cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Modicon M241 PLC TM241CE24R 24 I/O Ethernet

Schneider Electric · Control & Automation · PLCs · France · se.com
Part Number
TM241CE24R  ·  HS 8537.10
Schneider Modicon M241 PLC TM241CE24R 24 I/O Ethernet

Schneider Electric TM241CE24R Modicon M241 high-performance logic controller, 24 I/O (14 digital inputs incl.

Technical Specifications

SeriesModicon M241
Digital Inputs14 (8 fast 200kHz)
Digital Outputs10 relay
Communication1x Ethernet, 2x serial (1 RS232/485, 1 RS485), USB-mini-B
Supply Voltage24V DC
ExpansionUp to 14 TM3 / 7 TM4 modules
ProgrammingEcoStruxure Machine (CODESYS, all 5 IEC 61131-3 languages)
Mounting35mm DIN rail or screw plate
Range of productModicon M241
Product or component typeLogic controller
[Us] rated supply voltage100...240 V AC
Discrete input number14, discrete input 8 fast input conforming to IEC 61131-2 Type 1
Discrete output typeRelay; Transistor
Discrete output number6 relay; 4 transistor 4 fast output
Discrete output voltage5...125 V DC for relay output; 5...250 V AC for relay output; 24 V DC for transistor output
Discrete output current2 A for relay output (Q4...Q9); 0.1 A for fast output (PTO mode) (TR0...TR3); 0.5 A for transistor output (TR0...TR3)
Discrete I/O number24
Maximum number of I/O expansion module7 (local I/O-Architecture); 14 (remote I/O-Architecture)
Supply voltage limits85…264 V
Network frequency50/60 Hz
Discrete input logicSink or source
Discrete input voltage24 V
Discrete input voltage typeDC
Voltage state 1 guaranteed>= 15 V for input
Voltage state 0 guaranteed<= 5 V for input
Discrete input current5 mA for input
Input impedance4.7 kOhm for input
Response time50 µs turn-on, I0...I13 terminal(s) for input
Configurable filtering time1 s for fast input
Discrete output logicPositive logic (source)
Output voltage limits125 V DC relay output; 30 V DC transistor output; 277 V AC relay output
Maximum output frequency1 kHz for transistor output; 20 kHz for fast output (PWM mode); 100 kHz for fast output (PLS mode)
Accuracy+/- 0.1 % at 0.02…0.1 kHz for fast output; +/- 1 % at 0.1…1 kHz for fast output
Protection typeShort-circuit protection for transistor output; Short-circuit and overload protection with automatic reset for transistor output; Reverse polarity protection for transistor output; Without protection for relay output
Reset time10 ms automatic reset output; 12 s automatic reset fast output
Memory capacity64 MB for system memory RAM
Data backed up128 MB built-in flash memory for backup of user programs
Data storage equipment<= 16 GB SD card (optional)
Battery typeBR2032 lithium non-rechargeable, battery life: 4 year(s)
Backup time2 years at 25 °C
Execution time for 1 KInstruction0.3 ms for event and periodic task; 0.7 ms for other instruction
Application structure8 external event tasks; 3 cyclic master tasks + 1 freewheeling task; 8 event tasks; 4 cyclic master tasks
Realtime clockWith
Clock drift<= 60 s/month at 25 °C
Positioning functionsPTO function 4 channel(s) (positioning frequency: 100 kHz)
Counting input number4 fast input (HSC mode) at 200 kHz; 14 standard input at 1 kHz
Control signal typeA/B at 100 kHz for fast input (HSC mode); Pulse/direction at 200 kHz for fast input (HSC mode); Single phase at 200 kHz for fast input (HSC mode)
Integrated connection typeNon isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface ; Non isolated serial link serial 2 with removable screw terminal block connector and RS485 interface ; USB port with mini B USB 2.0 connector; Ethernet with RJ45 connector
Supply(serial 1)serial link supply: 5 V, <200 mA
Transmission rate1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485; 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232; 480 Mbit/s for bus length of 3 m for USB; 10/100 Mbit/s for Ethernet
Communication port protocolNon isolated serial link: Modbus master/slave
Port Ethernet10BASE-T/100BASE-TX - 1 port(s) copper cable
ethernet servicesFDR; DHCP server via TM4 Ethernet switch network module; DHCP client embedded Ethernet port; SMS notifications; Updating firmware; SNMP client/server; Programming; NGVL; Monitoring; IEC VAR ACCESS; FTP client/server; Downloading; SQL client; Modbus TCP client I/O scanner; Ethernet/IP originator I/O scanner embedded Ethernet port; Ethernet/IP target, Modbus TCP server and Modbus TCP slave; Send and receive email from the controller based on TCP/UDP library; Web server (WebVisu & XWeb system); OPC UA server; DNS client
