cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Siemens SIMATIC, electronic module for ET200ISP, 4 DO, 17.4 V DC/27 mA, "L"-shutdown, Ex ib (ia Ga) IIC T4 Gb (6ES7132-7GD10-0AB0)

Siemens · Control & Automation · I/O Modules · Germany · siemens.com
Part Number
6ES7132-7GD10-0AB0  ·  HS 8538.90
Siemens SIMATIC, electronic module for ET200ISP, 4 DO, 17.4 V DC/27 mA, "L"-shutdown, Ex ib (ia Ga) IIC T4 Gb (6ES7132-7GD10-0AB0)

Siemens 6ES7132-7GD10-0AB0 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform. SIMATIC ET 200iSP 4DQ 17.4 V DC/27 mA SHUT DOWN "L".

Technical Specifications

Manufacturer part number (MPN)6ES7132-7GD10-0AB0
EAN / GTIN4019169150194
Sales unitpcs
Product type designation4DQ 17.4 V DC/27 mA
HW functional status7
Firmware versionV3.0.0
Rack mountingNo
Front mountingYes
Rail mountingYes
Wall mounting/direct mountingNo
Type of supply voltageDC
Current consumption, typ.260 mA
From load voltage (power bus), max.300 mA; with actuator supply
Power loss, typ.2.1 W
Address space per module — Address space per module, max.2 byte
Fieldbus connection via separate transceiverYes
Type of digital outputTransistor
Number of digital outputs4; additionally 1 intrinsically-safe input for L shutdown
Short-circuit protectionYes
No-load voltage Uao (DC)17.4 V
Internal resistor Ri150 Ω
Trend key points E — Voltage Ue (DC)13.3 V
Trend key points E — Current Ie27 mA; 54 mA when outputs connected in parallel
Output voltage — Type of output voltageDC
Output current — for signal "1" rated value0.027 A
Output delay with resistive load — "0" to "1", max.2 ms
Output delay with resistive load — "1" to "0", max.1.5 ms
Switching frequency — with resistive load, max.100 Hz
Switching frequency — with inductive load, max.2 Hz
Cable length — shielded, max.500 m
Cable length — unshielded, max.500 m
Number of PROFINET interfaces0
Number of RS 485 interfaces0
Diagnoses — Wire breakYes; R > 10 kohms, I < 100 µA
Diagnoses — Short-circuitYes; R< 80 Ohm (one output), R< 40 Ohm (outputs connected in parallel)
Module for Ex(i) protectionYes; for more Co/Lo combinations, see certificate IECEx KEM 05.0011
Maximum values for connecting terminals for gas group IIC — Uo (no-load voltage), max.19.4 V
Maximum values for connecting terminals for gas group IIC — Io (short-circuit current), max.132 mA
Maximum values for connecting terminals for gas group IIC — Po (power output), max.0.64 W
Maximum values for connecting terminals for gas group IIC — Co (permissible external capacity), max.0.23 µF
Maximum values for connecting terminals for gas group IIC — Lo (permissible external inductivity), max.1.9 mH
Maximum values for connecting terminals for gas group IIC — Ui (intrinsically safe input voltage), max.28 V; switch input circuit
Maximum values for connecting terminals for gas group IIC — Pi (intrinsically safe input power), max.1.2 W; switch input circuit
Maximum values for connecting terminals for gas group IIC — Ci (internal capacity), max.3 nF; switch input circuit
IP degree of protectionIP30
CE markCE 0344
UKCA markDEKRA 21UKEX0085 Importer UK: Siemens plc Manchester M20 2UR
CULusLISTED E334384
FM approvalCLASSIFIED 3025852
INMETRO certificateUL-BR 12.0073
Use in hazardous areas — ATEX markingII 2 G (1) G Ex ib [ia Ga] IIC T4 Gb II 2 G (1) D Ex ib [ia IIIC Da] IIC T4 Gb I M2 Ex ib [ia] I Mb
Use in hazardous areas — ATEX certificateKEMA 04 ATEX 1249
Use in hazardous areas — IECExIECEx KEM 05.0011
Use in hazardous areas — CCC Ex2020322316002945
Use in hazardous areas — EAC ExPB Ex ib [ia] I Mb 1Ex ib [ia Ga] IIC T4 Gb [Ex ia Da] IIIC
Use in hazardous areas — FM markingClass I, Zone 1 AEx ib [ia] IIC T4 Ex ib IIC T4 NI, Class I, DIV.2, GP. A,B,C,D T4 AIS, Class I, DIV.1, GP. A,B,C,D T4 DIP Class II, III, GP. E,F,G
Use in hazardous areas — Explosion protection category for gasATEX gas explosion protection, Zone 1
Use in hazardous areas — Explosion protection category for dustATEX dust explosion protection, Zone 21 always install in corresponding enclosure
Design of electrical connectionScrew/spring-type terminal
Dimensions — Width30 mm
Dimensions — Height129 mm
Dimensions — Depth136.5 mm
Weight, approx.255 g
Voltage type (supply voltage)DC
Type of voltage (input voltage)DC
Output current0.027 A
Type of output voltageDC
Degree of protection (IP)IP30
Type of electric connectionScrew-/spring clamp connection
SIL according to IEC 61508None
Performance level according to EN ISO 13849-1None
Explosion safety category for gasATEX gas-ex-protection, Cat. 2G
Width30 mm
Height129 mm
Depth136.5 mm
Country of originGermany

Properties

MOQ1

Cross-References

Attached Documents