| Product type | Distributed I/O |
| Product group | Industry and automation |
| Carbon footprint (EPD) | 0.3488 kg CO2e per pcs |
| Country of origin | Austria |
| Customs tariff code (EU CN) | 90291000 |
| HS code | 9029.10 |
| Manufacturer part number | TM5SE1IC02505 |
| Range of product | Modicon TM5 |
| Product or component type | Counter module |
| Function of module | 2 x 24 V DC RS422 sink auxiliary inputs; 24 V DC encoder power supply |
| Discrete input number | 1 |
| Counting frequency | 250 kHz |
| Encoder type | 1 incremental encoder |
| Product compatibility | Motion controller; Logic controller |
| Range compatibility | Modicon LMC058; Modicon M258 |
| Counter inputs resolution | 16 bits/32 bits |
| Maximum cycle time | 2 ms |
| Input compatibility | 1 incremental encoder (5 V) |
| Isolation | 500 Vrms AC insulation between channel and bus |
| Discrete input logic | Sink |
| Discrete input voltage | 24 V DC |
| Discrete input current | 3.3 mA at 24 V |
| Input resistance | 7.19 kOhm |
| Input filtering | <= 200 ms |
| Current consumption | 2 mA at 5 V DC bus; 63 mA at 24 V DC input/output |
| Maximum power dissipation in W | 1.51 W |
| Marking | CE |
| DC supply voltage | 24 V |
| Height | 99 mm |
| Width | 12.5 mm |
| Depth | 75 mm |
| Standards | UL 508; CSA C22.2 No 142; CSA C22.2 No 213; IEC 61131-2 |
| Product certifications | cULus; C-Tick; GOST-R; CSA |
| Ambient air temperature for operation | 0…55 °C without derating (horizontal installation); 0…60 °C with derating factor (horizontal installation); 0…50 °C (vertical installation) |
| Ambient air temperature for storage | -25…70 °C |
| Relative humidity | 5…95 % without condensation |
| IP degree of protection | IP20 conforming to IEC 61131-2 |
| Pollution degree | 2 conforming to IEC 60664 |
| Operating altitude | 0...2000 m |
| Storage altitude | 0…3000 m |
| Vibration resistance | 1 gn at 8.4…150 Hz on DIN rail; 3.5 mm at 5…8.4 Hz on DIN rail |
| Shock resistance | 15 gn for 11 ms |
| Resistance to electrostatic discharge | 4 kV on contact conforming to IEC 61000-4-2; 8 kV in air conforming to IEC 61000-4-2 |
| Resistance to electromagnetic fields | 1 V/m 2...2.7 GHz conforming to IEC 61000-4-3; 10 V/m 80...2000 MHz conforming to IEC 61000-4-3 |
| Resistance to fast transients | 1 kV (I/O) conforming to IEC 61000-4-4; 1 kV (shielded cable) conforming to IEC 61000-4-4; 2 kV (power lines) conforming to IEC 61000-4-4 |
| Surge withstand | 0.5 kV differential mode conforming to IEC 61000-4-5; 1 kV common mode conforming to IEC 61000-4-5 |
| Electromagnetic compatibility | EN/IEC 61000-4-6 |
| Disturbance radiated/conducted | CISPR 11 |
| Warranty (in months) | 18 |
| EAN | 3595864074832 |