Siemens SIMATIC ET 200SP AQ 2 X U/I High Feature (6ES7135-6HB00-0CA1)

Siemens · Control & Automation · PLCs & Industrial Networking · Germany · siemens.com
Part Number
6ES7135-6HB00-0CA1  ·  HS 8538.90
Siemens SIMATIC ET 200SP AQ 2 X U/I High Feature (6ES7135-6HB00-0CA1)

Siemens 6ES7135-6HB00-0CA1 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform. ET200SP AQ2x U/In HF.

Technical Specifications

Manufacturer part number (MPN)6ES7135-6HB00-0CA1
EAN / GTIN4047623403371
Sales unitpcs
Product type designationAQ 2xU/I HF
HW functional statusfrom FS21
Firmware versionV1.0.3
Usable BaseUnitsBU type A0, A1
Color code for module-specific color-coded labelCC00
Product function — I&M dataYes; I&M0 to I&M3
Product function — Isochronous modeYes; 250 µs
Engineering with — STEP 7 TIA Portal configurable/integrated from versionV13 / V13
Engineering with — STEP 7 configurable/integrated from versionV5.5 SP3 / -
Engineering with — PCS 7 configurable/integrated from versionV8.1 SP1
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Current consumption (rated value)45 mA; without load
Current consumption, max.90 mA; 2 channels current output 20 mA
Power loss, typ.0.9 W
Address space per module — Address space per module, max.4 byte; + 1 byte for QI information
Number of analog outputs2
Voltage output, short-circuit current, max.45 mA
Cycle time (all channels), min.750 µs
Output ranges, voltage — 0 to 10 VYes; 15 bit
Output ranges, voltage — 1 V to 5 VYes; 13 bit
Output ranges, voltage — -5 V to +5 VYes; 15 bit incl. sign
Output ranges, voltage — -10 V to +10 VYes; 16 bit incl. sign
Output ranges, current — 0 to 20 mAYes; 15 bit
Output ranges, current — -20 mA to +20 mAYes; 16 bit incl. sign
Output ranges, current — 4 mA to 20 mAYes; 14 bit
Load impedance (in rated range of output) — with voltage outputs, min.2 kΩ
Load impedance (in rated range of output) — with voltage outputs, capacitive load, max.1 µF
Load impedance (in rated range of output) — with current outputs, max.500 Ω
Load impedance (in rated range of output) — with current outputs, inductive load, max.1 mH
Destruction limits against externally applied voltages and currents — Voltages at the outputs30 V
Cable length — shielded, max.1 000 m; 200 m for voltage output
Integration and conversion time/resolution per channel — Resolution with overrange (bit including sign), max.16 bit
Settling time — for resistive load0.05 ms
Settling time — for capacitive load0.05 ms; Max. 47 nF and 20 m cable length
Settling time — for inductive load0.05 ms
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)0.02 %
Linearity error (relative to output range), (+/-)0.03 %
Temperature error (relative to output range), (+/-)0.003 %/K
Crosstalk between the outputs, max.-50 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.03 %
Operational error limit in overall temperature range — Voltage, relative to output range, (+/-)0.2 %
Operational error limit in overall temperature range — Current, relative to output range, (+/-)0.2 %
Basic error limit (operational limit at 25 °C) — Voltage, relative to output range, (+/-)0.1 %
Basic error limit (operational limit at 25 °C) — Current, relative to output range, (+/-)0.1 %
Execution and activation time (TCO), min.500 µs
Bus cycle time (TDP), min.750 µs
Jitter, max.5 µs
Isolation tested with707 V DC (type test)
Ambient temperature during operation — horizontal installation, min.-30 °C; < 0 °C as of FS04
Ambient temperature during operation — horizontal installation, max.60 °C
Ambient temperature during operation — vertical installation, min.-30 °C; < 0 °C as of FS04
Ambient temperature during operation — vertical installation, max.50 °C
Altitude during operation relating to sea level — Installation altitude above sea level, max.5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200SP System Manual
Absolute humidity — dew point, min.-60 °C; suitable for dry room applications
Dimensions — Width15 mm
Dimensions — Height73 mm
Dimensions — Depth58 mm
Weight, approx.31 g
Supporting protocol for EtherCATNo
Voltage type (supply voltage)DC
Input, currentNo
Input, voltageNo
Input, resistorNo
Input, resistance thermometerNo
Input, thermocoupleNo
Input signal, configurableNo
Resolution of the analogue outputs16 Bit
Number of analogue outputs2
Analogue inputs configurableNo
Degree of protection (IP)IP20
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustNone
Width15 mm
Height73 mm
Depth58 mm
Country of originGermany