Local signalling1 LED (green) for PWR; 1 LED (green) for RUN; 1 LED (red) for module error (ERR); 1 LED (red) for I/O error (I/O); 1 LED (green) for SD card access (SD); 1 LED (red) for BAT; 1 LED (green) for SL1; 1 LED (green) for SL2; 1 LED (red) for bus fault on TM4 (TM4); 1 LED per channel (green) for I/O state; 1 LED (green) for Ethernet port activity
Electrical connectionremovable screw terminal blockfor inputs and outputs (pitch 5.08 mm); removable screw terminal blockfor connecting the 24 V DC power supply (pitch 5.08 mm)
Maximum cable distance between devicesUnshielded cable: <50 m for input; Shielded cable: <10 m for fast input; Unshielded cable: <50 m for output; Shielded cable: <3 m for fast output
InsulationBetween supply and internal logic at 500 V AC; Non-insulated between supply and ground
MarkingCE
Sensor power supply24 V DC at 400 mA supplied by the controller
Surge withstand2 kV power lines (AC) common mode conforming to IEC 61000-4-5; 2 kV relay output common mode conforming to IEC 61000-4-5; 1 kV shielded cable common mode conforming to IEC 61000-4-5; 1 kV power lines (AC) differential mode conforming to IEC 61000-4-5; 1 kV relay output differential mode conforming to IEC 61000-4-5; 1 kV input common mode conforming to IEC 61000-4-5; 1 kV transistor output common mode conforming to IEC 61000-4-5
Web servicesWeb server
Maximum number of connections8 Modbus server; 8 SoMachine protocol; 10 web server; 4 FTP server; 16 Ethernet/IP target; 8 Modbus client
Number of server device(s)64 Modbus TCP: ; 16 EtherNet/IP:
Cycle time10 ms 16 EtherNet/IP; 64 ms 64 Modbus TCP
Mounting supportTop hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; plate or panel with fixing kit
Height90 mm
Depth95 mm
Width150 mm
Product weight0.53 kg
StandardsANSI/ISA 12-12-01; CSA C22.2 No 142; CSA C22.2 No 213; IEC 61131-2:2007; Marine specification (LR, ABS, DNV, GL); UL 508
Product certificationsRCM; cULus; CE; UKCA; DNV-GL; ABS; LR
Resistance to electrostatic discharge8 kV in air conforming to IEC 61000-4-2; 4 kV on contact conforming to IEC 61000-4-2
Resistance to electromagnetic fields10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3; 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3; 1 V/m 2 GHz...3 GHz conforming to IEC 61000-4-3
Resistance to fast transients2 kV (power lines) conforming to IEC 61000-4-4; 2 kV (relay output) conforming to IEC 61000-4-4; 1 kV (Ethernet line) conforming to IEC 61000-4-4; 1 kV (serial link) conforming to IEC 61000-4-4; 1 kV (input) conforming to IEC 61000-4-4; 1 kV (transistor output) conforming to IEC 61000-4-4
Resistance to conducted disturbances10 V 0.15...80 MHz conforming to IEC 61000-4-6; 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL); 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Electromagnetic emissionConducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to IEC 55011; Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to IEC 55011; Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines) at 0.15…0.5 MHz conforming to IEC 55011; Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines) at 0.5…300 MHz conforming to IEC 55011; Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to IEC 55011; Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to IEC 55011; Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to IEC 55011
Immunity to microbreaks10 ms
Ambient air temperature for operation-10…50 °C (vertical installation); -10…55 °C (horizontal installation)
Ambient air temperature for storage-25…70 °C
Relative humidity10…95 %, without condensation (in operation); 10…95 %, without condensation (in storage)
IP degree of protectionIP20 with protective cover in place
Pollution degree2
Operating altitude0...2000 m
Storage altitude0…3000 m
Vibration resistance3.5 mm at 5…8.4 Hz on symmetrical rail; 3 gn at 8.4…150 Hz on symmetrical rail; 3.5 mm at 5…8.4 Hz on panel mounting; 3 gn at 8.4…150 Hz on panel mounting
Shock resistance15 gn for 11 ms
Number of Units in Package 11
Number of Units in Package 28
Number of Units in Package 364
Country of originID
Warranty (in months)18
EAN3606480648830

Properties

MaterialPolycarbonate/ABS housing
Temperature range0°C to +55°C
Primary standardIEC 61131-2
MOQ1

Compatibility

TM3/TM4 expansion modules, TMC4 cartridges. Programming via EcoStruxure Machine. Native CANopen master with CANopen cartridge.

Standards

Approvals

Attached Documents