cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider NSX250F Maximum breaker - 3606482005556

Schneider Electric · Electrical Components · Moulded Case Circuit Breakers · France · se.com
Part Number
C25F42D100  ·  HS 8536.20
Schneider NSX250F Maximum breaker - 3606482005556

Schneider NSX250F Maximum breaker. Molded case circuit breakers (Electrical Engineering / Components for panels and boxes). Supplied under manufacturer part number C25F42D100, EAN 3606482005556, HS code 8536.20, country of origin Poland.

Technical Specifications

Product typeMolded case circuit breakers
Product groupComponents for panels and boxes
REACH SVHC substance above 0.1%Lead, Lead tetroxide, Lead-monoxide
Carbon footprint (EPD)16.0000 kg CO2e per pcs
Environmental declarationPEP ECO Passport
Country of originPoland
Customs tariff code (EU CN)85362090
HS code8536.20
Manufacturer part numberC25F42D100
RangeComPacT
Product nameComPacT NSX
Device short nameNSX250F
Product or component typeCircuit breaker
Device applicationDistribution
Poles description4P
Protected poles description4D; 3D + N/2; 3D
Neutral positionLeft
[In] rated current100 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1; 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1; 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Breaking capacity codeF 36 kA 415 V AC
Trip unit nameMicroLogic 2.2
Trip unit technologyElectronic
Trip unit protection functionsLSoI
Control typeToggle
Circuit breaker mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service breaking capacity85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability20000 cycles
Electrical durability20000 cycles at 440 V In/2; 10000 cycles at 440 V In; 10000 cycles at 690 V In/2; 5000 cycles at 690 V In
Power dissipation per pole17.6 W
Mounting supportBackplate
Mounting positionHorizontal and vertical; Flat on the back
Upside connectionFront
Downside connectionFront
Connection pitch35 mm
Protection typeL : for overload protection (long time); So : for short time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection
Trip unit rating100 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range40...100 A
Long-time protection delay adjustment type trFixed
[tr] long-time delay adjustment range400 s at 1.5 x Ir; 16 s at 6 x Ir; 11 s at 7.2 x Ir
Neutral protection setting0.5 x Ir (3D + N/2); 1 x Ir (4D); No protection (3D)
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range1500 A
Earth-leakage protectionWithout
Zone selective interlocking ZSIWithout
Number of slots5 slot(s)
Local signallingFlashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload
Width (W)140 mm
Height (H)161 mm
Depth (D)86 mm
Product weight2.8 kg
StandardsEN/IEC 60947-2
Overvoltage categoryIII
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Relative humidity0…95 %
Operating altitude0...2000 m without derating; 2000 m...5000 m with derating
Warranty (in months)18
EAN3606482005556

Properties

MOQ1

Cross-References

Attached Documents