| Manufacturer part number (MPN) | 6EP3324-7SB00-3AX0 EAN / GTIN: 4025515155195 Sales unit: pcs Type of the power supply network: 1-phase AC or DC Supply voltage at AC — minimum rated value: 120 V Supply voltage at AC — maximum rated value: 240 V Supply voltage at AC — initial value: 85 V Supply voltage at AC — full-scale value: 264 V Supply voltage at DC: 110 ... 240 V Input voltage at DC: 85 ... 275 V Overvoltage overload capability: 300 V AC for 30 s Buffering time for rated value of the output current in the event of power failure minimum: 70 ms Line frequency: 50/60 Hz Input current — at rated input voltage 120 V: 1.4 A Input current — at rated input voltage 240 V: 0.8 A Current limitation of inrush current at 25 °C maximum: 6 A Fuse protection type: 5 A Fuse protection type in the feeder: Circuit breaker from 4 A characteristic C/6 A characteristic B to 10 A characteristic C or circuit breaker 3RV2011-1EA10 (setting 4 A) or 3RV2711-1ED10 (UL 489) Number of outputs: 1 Output voltage at DC rated value: 12 V Adjustable output voltage: 12 ... 15.5 V; max. 144 W (173 W up to 45°C) Relative overall tolerance of the voltage: 3 % Residual ripple — maximum: 30 mV Residual ripple — typical: 20 mV Voltage peak — maximum: 30 mV Voltage peak — typical: 20 mV Display version for normal operation: Green LED for 24 V OK Type of signal at output: Electronic contact (NO contact, contact rating 30 V DC/0.1 A) for DC O.K. or diagnostic interface Behavior of the output voltage when switching on: Overshoot of Vout < 2 % Response delay maximum: 0.5 s Voltage increase time of the output voltage — typical: 100 ms Output current — rated value: 12 A Output current — rated range: 0 ... 12 A; 14.4 A up to +45°C; +60 ... +70 °C: Derating 3%/K Supplied active power typical: 144 W Short-term overload current — on short-circuiting during the start-up typical: 14.4 A Short-term overload current — at short-circuit during operation typical: 14.4 A Number of parallel-switched equipment resources for increasing the power: 2 Efficiency in percent: 89.3 % Power loss [W] — at rated output voltage for rated value of the output current typical: 17 W Power loss [W] — during no-load operation maximum: 3 W Relative control precision of the output voltage at load step of resistive load 10/90/10 % typical: 3 % Setting time — load step 10 to 90% typical: 2 ms Setting time — load step 90 to 10% typical: 2 ms Design of the overvoltage protection: < 20 V Overcurrent overload capability — in normal operation: overload capability 150 % Iout rated up to 5 s/min Galvanic isolation: Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) Leakage current — maximum: 3.5 mA Protection class IP: IP20 Standard — for emitted interference: EN 55022 Class B Standard — for mains harmonics limitation: EN 61000-3-2 Standard — for interference immunity: EN 61000-6-2 Ambient temperature — during operation: -30 ... +70 °C; with natural convection a monotonically increasing start-up from -25 °C, safe start-up from -40 °C Ambient temperature — during transport: -40 ... +85 °C Ambient temperature — during storage: -40 ... +85 °C General information — at input: L1/+ |