width | 30 mm |
| Dimensions — Height | 129 mm |
| Dimensions — Depth | 136.5 mm |
| Weight, approx. | 230 g |