Schneider Electric TM241CE40R Modicon M241 logic controller, 40 I/O (24 digital inputs incl. 8 fast 200kHz, 16 relay outputs), 1 Ethernet + 2 serial lines, 24V DC supply.
| Series | Modicon M241 |
| Digital Inputs | 24 (8 fast 200kHz) |
| Digital Outputs | 16 relay |
| Communication | 1x Ethernet, 2x serial, USB-mini-B |
| Supply Voltage | 24V DC |
| Expansion | Up to 14 TM3 / 7 TM4 modules |
| Programming | EcoStruxure Machine |
| Mounting | 35mm DIN rail or screw plate |
| Range of product | Modicon M241 |
| Product or component type | Logic controller |
| [Us] rated supply voltage | 100...240 V AC |
| Discrete input number | 24, discrete input 8 fast input conforming to IEC 61131-2 Type 1 |
| Discrete output type | Relay; Transistor |
| Discrete output number | 4 transistor 4 fast output; 12 relay |
| Discrete output voltage | 5...125 V DC for relay output; 5...250 V AC for relay output; 24 V DC for transistor output |
| Discrete output current | 0.1 A for fast output (PTO mode) (TR0...TR3); 2 A for relay output (Q4...Q15); 0.5 A for transistor output (TR0...TR3) |
| Discrete I/O number | 40 |
| Maximum number of I/O expansion module | 7 (local I/O-Architecture); 14 (remote I/O-Architecture) |
| Supply voltage limits | 85…264 V |
| Network frequency | 50/60 Hz |
| Discrete input logic | Sink or source |
| Discrete input voltage | 24 V |
| Discrete input voltage type | DC |
| Voltage state 1 guaranteed | >= 15 V for input |
| Voltage state 0 guaranteed | <= 5 V for input |
| Discrete input current | 7 mA for input |
| Input impedance | 4.7 kOhm for input |
| Response time | 50 µs turn-on, I0...I15 terminal(s) for input |
| Configurable filtering time | 1 s for fast input |
| Discrete output logic | Positive logic (source) |
| Output voltage limits | 125 V DC relay output; 30 V DC transistor output; 277 V AC relay output |
| Maximum output frequency | 1 kHz for transistor output; 20 kHz for fast output (PWM mode); 100 kHz for fast output (PLS mode) |
| Accuracy | +/- 0.1 % at 0.02…0.1 kHz for fast output; +/- 1 % at 0.1…1 kHz for fast output |
| Protection type | Short-circuit protection for transistor output; Short-circuit and overload protection with automatic reset for transistor output; Reverse polarity protection for transistor output; Without protection for relay output |
| Reset time | 10 ms automatic reset output; 12 s automatic reset fast output |
| Memory capacity | 64 MB for system memory RAM |
| Data backed up | 128 MB built-in flash memory for backup of user programs |
| Data storage equipment | <= 16 GB SD card (optional) |
| Battery type | BR2032 lithium non-rechargeable, battery life: 4 year(s) |
| Backup time | 2 years at 25 °C |
| Execution time for 1 KInstruction | 0.3 ms for event and periodic task; 0.7 ms for other instruction |
| Application structure | 4 cyclic master tasks; 8 event tasks; 8 external event tasks; 3 cyclic master tasks + 1 freewheeling task |
| Realtime clock | With |
| Clock drift | <= 60 s/month at 25 °C |
| Positioning functions | PTO function 4 channel(s) (positioning frequency: 100 kHz) |
| Counting input number | 4 fast input (HSC mode) at 200 kHz; 14 standard input at 1 kHz |
| Control signal type | A/B at 100 kHz for fast input (HSC mode); Pulse/direction at 200 kHz for fast input (HSC mode); Single phase at 200 kHz for fast input (HSC mode) |
| Integrated connection type | Non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface ; Non isolated serial link serial 2 with removable screw terminal block connector and RS485 interface ; USB port with mini B USB 2.0 connector; Ethernet with RJ45 connector |
| Supply | (serial 1)serial link supply: 5 V, <200 mA |
| Transmission rate | 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485; 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232; 480 Mbit/s for bus length of 3 m for USB; 10/100 Mbit/s for Ethernet |
| Communication port protocol | Non isolated serial link: Modbus master/slave |
| Port Ethernet | 10BASE-T/100BASE-TX - 1 port(s) copper cable |
| ethernet services | FDR; DHCP server via TM4 Ethernet switch network module; DHCP client embedded Ethernet port; SMS notifications; Updating firmware; SNMP client/server; Programming; NGVL; Monitoring; IEC VAR ACCESS; FTP client/server; Downloading; SQL client; Modbus TCP client I/O scanner; Ethernet/IP originator I/O scanner embedded Ethernet port; Ethernet/IP target, Modbus TCP server and Modbus TCP slave; Send and receive email from the controller based on TCP/UDP library; Web server (WebVisu & XWeb system); OPC UA server; DNS client |
