cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider NSX400F Maximum breaker - 3606482002623

Schneider Electric · Electrical Components · Moulded Case Circuit Breakers · France · se.com
Part Number
C40F32M320  ·  HS 8536.20
Schneider NSX400F Maximum breaker - 3606482002623

Schneider NSX400F Maximum breaker. Molded case circuit breakers (Electrical Engineering / Components for panels and boxes). Supplied under manufacturer part number C40F32M320, EAN 3606482002623, HS code 8536.20, country of origin France.

Technical Specifications

Product typeMolded case circuit breakers
Product groupComponents for panels and boxes
REACH SVHC substance above 0.1%Lead, Lead tetroxide, Lead-monoxide, Octrizole
Carbon footprint (EPD)35.4000 kg CO2e per pcs
Environmental declarationPEP ECO Passport
Country of originFrance
Customs tariff code (EU CN)85362090
HS code8536.20
Manufacturer part numberC40F32M320
RangeComPacT
Product nameComPacT NSX
Device short nameNSX400F
Product or component typeCircuit breaker
Device applicationMotor protection
Poles description3P
Protected poles description3D
[In] rated current320 A at 65 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1; 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1; 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Breaking capacity codeF 36 kA 415 V AC
Trip unit nameMicroLogic 2.3 M
Trip unit technologyElectronic
Trip unit protection functionsLSoI
Control typeToggle
Circuit breaker mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service breaking capacity40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability15000 cycles
Electrical durability12000 cycles at 440 V In/2; 6000 cycles at 440 V In; 6000 cycles at 690 V In/2; 3000 cycles at 690 V In
Power dissipation per pole19.2 W
Mounting supportBackplate
Mounting positionHorizontal and vertical; Flat on the back
Upside connectionFront
Downside connectionFront
Connection pitch45 mm
Protection typeL : for overload protection (long time); So : for short time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection
Trip unit rating320 A at 65 °C
Motor tripping class20; 5; 10
Complementary motor protectionPhase unbalance
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range160...320 A
Long-time protection delay adjustment type trFixed
[tr] long-time delay adjustment range120 s at 1.5 x Ir for trip class 5; 6.5 s at 6 x Ir for trip class 5; 5 s at 7.2 x Ir for trip class 5; 240 s at 1.5 x Ir for trip class 10; 13.5 s at 6 x Ir for trip class 10; 10 s at 7.2 x Ir for trip class 10; 480 s at 1.5 x Ir for trip class 20; 26 s at 6 x Ir for trip class 20; 20 s at 7.2 x Ir for trip class 20
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range5...13 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range4800 A
Earth-leakage protectionWithout
Zone selective interlocking ZSIWithout
Number of slots6 slot(s)
Local signallingFlashing LED (green) for ready to operate; LED 95 % Ith (red) for temperature over set point
Width (W)140 mm
Height (H)255 mm
Depth (D)110 mm
Product weight6.05 kg
StandardsEN/IEC 60947-2
Overvoltage categoryIII
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Relative humidity0…95 %
Operating altitude0...2000 m without derating; 2000 m...5000 m with derating
Warranty (in months)18
EAN3606482002623

Properties

MOQ1

Cross-References

Attached Documents