| Manufacturer part number (MPN) | 3RA2110-0DA15-1AP0 |
| EAN / GTIN | 4011209794047 |
| Sales unit | pcs |
| Product brand name | SIRIUS |
| Product designation | Direct (on-line) starter |
| Design of the product | for DIN-rail or screw mounting |
| Product type designation | 3RA21 |
| Manufacturer's article number — of the supplied contactor | 3RT2015-1AP01 |
| Manufacturer's article number — of the supplied circuit-breakers | 3RV2011-0DA10 |
| Manufacturer's article number — of the supplied link module | 3RA1921-1DA00 |
| Size of the circuit-breaker | S00 |
| Size of load feeder | S00 |
| Power loss [W] for rated value of the current — at AC in hot operating state per pole | 2 W |
| Power loss [W] for rated value of the current — without load current share typical | 4.2 W |
| Type of calculation of power loss current-dependent | quadratic |
| Insulation voltage with degree of pollution 3 at AC rated value | 690 V |
| Surge voltage resistance rated value | 6 kV |
| Degree of protection NEMA rating | other |
| Shock resistance according to IEC 60068-2-27 | 6 g / 11 ms |
| Mechanical service life (operating cycles) of contactor typical | 30 000 000 |
| Type of coordination | 2 |
| Reference code according to IEC 81346-2 | 2019: Q |
| Ambient temperature — during operation | -20 ... +60 °C |
| Ambient temperature — during storage | -50 ... +80 °C |
| Ambient temperature — during transport | -50 ... +80 °C |
| Temperature compensation | -20 ... +60 °C |
| Relative humidity during operation | 10 ... 95 % |
| Number of poles for main current circuit | 3 |
| Design of the switching contact | electromechanical |
| Adjustable current response value current of the current-dependent overload release | 0.22 ... 0.32 A |
| Operating voltage — rated value | 690 V |
| Operating voltage — at AC-3 rated value maximum | 690 V |
| Operating voltage — at AC-3e rated value maximum | 690 V |
| Operating frequency rated value | 50 ... 60 Hz |
| Operational current — at AC-3 at 400 V rated value | 0.3 A |
| Operational current — at AC-3e at 400 V rated value | 0.32 A |
| At AC-3 — at 400 V rated value | 90 W |
| At AC-3e — at 400 V rated value | 90 W |
| Type of voltage of the control supply voltage | AC |
| Control supply voltage at AC — at 50 Hz rated value | 230 V |
| Control supply voltage at AC — at 60 Hz rated value | 230 V |
| Apparent holding power of magnet coil at AC | 4.2 VA |
| Apparent holding power of magnet coil at AC — at 50 Hz | 4.2 VA |
| Apparent holding power of magnet coil at AC — at 60 Hz | 3.3 VA |
| Inductive power factor with the holding power of the coil | 0.25 |
| Inductive power factor with the holding power of the coil — at 50 Hz | 0.25 |
| Inductive power factor with the holding power of the coil — at 60 Hz | 0.25 |
| Product extension auxiliary switch | Yes |
| Trip class | CLASS 10 |
| Design of the overload release | thermal (bimetallic) |
| Response value current of instantaneous short-circuit trip unit | 4.2 A |
| Full-load current (FLA) for 3-phase AC motor — at 480 V rated value | 0.3 A |
| Full-load current (FLA) for 3-phase AC motor — at 600 V rated value | 0.3 A |
| Product function short circuit protection | Yes |
| Design of the short-circuit trip | magnetic |
| Conditional short-circuit current (Iq) — at 400 V according to IEC 60947-4-1 rated value | 150 000 A |
| Mounting position | vertical |
| Fastening method | screw and snap-on mounting onto 35 mm DIN rail |
| Installation/ mounting/ dimensions — height | 167 mm |
| Installation/ mounting/ dimensions — width | 45 mm |
| Installation/ mounting/ dimensions — depth | 97 mm |
| For grounded parts — forwards | 20 mm |
| For grounded parts — backwards | 0 mm |
| For grounded parts — upwards | 50 mm |
| For grounded parts — at the side | 20 mm |
| For grounded parts — downwards | 10 mm |
| For live parts — forwards | 20 mm |
| For live parts — backwards | 0 mm |
| For live parts — upwards | 50 mm |
| For live parts — downwards | 10 mm |
| For live parts — at the side | 20 mm |
| Type of electrical connection — for main current circuit | screw-type terminals |
| Type of electrical connection — for auxiliary and control circuit | screw-type terminals |
| Product function suitable for safety function | Yes |
| Touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |
| Protocol is supported — PROFINET IO protocol | No |
| Protocol is supported — PROFIsafe protocol | No |
| Protocol is supported AS-Interface protocol | No |
| Width | 45 mm |
| Height | 167 mm |
| Depth | 97 mm |
| Rated operation power at AC-3, 400 V | 0.09 kW |
| Number of command positions | 1 |
| Suitable for emergency stop | Yes |
| Rated operation current Ie | 0.3 A |
| Supporting protocol for LON | No |
| Supporting protocol for TCP/IP | No |
| Supporting protocol for ASI | No |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | No |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for Modbus | No |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for other bus systems | No |
| External reset possible | No |
| Suitable for rail mounting | Yes |
| Rated control supply voltage AC 50 Hz | 230 V |
| Rated control supply voltage AC 60 Hz | 230 V |
| Degree of protection (IP) | IP20 |
| Supporting protocol for SERCOS | No |
| Supporting protocol for INTERBUS-Safety | No |
| Release class | CLASS 10 |
| Type of electrical connection of main circuit | Screw connection |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for EtherNet/IP | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Voltage type for actuating | AC |
| Rated operation current at AC-3, 400 V | 0.3 A |
| Ambient temperature, upper operating limit | 60 °C |
| Temperature compensated overload protection | Yes |
| Rated conditional short-circuit current, type 2, 400 V | 150000 A |
| Rated conditional short-circuit current, type 2, 230 V | 150000 A |
| Rated conditional short-circuit current, type 1, 480 Y/277 V | 65000 A |
| Rated conditional short-circuit current, type 1, 600 Y/347 V | 30000 A |
| Coordination class according to IEC 60947-4-3 | Class 2 |
| Country of origin | Germany |