| Manufacturer part number (MPN) | 3RV2411-1JA10 |
| EAN / GTIN | 4011209713185 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Setting range | 7-10 A |
| Width | 45 mm |
| Height | 97 mm |
| Depth | 97 mm |
| Rated operation power at AC-3, 400 V | 4 kW |
| With integrated auxiliary switch | No |
| Rated permanent current Iu | 10 A |
| With integrated under voltage release | No |
| Number of poles | 3 |
| Rated operating voltage | 690 V |
| Overload release current setting | 7–10 A |
| Power loss | 9.25 W |
| Degree of protection (IP) | IP20 |
| With thermal overload protection | Yes |
| Type of electrical connection of main circuit | Screw connection |
| Switch off technique | Magnetic |
| Rated operation power at AC-3, 230 V | 2.2 kW |
| Rated short-circuit breaking capacity Icu at 400 V |
| AC | 100 kA |
| Adjustment range undelayed short-circuit release | 208 A |
| Phase failure sensitive | Yes |
| Device construction | Built-in device fixed built-in technique |
| Country of origin | Germany |