cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Siemens SIRIUS Load feeder fuseless, Reversing duty 400 V AC, Size S0 13.0...20.0 A 24 V DC screw terminal for installation on standard mounting rail with standard mounting rail adapter Type of coordination 1, Iq = 150 kA 1 NO+1 NC (contactor) (3RA2220-4BB26-0BB4)

Siemens · Drives & Controllers · Motor Starters · Germany · siemens.com
Part Number
3RA2220-4BB26-0BB4  ·  HS 8536.49
Siemens SIRIUS Load feeder fuseless, Reversing duty 400 V AC, Size S0 13.0...20.0 A 24 V DC screw terminal for installation on standard mounting rail with standard mounting rail adapter Type of coordination 1, Iq = 150 kA 1 NO+1 NC (contactor) (3RA2220-4BB26-0BB4)

Siemens 3RA2220-4BB26-0BB4 Reversing switch 14 - 20A, Dc 24V.

Technical Specifications

Manufacturer part number (MPN)3RA2220-4BB26-0BB4
EAN / GTIN4011209794580
Sales unitpcs
Voltage24 V
Rated current20 A
Product brand nameSIRIUS
Product designationReversing starter
Design of the productfor DIN-rail or screw mounting
Product type designation3RA22
Manufacturer's article number — of the supplied contactor3RT2026-1BB40
Manufacturer's article number — of the supplied circuit-breakers3RV2021-4BA10
Manufacturer's article number — of the supplied RH assembly kit3RA2923-1BB1
Manufacturer's article number — of the supplied link module3RA2921-1BA00
Manufacturer's article number — of the supplied DIN-rail adapter3RA2922-1AA00
Size of the circuit-breakerS0
Size of load feederS0
Power loss [W] for rated value of the current — at AC in hot operating state per pole5.4 W
Power loss [W] for rated value of the current — without load current share typical5.9 W
Type of calculation of power loss current-dependentquadratic
Insulation voltage with degree of pollution 3 at AC rated value690 V
Surge voltage resistance rated value6 kV
Degree of protection NEMA ratingother
Shock resistance according to IEC 60068-2-276 g / 11 ms
Mechanical service life (operating cycles) of contactor typical10 000 000
Type of coordination1
Reference code according to IEC 81346-22019: Q
Ambient temperature — during operation-20 ... +60 °C
Ambient temperature — during storage-50 ... +80 °C
Ambient temperature — during transport-50 ... +80 °C
Temperature compensation-20 ... +60 °C
Relative humidity during operation10 ... 95 %
Number of poles for main current circuit3
Design of the switching contactelectromechanical
Adjustable current response value current of the current-dependent overload release13 ... 20 A
Operating voltage — rated value690 V
Operating voltage — at AC-3 rated value maximum690 V
Operating voltage — at AC-3e rated value maximum690 V
Operating frequency rated value50 ... 60 Hz
Operational current — at AC-3 at 400 V rated value20 A
Operational current — at AC-3e at 400 V rated value20 A
At AC-3 — at 400 V rated value7 500 W
At AC-3e — at 400 V rated value7 500 W
Type of voltage of the control supply voltageDC
Control supply voltage at DC rated value24 V
Holding power of magnet coil at DC5.9 W
Product extension auxiliary switchYes
Trip classCLASS 10
Design of the overload releasethermal (bimetallic)
Response value current of instantaneous short-circuit trip unit260 A
Full-load current (FLA) for 3-phase AC motor — at 480 V rated value20 A
Full-load current (FLA) for 3-phase AC motor — at 600 V rated value20 A
For single-phase AC motor — at 110/120 V rated value1.5 hp
For single-phase AC motor — at 230 V rated value3 hp
For 3-phase AC motor — at 200/208 V rated value5 hp
For 3-phase AC motor — at 220/230 V rated value7.5 hp
For 3-phase AC motor — at 460/480 V rated value15 hp
Product function short circuit protectionYes
Design of the short-circuit tripmagnetic
Conditional short-circuit current (Iq) — at 400 V according to IEC 60947-4-1 rated value150 000 A
Mounting positionvertical
Fastening methodOn adapter for screw and snap-on mounting on 35 mm DIN rail
Installation/ mounting/ dimensions — height265 mm
Installation/ mounting/ dimensions — width90 mm
Installation/ mounting/ dimensions — depth130 mm
For grounded parts — forwards32 mm
For grounded parts — backwards0 mm
For grounded parts — upwards50 mm
For grounded parts — at the side10 mm
For grounded parts — downwards10 mm
For live parts — forwards32 mm
For live parts — backwards0 mm
For live parts — upwards50 mm
For live parts — downwards10 mm
For live parts — at the side10 mm
Type of electrical connection — for main current circuitscrew-type terminals
Type of electrical connection — for auxiliary and control circuitscrew-type terminals
Product function suitable for safety functionYes
Touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front
Protocol is supported — PROFINET IO protocolNo
Protocol is supported — PROFIsafe protocolNo
Protocol is supported AS-Interface protocolNo
Width90 mm
Height265 mm
Depth130 mm
Rated operation power at AC-3, 400 V7.5 kW
Number of command positions1
Suitable for emergency stopYes
Rated operation current Ie15.5 A
Supporting protocol for LONNo
Supporting protocol for TCP/IPNo
Supporting protocol for ASINo
Supporting protocol for PROFIBUSNo
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for ModbusNo
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for other bus systemsNo
External reset possibleNo
Suitable for rail mountingYes
Rated control supply voltage DC24 V
Degree of protection (IP)IP20
Supporting protocol for SERCOSNo
Supporting protocol for INTERBUS-SafetyNo
Release classCLASS 10
Type of electrical connection of main circuitScrew connection
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for EtherNet/IPNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for PROFINET CBANo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Voltage type for actuatingDC
Rated operation current at AC-3, 400 V15.5 A
Ambient temperature, upper operating limit60 °C
Temperature compensated overload protectionYes
Rated conditional short-circuit current, type 1, 480 Y/277 V65000 A
Coordination class according to IEC 60947-4-3Class 2
Country of originGermany

Properties

MOQ1

Cross-References

Attached Documents