| Manufacturer part number (MPN) | 3RB3016-1TB0 |
| EAN / GTIN | 4011209748651 |
| Sales unit | pcs |
| adjustable current response value of the current-dependent overload release | 4 ... 16 A |
| operating voltage — rated value | 690 V |
| operating frequency rated value | 50 ... 60 Hz |
| operational current rated value | 16 A |
| operational current at AC-3e at 400 V rated value | 16 A |
| operating power — for 3-phase motors at 400 V at 50 Hz | 2.2 ... 7.5 kW |
| operating power — for AC motors at 500 V at 50 Hz | 2.2 ... 7.5 kW |
| operating power — for AC motors at 690 V at 50 Hz | 3 ... 11 kW |
| thermal current | 16 A |
| power loss [W] for rated value of the current at AC in hot operating state | 1.1 W |
| insulation voltage with degree of pollution 3 at AC rated value | 690 V |
| surge voltage resistance rated value | 6 kV |
| recovery time after overload trip — with automatic reset typical | 3 min |
| operational current of auxiliary contacts at AC-15 — at 24 V | 4 A |
| operational current of auxiliary contacts at AC-15 — at 230 V | 3 A |
| operational current of auxiliary contacts at DC-13 — at 24 V | 2 A |
| operational current of auxiliary contacts at DC-13 — at 110 V | 0.3 A |
| operational current of auxiliary contacts at DC-13 — at 220 V | 0.11 A |
| full-load current (FLA) for 3-phase AC motor — at 480 V rated value | 16 A |
| full-load current (FLA) for 3-phase AC motor — at 600 V rated value | 16 A |
| short-circuit protection of the auxiliary switch required | fuse gG: 6 A |
| maximum permissible voltage for protective separation — ungrounded star point main and auxiliary circuit | 600 V |
| maximum permissible voltage for protective separation — grounded star point main and auxiliary circuit | 690 V |
| shock resistance according to IEC 60068-2-27 | 15 g / 11 ms |
| vibration resistance | 1 … 6 Hz, 15 mm; 6 … 500 Hz, 20 m/s²; 10 cycles |
| installation altitude at height above sea level maximum | 2 000 m |
| Installation/mounting/dimensions — height | 79 mm |
| Installation/mounting/dimensions — width | 45 mm |
| Installation/mounting/dimensions — depth | 73 mm |
| connectable conductor cross-section for main contacts — solid | 1x (0.5 ... 4 mm²), 2x (0.5 ... 1.5 mm²) |
| connectable conductor cross-section for main contacts — finely stranded with core end processing | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 2.5 mm²) |
| tightening torque — for main contacts with screw-type terminals | 0.8 ... 1.2 N·m |
| Net Weight | 0.219 kg |
| Mounting method | Direct attachment |
| Width | 45 mm |
| Height | 79 mm |
| Depth | 73 mm |
| Number of auxiliary contacts as normally open contact | 1 |
| Number of auxiliary contacts as normally closed contact | 1 |
| Release class | CLASS 10 |
| Type of electrical connection of main circuit | Screw connection |
| Reset function input | No |
| Reset function automatic | Yes |
| Country of origin | Czechia |