The Siemens 5SM2845-8 is a SENTRON 5SM2 RC unit — a residual current (RCD) block that clips directly onto a Siemens 5SY miniature circuit breaker. The assembled pair works as a combined residual-current and overcurrent protective device to DIN EN 61009-1, so one device gives both protection against electric shock and earth-fault fire and the line protection of the MCB behind it. This version is Type A: it detects sinusoidal AC residual currents and pulsating DC residual currents, which is the type required for circuits feeding electronic loads. It is 4-pole, rated 63 A at 400 V AC, with a rated residual current of 1 A. It suits 5SY miniature circuit breakers rated 6–63 A. The unit is selective (time-delayed), so it is intended as the upstream group device and will hold in while a downstream instantaneous RCD clears the fault — this is what keeps a single earth fault from tripping the whole board. Device depth is 70 mm. Supplied by cBallast on quote-to-invoice terms; lead time and freight are quoted per RFQ against the destination Incoterm.
| Manufacturer part number (MPN) | 5SM2845-8 |
| EAN / GTIN | 4001869171142 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Voltage | 400 V |
| Setting range | 6-63 A |
| Nominal voltage | 400 V |
| Nominal current | 63 A |
| Rated fault current adjustable | No |
| Rated fault current | 1 A |
| Delay adjustable | No |
| Number of poles | 4 |
| Leakage current type | A |
| Surge current capacity | 4000 kA |
| Frequency | 50/60 Hz |
| Rated insulation voltage Ui | 460 V |
| Rated impulse withstand voltage Uimp | 5 kV |
| Connectable conductor cross section solid-core | 1.5–25 mm² |
| Connectable conductor cross section multi-wired | 1.5–25 mm² |
| Anti-nuisance tripping version | Yes |
| With interlocking device | No |
| Degree of protection (IP) | IP20 |
| Pollution degree | 2 |
| Ambient temperature during operating | -25–45 °C |
| Country of origin | Czechia |
| Product family | SENTRON 5SM2 RC unit (add-on residual current device) |
| Residual current type | Type A (sinusoidal AC and pulsating DC) |
| Rated residual current (IΔn) | 1 A |
| Tripping characteristic | Selective / time-delayed (S) |
| Suitable for | Siemens 5SY miniature circuit breakers, 6–63 A |
| Device depth | 70 mm |
| Standard | DIN EN 61009-1 (combined with MCB) |