| Manufacturer part number (MPN) | 6EP3334-3SB00-0AX0 EAN / GTIN: 4025515156246 Sales unit: pcs Type of the power supply network: 1-phase AC Supply voltage 1 at AC: 100 ... 120 V Supply voltage 2 at AC: 200 ... 240 V Input voltage 1 at AC: 85 ... 132 V Input voltage 2 at AC: 187 ... 264 V Buffering time for rated value of the output current in the event of power failure minimum: 15 ms Operating condition of the mains buffering: at Vin = 120/240 V Line frequency: 50/60 Hz Input current — at rated input voltage 100 V: 5 A Input current — at rated input voltage 120 V: 4.3 A Input current — at rated input voltage 200 V: 2.6 A Input current — at rated input voltage 230 V: 2.5 A Input current — at rated input voltage 240 V: 2.4 A Current limitation of inrush current at 25 °C maximum: 60 A Duration of inrush current limiting at 25 °C — typical: 20 ms I2t value maximum: 3.2 A²·s Fuse protection type: 6.3 A Fuse protection type in the feeder: Recommended miniature circuit breaker: from 6 A characteristic C to from 16 A characteristic C Output voltage at DC rated value: 24 V Output voltage — at output 1 at DC rated value: 24 V Adjustable output voltage: 24 ... 28 V Relative overall tolerance of the voltage: 3 % Relative control precision of the output voltage — on slow fluctuation of input voltage: 0.2 % Relative control precision of the output voltage — on slow fluctuation of ohm loading: 0.3 % Residual ripple — maximum: 150 mV Residual ripple — typical: 25 mV Voltage peak — maximum: 240 mV Voltage peak — typical: 20 mV Display version for normal operation: Green LED for 24 V OK Type of signal at output: Signal contact (signal load capacity: 5 mA) for DC OK Response delay maximum: 1.5 s Voltage increase time of the output voltage — typical: 130 ms Voltage increase time of the output voltage — maximum: 500 ms Output current — rated value: 10 A Output current — rated range: 0 ... 10 A; +60 ... +70 °C: Derating 4%/K Supplied active power typical: 240 W Number of parallel-switched equipment resources for increasing the power: 2 Efficiency in percent: 90 % Power loss [W] — at rated output voltage for rated value of the output current typical: 27 W Power loss [W] — during no-load operation maximum: 3 W Relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical: 0.2 % Relative control precision of the output voltage load step of resistive load 50/100/50 % typical: 2 % Relative control precision of the output voltage at load step of resistive load 10/90/10 % typical: 3 % Setting time — load step 10 to 90% typical: 1 ms Setting time — load step 90 to 10% typical: 1 ms Design of the overvoltage protection: < 32 V Enduring short circuit current RMS value — typical: 12.5 A Galvanic isolation: Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) Leakage current — maximum: 1.3 mA Leakage current — typical: 0.7 mA Protection class IP: IP20 Ambient temperature — during operation: -25 ... +70 °C; with natural convection Ambient temperature — during transport: -40 ... +85 °C Ambient temperature — during storage: -40 ... +85 °C Connection method — at input: L |