cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Siemens SIMATIC S7 automation module 6ES7215-1HG40-0XB0

Siemens · Control & Automation · PLCs · Germany · siemens.com
Part Number
6ES7215-1HG40-0XB0  ·  HS 8537.10
Image not available for this product

Siemens 6ES7215-1HG40-0XB0 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform. Simatic S7-1200, CPU 1215C, 2 Profinett porter, 14DI24VDC, 10DO24VDC, 2AI0-10V DC,2AO 0-20MADC,.

Technical Specifications

Manufacturer part number (MPN)6ES7215-1HG40-0XB0
EAN / GTIN4047623402763
Sales unitpcs
Product type designationCPU 1215C DC/DC/relay
Firmware versionV4.7
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Load voltage L+ – Rated value (DC)24 V
Current consumption (rated value)500 mA; CPU only
Current consumption, max.1 500 mA; CPU with all expansion modules
Inrush current, max.12 A; at 28.8 V DC
I²t0.8 A²·s
for backplane bus (5 V DC), max.1 600 mA; Max. 5 V DC for SM and CM
24 VL+ minus 4 V DC min.
Power loss, typ.12 W
Work memory – integrated200 kbyte
Load memory – Integrated4 Mbyte
for bit operations, typ.0.08 µs; / instruction
for word operations, typ.1.7 µs; / instruction
for floating point arithmetic, typ.2.3 µs; / instruction
Retentive data area (incl. timers, counters, flags), max.14 kbyte
Size, max.8 kbyte; Size of bit memory address area
Inputs, adjustable1 kbyte
Outputs, adjustable1 kbyte
Hardware configuration – Number of modules per system, max.3 comm. modules, 1 signal board, 8 signal modules
Deviation per day, max.±60 s/month at 25 °C
Number of digital inputs14; Integrated
Digital inputs – of which inputs usable for technological functions6; HSC (High Speed Counting)
Input voltage – Rated value (DC)24 V
for signal "0"5 V DC at 1 mA
for signal "1"15 V DC at 2.5 mA
for standard inputs – — at "0" to "1", min.0.2 ms
for standard inputs – — at "0" to "1", max.12.8 ms
Number of digital outputs10; Relays
with resistive load, max.2 A
on lamp load, max.30 W with DC, 200 W with AC
— Input resistance (0 to 10 V)≥100k ohms
Resolution with overrange (bit including sign), max.10 bit
Memory size per trace, max.512 kbyte
Counting frequency, max.100 kHz
Potential separation digital inputs500 V AC for 1 minute
EMC – — Test voltage at air discharge8 kV
EMC – — Test voltage at contact discharge6 kV
Ambient temperature during operation – min.-20 °C
Ambient temperature during storage/transportation – min.-40 °C
Ambient temperature during storage/transportation – max.70 °C
Vibration resistance during operation acc. to IEC 60068-2-62 g (m/s²) wall mounting, 1 g (m/s²) DIN rail
Dimensions – Width130 mm
Dimensions – Height100 mm
Dimensions – Depth75 mm
Weight, approx.585 g
Width130 mm
ModelCompact
Height100 mm
Depth75 mm
With displayNo
Suitable for safety functionsNo
Number of analogue inputs2
Number of analogue outputs2
Voltage type (supply voltage)DC
Type of memoryRAM
Memory size125 kByte
Processing time (1K, binary operation)0.08 ms
Supporting protocol for LONNo
Number of HW-interfaces industrial Ethernet1
With optical interfaceNo
Additional program memory possibleNo
Supporting protocol for TCP/IPYes
Supporting protocol for ASIYes
Supporting protocol for PROFIBUSYes
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for KNXNo
Supporting protocol for ModbusYes
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for other bus systemsYes
RedundancyYes
Suitable for rail mountingYes
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustNone
System accessoryYes
Appendant operation agent (Ex ia)No
Supporting protocol for SERCOSNo
Supporting protocol for INTERBUS-SafetyNo
Number of interfaces PROFINET1
Front built-in possibleYes
Rack-assembly possibleYes
Wall mounting/direct mountingYes
Radio standard BluetoothNo
Radio standard WLAN 802.11No
IO link masterNo
Number of relay outputs10
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for EtherNet/IPNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for PROFINET CBANo
Supporting protocol for PROFINET IOYes
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Supply voltage DC20.4–28.8 V
Radio standard GPRSNo
Radio standard GSMNo
Mobile communications standard 3G (UMTS)No
Mobile communications standard 4G (LTE)No
Supporting protocol for EtherCATNo
Country of originGermany

Properties

MOQ1

Cross-References

Attached Documents