cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider MULTI9 C60SP Circuit breaker - MULTI9 C60SP, 13A, 4P, D

Schneider Electric · Electrical Components · Moulded Case Circuit Breakers · France · se.com
Part Number
M9F23413  ·  HS 8536.20
Schneider MULTI9 C60SP Circuit breaker - MULTI9 C60SP, 13A, 4P, D

Schneider Multi9 C60SP Circuit breaker. Circuit breakers (Electrical Engineering / Components for panels and boxes). Principal data: series Multi9 C60SP, current rating 13 A, number of poles 4P, tripping characteristic D. Supplied under manufacturer part number M9F23413, EAN 3606481169280, HS code 8536.20, country of origin France.

Technical Specifications

Product typeCircuit breakers
Product groupComponents for panels and boxes
SeriesMulti9 C60SP
Current rating13 A
Number of poles4P
Tripping characteristicD
REACH SVHC substance above 0.1%Triphenyl phosphate
Sales unitPack
Carbon footprint (EPD)0.7980 kg CO2e per pcs
Environmental declarationPEP ECO Passport
Country of originFrance
Customs tariff code (EU CN)85362010
HS code8536.20
Manufacturer part numberM9F23413
RangeMulti9
Product nameMulti9 C60
Product or component typeMiniature circuit-breaker
Device short nameC60SP
Device applicationDistribution
Poles description4P
Number of protected poles4
[In] rated current13 A at 25 °C conforming to EN/IEC 60947-2
Network typeAC
Trip unit technologyThermal-magnetic
Curve codeD
Breaking capacity14 kA AIR at 240 V AC conforming to UL 1077; 14 kA AIR at 240 V AC conforming to CSA C22.2 No 235; 10 kA AIR at 480Y/277 V AC conforming to UL 1077; 10 kA AIR at 480Y/277 V AC conforming to CSA C22.2 No 235; 6 kA Icu at 440 V AC conforming to EN/IEC 60947-2; 10 kA Icu at 415 V AC conforming to EN/IEC 60947-2; 20 kA Icu at 240 V AC conforming to EN/IEC 60947-2; 6 kA Icu at 440 V AC conforming to GB/T 14048.2; 10 kA Icu at 415 V AC conforming to GB/T 14048.2; 20 kA Icu at 240 V AC conforming to GB/T 14048.2
StandardsEN/IEC 60947-2; GB/T 14048.2; UL 1077; CSA C22.2 No 235
Product certificationsIEC; CCC; UR; CSA
[Ue] rated operational voltage240 V AC 50/60 Hz; 415 V AC 50/60 Hz; 440 V AC 50/60 Hz
Magnetic tripping limit12 x In +/- 20 % AC
[Ics] rated service breaking capacity4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC; 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC; 15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC; 4.5 kA 75 % conforming to GB/T 14048.2 - 440 V AC; 7.5 kA 75 % conforming to GB/T 14048.2 - 415 V AC; 15 kA 75 % conforming to GB/T 14048.2 - 240 V AC
[Ui] rated insulation voltage500 V AC conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Suitability for isolationYes conforming to EN/IEC 60947-2
Contact position indicatorYes
Control typeToggle
Local signallingON/OFF indication
mounting modeClip-on
Mounting supportDIN rail
9 mm pitches8
Height81 mm
Width72 mm
Depth72 mm
ColourGrey
Mechanical durability20000 cycles
Electrical durability10000 cycles
Provision for padlockingPadlockable
Connections - terminalsTunnel type terminal (top or bottom)1…25 mm² (18 AWG...8 AWG) - rigid; Tunnel type terminal (top or bottom)1…16 mm² (18 AWG...8 AWG) - flexible with ferrule; Tunnel type terminal (top or bottom)1…16 mm² (18 AWG...8 AWG) - flexible
Wire stripping length14 mm for top or bottom connection
Tightening torque2.5 N.m top or bottom
Earth-leakage protectionWithout
IP degree of protectionIP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Operating altitude0...2000 m
Ambient air temperature for operation-30…70 °C
Ambient air temperature for storage-40…80 °C
Warranty (in months)18
EAN3606481169280

Properties

MOQ1

Cross-References

Attached Documents