Siemens SIRIUS ACT Contact module with 1 contact element, 1 NC, spring-type terminal, for front plate mounting (3SU1400-1AA10-3CA0)

Siemens · Control & Automation · Pushbuttons & Pilot Lights · Germany · siemens.com
Part Number
3SU1400-1AA10-3CA0  ·  HS 8536.50
Siemens SIRIUS ACT Contact module with 1 contact element, 1 NC, spring-type terminal, for front plate mounting (3SU1400-1AA10-3CA0)

Siemens 3SU1400-1AA10-3CA0 — SIRIUS ACT 22 mm command and signalling device. Panel-mount pushbutton, indicator lamp or emergency-stop actuator in the 22 mm cutout family. SIRIUS ACT,Contact Element,1NC.

Technical Specifications

Manufacturer part number (MPN)3SU1400-1AA10-3CA0
EAN / GTIN4011209950900
Sales unitpcs
Package quantity5 pcs
Product type designation3SU1
Insulation voltage rated value500 V
Degree of pollution3
Type of voltage — of the operating voltageAC/DC
Type of voltage — of the input voltageAC/DC
Surge voltage resistance rated value6 kV
Protection class IP — of the enclosureIP40
Protection class IP — of the terminalIP20
Shock resistance — according to IEC 60068-2-27sinusoidal half-wave 15 g / 11 ms
Shock resistance — for railway applications according to EN 61373Category 1, Class B
Vibration resistance — according to IEC 60068-2-610 ... 500 Hz: 5 g
Vibration resistance — for railway applications according to EN 61373Category 1, Class B
Operating frequency maximum3 600 1/h
Mechanical service life (operating cycles) typical10 000 000
Electrical endurance (operating cycles) typical10 000 000
Thermal current10 A
Continuous current of the C characteristic MCB10 A
General technical data — Net Weight8 g
At AC — at 50 Hz rated value5 ... 500 V
At AC — at 60 Hz rated value5 ... 500 V
At AC — at DC rated value5 ... 500 V
Contact reliabilityOne maloperation per 100 million (17 V, 5 mA), one maloperation per 10 million (5 V, 1 mA)
Design of the contact of auxiliary contactsSilver alloy
Number of NC contacts for auxiliary contacts1
Number of NC contacts for auxiliary contacts — lagging switching0
Number of NO contacts for auxiliary contacts0
Number of NO contacts for auxiliary contacts — leading contact0
Operational current at AC-12 — at 24 V rated value10 A
Operational current at AC-12 — at 48 V rated value10 A
Operational current at AC-12 — at 110 V rated value10 A
Operational current at AC-12 — at 230 V rated value8 A
Operational current at AC-12 — at 400 V rated value8 A
Operational current at AC-15 — at 24 V rated value6 A
Operational current at AC-15 — at 48 V rated value6 A
Operational current at AC-15 — at 110 V rated value6 A
Operational current at AC-15 — at 230 V rated value6 A
Operational current at AC-15 — at 400 V rated value3 A
Operational current at AC-15 — at 500 V rated value1.4 A
Operational current at DC-12 — at 24 V rated value10 A
Operational current at DC-12 — at 48 V rated value5 A
Operational current at DC-12 — at 110 V rated value2.5 A
Operational current at DC-12 — at 230 V rated value1 A
Operational current at DC-12 — at 400 V rated value0.3 A
Operational current at DC-12 — at 500 V rated value0.3 A
Operational current at DC-13 — at 24 V rated value3 A
Operational current at DC-13 — at 48 V rated value1.5 A
Operational current at DC-13 — at 110 V rated value0.7 A
Operational current at DC-13 — at 230 V rated value0.3 A
Operational current at DC-13 — at 400 V rated value0.1 A
Operational current at DC-13 — at 500 V rated value0.1 A
Type of electrical connectionspring-loaded terminals
Type of connectable conductor cross-sections — solid without core end processing2x (0.25 ... 1.5 mm²)
Type of connectable conductor cross-sections — finely stranded with core end processing2x (0.25 ... 0.75 mm²)
Type of connectable conductor cross-sections — finely stranded without core end processing2x (0.25 ... 1.5 mm²)
Type of connectable conductor cross-sections — for AWG cables2x (24 ... 16)
Ambient temperature — during operation-25 ... +70 °C
Ambient temperature — during storage-40 ... +80 °C
Installation/ mounting/ dimensions — height36 mm
Installation/ mounting/ dimensions — width9.8 mm
Installation/ mounting/ dimensions — depth27.7 mm
Country of originGermany