Siemens SIRIUS 3RB3 Electronic Overload Relay 4...16 A, Size S00, Class 20E, Main Spring-type, Aux Spring-type (3RB3016-2TE0)

Siemens · Switchgear & Protection · Overload Relays · Germany · siemens.com
Part Number
3RB3016-2TE0  ·  HS 8536.49
Siemens SIRIUS 3RB3 Electronic Overload Relay 4...16 A, Size S00, Class 20E, Main Spring-type, Aux Spring-type (3RB3016-2TE0)

Siemens 3RB3016-2TE0 Electronic Overload Relay Class 20 4-16A Spring terminals.

Technical Specifications

Manufacturer part number (MPN)3RB3016-2TE0
EAN / GTIN4011209748903
Sales unitpcs
Product type designation3RB3
Size of contactor can be combined company-specificS00
Power loss [W] for rated value of the current at AC in hot operating state1.1 W
Power loss [W] for rated value of the current at AC in hot operating state — per pole0.37 W
Insulation voltage with degree of pollution 3 at AC rated value690 V
Surge voltage resistance rated value6 kV
Shock resistance15 g / 11 ms
Shock resistance — according to IEC 60068-2-2715 g / 11 ms; Signaling contact 97 / 98 in position "Tripped": 9g / 11 ms
Vibration resistance1 … 6 Hz, 15 mm; 6 … 500 Hz, 20 m/s²; 10 cycles
Thermal current16 A
Recovery time after overload trip — with automatic reset typical3 min
Recovery time after overload trip — with remote-reset0 min
Recovery time after overload trip — with manual reset0 min
Installation altitude at height above sea level maximum2 000 m
Ambient temperature — during operation-25 ... +60 °C
Ambient temperature — during storage-40 ... +80 °C
Ambient temperature — during transport-40 ... +80 °C
Temperature compensation-25 ... +60 °C
Relative humidity during operation10 ... 95 %
Number of poles for main current circuit3
Adjustable current response value current of the current-dependent overload release4 ... 16 A
Operating voltage — rated value690 V
Operating voltage — at AC-3e rated value maximum690 V
Operating frequency rated value50 ... 60 Hz
Operational current rated value16 A
Operational current at AC-3e at 400 V rated value16 A
Operating power — for 3-phase motors at 400 V at 50 Hz2.2 ... 7.5 kW
Operating power — for AC motors at 500 V at 50 Hz2.2 ... 7.5 kW
Operating power — for AC motors at 690 V at 50 Hz3 ... 11 kW
Number of NC contacts for auxiliary contacts1
Number of NO contacts for auxiliary contacts1
Number of CO contacts for auxiliary contacts0
Operational current of auxiliary contacts at AC-15 — at 24 V4 A
Operational current of auxiliary contacts at AC-15 — at 110 V4 A
Operational current of auxiliary contacts at AC-15 — at 120 V4 A
Operational current of auxiliary contacts at AC-15 — at 125 V4 A
Operational current of auxiliary contacts at AC-15 — at 230 V3 A
Operational current of auxiliary contacts at DC-13 — at 24 V2 A
Operational current of auxiliary contacts at DC-13 — at 60 V0.55 A
Operational current of auxiliary contacts at DC-13 — at 110 V0.3 A
Operational current of auxiliary contacts at DC-13 — at 125 V0.3 A
Operational current of auxiliary contacts at DC-13 — at 220 V0.11 A
Full-load current (FLA) for 3-phase AC motor — at 480 V rated value16 A
Full-load current (FLA) for 3-phase AC motor — at 600 V rated value16 A
Contact rating of auxiliary contacts according to ULB600 / R300
For short-circuit protection of the main circuit — with type of coordination 1 requiredgG: 50 A
RK560 A
For short-circuit protection of the main circuit — with type of coordination 2 requiredgG: 50 A, J: 60 A
For short-circuit protection of the main circuit — for short-circuit protection of the auxiliary switch requiredfuse gG: 6 A
Installation/ mounting/ dimensions — height72 mm
Installation/ mounting/ dimensions — width45 mm
Installation/ mounting/ dimensions — depth90 mm
Type of connectable conductor cross-sections for main contacts — solid1x (0.5 ... 4 mm²)
Type of connectable conductor cross-sections for main contacts — solid or stranded1x (0,5 ... 4 mm²)
Type of connectable conductor cross-sections for main contacts — finely stranded with core end processing1x (0.5 ... 2.5 mm²)
Type of connectable conductor cross-sections for main contacts — finely stranded without core end processing1x (0.5 ... 2.5 mm²)
For auxiliary contacts — solid2x (0.25 ... 1.5 mm²)
For auxiliary contacts — solid or stranded2x (0,25 ... 1,5 mm²)
For auxiliary contacts — finely stranded with core end processing2x (0.25 ... 1.5 mm²)
For auxiliary contacts — finely stranded without core end processing2x (0.25 ... 1.5 mm²)
Conducted interference — due to high-frequency radiation according to IEC 61000-4-610 V in frequency range 0.15 to 80 MHz, modulation 80 % AM with 1 kHz
Mounting methodDirect attachment
Width45 mm
Height72 mm
Depth90 mm
Number of auxiliary contacts as normally open contact1
Number of auxiliary contacts as normally closed contact1
Release classClass 20
Type of electrical connection of main circuitSpring clamp connection
Reset function inputNo
Reset function automaticYes
Country of originCzechia

Properties

MOQ1

Cross-References