| Manufacturer part number (MPN) | 6EP3336-7SB00-3AX0 EAN / GTIN: 4025515155218 Sales unit: pcs Type of the power supply network: 1-phase AC or DC Supply voltage at AC — minimum rated value: 120 V Supply voltage at AC — maximum rated value: 240 V Supply voltage at DC: 110 ... 240 V Input voltage at DC: 85 ... 275 V Wide range input: Yes Overvoltage overload capability: 300 V AC for 30 s Buffering time for rated value of the output current in the event of power failure minimum: 25 ms Line frequency: 47 ... 63 Hz Input current — at rated input voltage 120 V: 4.4 A Input current — at rated input voltage 240 V: 2.2 A Current limitation of inrush current at 25 °C maximum: 12 A Fuse protection type: 10 A Voltage curve at output: Controlled, isolated DC voltage Number of outputs: 1 Output voltage at DC rated value: 24 V Output voltage adjustable: Yes; via potentiometer Adjustable output voltage: 24 ... 28 V; max. 480 W (576 W up to 45°C) Relative overall tolerance of the voltage: 3 % Residual ripple — maximum: 80 mV Display version for normal operation: Green LED for 24 V OK Behavior of the output voltage when switching on: Overshoot of Vout approx. 3 % Response delay maximum: 0.5 s Output current — rated value: 20 A Output current — rated range: 0 ... 20 A; 24 A up to +45°C; +60 ... +70 °C: Derating 3%/K Supplied active power typical: 480 W Short-term overload current — at short-circuit during operation typical: 30 A Number of parallel-switched equipment resources for increasing the power: 2 Efficiency in percent: 95.5 % Power loss [W] — at rated output voltage for rated value of the output current typical: 25 W Design of the overvoltage protection: < 32 V Property of the output short-circuit proof: Yes Design of short-circuit protection: Shutdown and periodic restart attempts Overcurrent overload capability — in normal operation: overload capability 150 % Iout rated up to 5 s/min Galvanic isolation between input and output: Yes Galvanic isolation: Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) Operating resource protection class: Class I Leakage current — maximum: 3.5 mA Protection class IP: IP20 Standard — for emitted interference: EN 55022 Class B Standard — for interference immunity: EN 61000-6-2 Ambient temperature — during operation: -30 ... +70 °C; with natural convection, safe start-up from -40 °C Ambient temperature — during storage: -40 ... +85 °C Type of electrical connection: push-in terminals Connection method — at input: L1/+ |