| Local signalling | 1 LED (green) for PWR; 1 LED (green) for RUN; 1 LED (red) for module error (ERR); 1 LED (red) for I/O error (I/O); 1 LED (green) for SD card access (SD); 1 LED (red) for BAT; 1 LED (green) for SL1; 1 LED (green) for SL2; 1 LED (red) for bus fault on TM4 (TM4); 1 LED per channel (green) for I/O state; 1 LED (green) for Ethernet port activity |
| Electrical connection | removable screw terminal blockfor inputs and outputs (pitch 5.08 mm); removable screw terminal blockfor connecting the 24 V DC power supply (pitch 5.08 mm) |
| Maximum cable distance between devices | Unshielded cable: <50 m for input; Shielded cable: <10 m for fast input; Unshielded cable: <50 m for output; Shielded cable: <3 m for fast output |
| Insulation | Between supply and internal logic at 500 V AC; Non-insulated between supply and ground |
| Marking | CE |
| Sensor power supply | 24 V DC at 400 mA supplied by the controller |
| Surge withstand | 2 kV power lines (AC) common mode conforming to IEC 61000-4-5; 2 kV relay output common mode conforming to IEC 61000-4-5; 1 kV shielded cable common mode conforming to IEC 61000-4-5; 1 kV power lines (AC) differential mode conforming to IEC 61000-4-5; 1 kV relay output differential mode conforming to IEC 61000-4-5; 1 kV input common mode conforming to IEC 61000-4-5; 1 kV transistor output common mode conforming to IEC 61000-4-5 |
| Web services | Web server |
| Maximum number of connections | 8 Modbus server; 8 SoMachine protocol; 10 web server; 4 FTP server; 16 Ethernet/IP target; 8 Modbus client |
| Number of server device(s) | 64 Modbus TCP: ; 16 EtherNet/IP: |
| Cycle time | 10 ms 16 EtherNet/IP; 64 ms 64 Modbus TCP |
| Mounting support | Top hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; plate or panel with fixing kit |
| Height | 90 mm |
| Depth | 95 mm |
| Width | 190 mm |
| Product weight | 0.62 kg |
| Standards | ANSI/ISA 12-12-01; CSA C22.2 No 142; CSA C22.2 No 213; IEC 61131-2:2007; Marine specification (LR, ABS, DNV, GL); UL 508 |
| Product certifications | RCM; cULus; CE; UKCA; DNV-GL; ABS; LR |
| Resistance to electrostatic discharge | 8 kV in air conforming to IEC 61000-4-2; 4 kV on contact conforming to IEC 61000-4-2 |
| Resistance to electromagnetic fields | 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3; 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3; 1 V/m 2 GHz...3 GHz conforming to IEC 61000-4-3 |
| Resistance to fast transients | 2 kV (power lines) conforming to IEC 61000-4-4; 2 kV (relay output) conforming to IEC 61000-4-4; 1 kV (Ethernet line) conforming to IEC 61000-4-4; 1 kV (serial link) conforming to IEC 61000-4-4; 1 kV (input) conforming to IEC 61000-4-4; 1 kV (transistor output) conforming to IEC 61000-4-4 |
| Resistance to conducted disturbances | 10 V 0.15...80 MHz conforming to IEC 61000-4-6; 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL); 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
| Electromagnetic emission | Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to IEC 55011; Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to IEC 55011; Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines) at 0.15…0.5 MHz conforming to IEC 55011; Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines) at 0.5…300 MHz conforming to IEC 55011; Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to IEC 55011; Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to IEC 55011; Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to IEC 55011 |
| Immunity to microbreaks | 10 ms |
| Ambient air temperature for operation | -10…50 °C (vertical installation); -10…55 °C (horizontal installation) |
| Ambient air temperature for storage | -25…70 °C |
| Relative humidity | 10…95 %, without condensation (in operation); 10…95 %, without condensation (in storage) |
| IP degree of protection | IP20 with protective cover in place |
| Pollution degree | 2 |
| Operating altitude | 0...2000 m |
| Storage altitude | 0…3000 m |
| Vibration resistance | 3.5 mm at 5…8.4 Hz on symmetrical rail; 3 gn at 8.4…150 Hz on symmetrical rail; 3.5 mm at 5…8.4 Hz on panel mounting; 3 gn at 8.4…150 Hz on panel mounting |
| Shock resistance | 15 gn for 11 ms |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 6 |
| Number of Units in Package 3 | 48 |
| Country of origin | ID |
| Warranty (in months) | 18 |
| EAN | 3606480648847 |
| Material | Polycarbonate/ABS housing |
| Temperature range | 0°C to +55°C |
| Primary standard | IEC 61131-2 |
| MOQ | 1 |
TM3/TM4 expansion, TMC4 cartridges, CANopen via cartridge. Programmed with EcoStruxure Machine (CODESYS).