Siemens SIRIUS Contactor assembly for star-delta (wye-delta) start, I/O-Link AC-3, 7.5 kW/400 V, 24 V DC 3-Pole, Size S00 Spring-type terminals electrical and mechanical interlock 3 NO integrated (3RA2416-8XE31-2BB4)

Siemens · Electrical Components · Contactors · Germany · siemens.com
Part Number
3RA2416-8XE31-2BB4  ·  HS 8536.49
Siemens SIRIUS Contactor assembly for star-delta (wye-delta) start, I/O-Link AC-3, 7.5 kW/400 V, 24 V DC 3-Pole, Size S00 Spring-type terminals electrical and mechanical interlock 3 NO integrated (3RA2416-8XE31-2BB4)

Siemens 3RA2416-8XE31-2BB4 Star/delta-selector switch IO-Link 7.5KW24V DC S00 Spring terminals 3NO.

Technical Specifications

Manufacturer part number (MPN)3RA2416-8XE31-2BB4
EAN / GTIN4011209838208
Sales unitpcs
Product brand nameSIRIUS
Product designationContactor assembly for star-delta (wye-delta) start
Product type designation3RA24
Manufacturer's article number — 1 of the supplied contactor3RT2017-2BB41-0CC0
Manufacturer's article number — 2 of the supplied contactor3RT2017-2BB41
Manufacturer's article number — 3 of the supplied contactor3RT2015-2BB41
Manufacturer's article number — of the supplied RS assembly kit3RA2913-2BB2
Manufacturer's article number — of the supplied function module for communication3RA2711-2CA00
Size of contactorS00
Shock resistance at rectangular impulse — at AC6,7 g / 5 ms, 4,2 g / 10 ms
Shock resistance at rectangular impulse — at DC6,7 g / 5 ms, 4,2 g / 10 ms
Shock resistance with its pulse — at AC10,5 g / 5 ms, 6,6 g / 10 ms
Shock resistance with its pulse — at DC10,5 g / 5 ms, 6,6 g / 10 ms
Mechanical service life (operating cycles) — of contactor typical10 000 000
Mechanical service life (operating cycles) — of the contactor with added auxiliary switch block typical10 000 000
Installation altitude at height above sea level maximum2 000 m
Ambient temperature — during operation-25 ... +60 °C
Ambient temperature — during storage-55 ... +80 °C
Number of poles for main current circuit3
Number of NO contacts for main contacts3
Number of NC contacts for main contacts0
Operating voltage — at AC-3 rated value maximum690 V
At AC-3 — at 400 V rated value16 A
At AC-3 — at 500 V rated value10.3 kW
At AC-3 — at 690 V rated value9.2 kW
Operating frequency — at AC-3 maximum1 000 1/h
Type of voltage of the control supply voltageDC
Control supply voltage 1 at DC rated value24 V
Closing power of magnet coil at DC10 W
Holding power of magnet coil at DC10 W
Number of NO contacts for auxiliary contacts — instantaneous contact3
Contact reliability of auxiliary contacts< 1 error per 100 million operating cycles
Contact rating of auxiliary contacts according to ULA600 / Q600
For short-circuit protection of the main circuit — with type of coordination 1 requiredgG NH 3NA, DIAZED 5SB
NEOZED 5SE35 A
For short-circuit protection of the main circuit — with type of coordination 2 requiredgG NH 3NA, DIAZED 5SB
NEOZED 5SE20 A
For short-circuit protection of the main circuit — for short-circuit protection of the auxiliary switch requiredfuse gG: 10 A
Mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
Fastening methodscrew and snap-on mounting onto 35 mm DIN rail
Installation/ mounting/ dimensions — height84 mm
Installation/ mounting/ dimensions — width135 mm
Installation/ mounting/ dimensions — depth145 mm
With side-by-side mounting — forwards6 mm
With side-by-side mounting — upwards6 mm
With side-by-side mounting — downwards6 mm
With side-by-side mounting — at the side6 mm
For grounded parts — forwards6 mm
For grounded parts — upwards6 mm
For grounded parts — at the side6 mm
For grounded parts — downwards6 mm
For live parts — forwards6 mm
For live parts — upwards6 mm
For live parts — downwards6 mm
For live parts — at the side6 mm
Type of electrical connection — for main current circuitspring-loaded terminals
Type of electrical connection — for auxiliary and control circuitspring-loaded terminals
Type of electrical connection — at contactor for auxiliary contactsSpring-type terminals
Type of electrical connection — of magnet coilSpring-loaded terminal
Type of connectable conductor cross-sections for main contacts — solid2x (0.5 ... 4 mm²)
Type of connectable conductor cross-sections for main contacts — solid or stranded2x (0,5 ... 4 mm²)
Type of connectable conductor cross-sections for main contacts — finely stranded with core end processing2x (0.5 ... 2.5 mm²)
Type of connectable conductor cross-sections for main contacts — finely stranded without core end processing2x (0.5 ... 2.5 mm²)
For auxiliary contacts — solid or stranded2x (0.5 ... 2.5 mm²)
For auxiliary contacts — finely stranded with core end processing2x (0.5 ... 1.5 mm²)
For auxiliary contacts — finely stranded without core end processing2x (0.5 ... 1.5 mm²)
For auxiliary contacts — for AWG cables for auxiliary contacts2x (20 ... 14)
Protection class IP on the front according to IEC 60529IP20
Touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front
Protocol is supported AS-Interface protocolNo
Product function control circuit interface with IO linkYes
Width135 mm
FunctionStar-delta contactor
Height84 mm
Depth145 mm
Rated operation power at AC-3, 400 V7.5 kW
Number of normally open contacts as main contact3
Rated operation current Ie at AC-3, 400 V16 A
Degree of protection (IP)IP20
Type of electrical connection of main circuitSpring clamp connection
Voltage type for actuatingDC
Country of originGermany

Properties

MOQ1

Cross-References