| Manufacturer part number (MPN) | 6EP3333-3SB00-0AX0 EAN / GTIN: 4025515156239 Sales unit: pcs Type of the power supply network: 1-phase AC Supply voltage at AC: Automatic range selection Supply voltage 1 at AC: 100 ... 120 V Supply voltage 2 at AC: 200 ... 240 V Input voltage 1 at AC: 85 ... 132 V Input voltage 2 at AC: 187 ... 264 V Buffering time for rated value of the output current in the event of power failure minimum: 15 ms Operating condition of the mains buffering: at Vin = 120/240 V Line frequency: 50/60 Hz Input current — at rated input voltage 100 V: 2.5 A Input current — at rated input voltage 120 V: 2.1 A Input current — at rated input voltage 230 V: 1.25 A Current limitation of inrush current at 25 °C maximum: 45 A I2t value maximum: 1.6 A²·s Fuse protection type: 3.15 A Fuse protection type in the feeder: Recommended miniature circuit breaker: from 6 A characteristic C to from 16 A characteristic C Voltage curve at output: Controlled, isolated DC voltage Output voltage at DC rated value: 24 V Adjustable output voltage: 24 ... 28 V Relative overall tolerance of the voltage: 3 % Relative control precision of the output voltage — on slow fluctuation of input voltage: 0.2 % Relative control precision of the output voltage — on slow fluctuation of ohm loading: 0.3 % Residual ripple — maximum: 150 mV Residual ripple — typical: 35 mV Voltage peak — maximum: 240 mV Display version for normal operation: Green LED for 24 V OK Type of signal at output: Signal contact (signal load capacity: 5 mA) for DC OK Response delay maximum: 1.5 s Voltage increase time of the output voltage — typical: 210 ms Output current — rated value: 5 A Output current — rated range: 0 ... 5 A; +60 ... +70 °C: Derating 4%/K Supplied active power typical: 120 W Number of parallel-switched equipment resources for increasing the power: 2 Efficiency in percent: 87 % Power loss [W] — at rated output voltage for rated value of the output current typical: 18 W Power loss [W] — during no-load operation maximum: 2.2 W Relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical: 0.2 % Relative control precision of the output voltage load step of resistive load 50/100/50 % typical: 1 % Setting time — load step 10 to 90% typical: 1 ms Setting time — load step 90 to 10% typical: 1 ms Design of the overvoltage protection: < 32 V Enduring short circuit current RMS value — typical: 6 A Galvanic isolation: Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) Leakage current — maximum: 1.4 mA Protection class IP: IP20 Standard — for emitted interference: EN 55032 Class A Standard — for mains harmonics limitation: EN 61000-3-2 Standard — for interference immunity: EN 61000-6-2 UL approval: Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 MTBF at 40 °C: 1 580 000 h Ambient temperature — during operation: -25 ... +70 °C; with natural convection Ambient temperature — during transport: -40 ... +85 °C Ambient temperature — during storage: -40 ... +85 °C Connection method — at input: L |