| Manufacturer part number (MPN) | 3VA2010-5KP420-0AA0 |
| EAN / GTIN | 4042948803790 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Rated current | 100 A |
| Rated permanent current Iu | 100 A |
| With integrated under voltage release | No |
| Number of poles | 4 |
| Overload release current setting | 40–100 A |
| Rated voltage | 690 V |
| Power loss | 13.5 W |
| Degree of protection (IP) | IP40 |
| Position of connection for main current circuit | Front side |
| Motor drive integrated | No |
| Type of electrical connection of main circuit | Screw connection |
| Type of control element | Rocker lever |
| With switched-off indicator | No |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz | 55 kA |
| Adjustment range short-term delayed short-circuit release | 60–1000 A |
| Adjustment range undelayed short-circuit release | 150–1200 A |
| Suitable for DIN rail (top hat rail) mounting | Yes |
| Integrated earth fault protection | No |
| Motor drive optional | Yes |
| Device construction | Built-in device slide-in technique (withdrawable) |
| DIN rail (top hat rail) mounting optional | Yes |
| Complete device with protection unit | Yes |
| Country of origin | Czechia |