| Manufacturer part number (MPN) | 6EP1935-6MD11 |
| EAN / GTIN | 4025515150480 |
| Sales unit | pcs |
| End-of-charge voltage at DC — at -10 °C recommended | 29 V |
| End-of-charge voltage at DC — at 0 °C recommended | 28.4 V |
| End-of-charge voltage at DC — at 20 °C recommended | 27.3 V |
| End-of-charge voltage at DC — at 30 °C recommended | 26.8 V |
| End-of-charge voltage at DC — at 40 °C recommended | 26.6 V |
| End-of-charge voltage at DC — at 50 °C recommended | 26.3 V |
| Battery capacity | 3.2 A·h |
| Output current in buffering mode maximum | 9.6 A |
| Peak current | 15 A |
| Charging current maximum | 0.8 A |
| Output voltage at DC rated value | 24 V |
| Communication function | No |
| Design of short-circuit protection | Battery fuse 15 A/32 V (solid-state circuitry blade-type fuse + support) |
| Design of the overload protection | Valve control |
| Operating resource protection class | Class III |
| Protection class IP | IP00 |
| Shipbuilding approval | Yes |
| Ambient condition | For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently valve... |
| Ambient temperature — during operation | -15 ... +50 °C |
| Ambient temperature — during transport | -20 ... +50 °C |
| Ambient temperature — during storage | -20 ... +50 °C |
| Relative temporary capacity loss at 20 °C in a month typical | 3 % |
| Service life of energy storage — typical | capacity falls to 80 % of original capacity (according to EUROBAT) |
| Service life of energy storage — at 20 °C typical | 4 a |
| Service life of energy storage — at 30 °C typical | 2 a |
| Service life of energy storage — at 40 °C typical | 1 a |
| Service life of energy storage — at 50 °C typical | 0.5 a |
| Note | Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored a... |
| Type of electrical connection | spring-loaded terminals |
| Type of electrical connection — for UPS module | 1 screw terminal each for 0.08 ... 2.5 mm² for + BAT and - BAT |
| Width × height × depth of the enclosure | 190 × 151 × 82 mm |
| Installation width × mounting height | 210 mm × 171 mm |
| Fastening method | snaps onto DIN rail EN 60715 35x7.5/15 or keyhole mounting for hooking in to M4 screws |
| Fastening method — DIN-rail mounting | Yes |
| Fastening method — S7 rail mounting | No |
| Fastening method — wall mounting | Yes |
| Mechanical data — net weight | 3.2 kg |
| Number of cells | 12 |
| Product component included | Accessories pack with solid-state circuitry fuse 15 A |
| Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
| Nominal voltage | 24 V |
| Width | 190 mm |
| Weight | 3.2 g |
| Capacity | 3.2 mAh |
| Plastic housing | No |
| Length | 82 mm |
| Suitable for EX-applications | No |
| Ambient temperature | -15–50 °C |
| Suitable for rapid charger | No |
| Height including pole | 151 mm |
| Battery pack | Yes |
| Country of origin | Germany |