cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider LUCL Short Circuit Release - TeSys Ultra 3389119408004

Schneider Electric · Drives & Controllers · Motor Starters · France · se.com
Part Number
LUCL18ES  ·  HS 8536.30
Schneider LUCL Short Circuit Release - TeSys Ultra 3389119408004

Schneider LUCL Short Circuit Release. Contactors and thermal relays (Electrical Engineering / Components for panels and boxes). Principal data: series TeSys Ultra. Supplied under manufacturer part number LUCL18ES, EAN 3389119408004, HS code 8536.30, country of origin France.

Technical Specifications

Product typeContactors and thermal relays
Product groupComponents for panels and boxes
SeriesTeSys Ultra
Voltage48 ACDC V
Supply voltage48 ACDC V
Setting range4.5 to 18
REACH SVHC substance above 0.1%2-methylimidazole, Lead, Diarylmethane, Diboron-trioxide, Lead-monoxide
Carbon footprint (EPD)9.4500 kg CO2e per pcs
Environmental declarationPEP ECO Passport
Country of originFrance
Customs tariff code (EU CN)85363030
HS code8536.30
Manufacturer part numberLUCL18ES
RangeTeSys
Range of productTeSys Ultra
Product nameTeSys Ultra
Device short nameLUCL
Product or component typeMagnetic control unit
Device applicationMotor control; Motor protection
Product specific applicationProtection of variable speed drive or soft startsoft stop unit
main function availableManual reset; Short-circuit protection
Product compatibilityPower base LUB32; Power base LUB38; Power base LUB320; Power base LUB380; Reversing contactor breaker LU2B32ES
[Ue] rated operational voltage690 V AC
Network frequency40...60 Hz
Load type3-phase motor - cooling: self-cooled
Utilisation categoryAC-43; AC-44; AC-41
Motor power kW7.5 kW at 400...440 V AC 50/60 Hz; 9 kW at 500 V AC 50/60 Hz; 15 kW at 690 V AC 50/60 Hz
rated motor current adjustment range4.5…18 A
Tripping threshold14.2 x Ir +/- 20 %
[Uc] control circuit voltage48 V AC; 48...72 V DC
Control circuit voltage limits38.5...72 V for AC circuit 48 V in operation; 38.5...93 V for DC circuit 48...72 V in operation; 29 V for AC circuit 48 V drop-out; 29 V for DC circuit 48...72 V drop-out
Typical current consumption280 mA at 48 V AC I maximum while closing with LUB32; 280 mA at 48 V AC I maximum while closing with LUB38; 280 mA at 48...72 V DC I maximum while closing with LUB32; 280 mA at 48...72 V DC I maximum while closing with LUB38; 45 mA at 48 V AC I rms sealed with LUB32; 45 mA at 48 V AC I rms sealed with LUB38; 45 mA at 48...72 V DC I rms sealed with LUB32; 45 mA at 48...72 V DC I rms sealed with LUB38
Heat dissipation3 W for control circuit with LUB32; 3 W for control circuit with LUB38
Operating time35 ms opening with LUB32 for control circuit; 35 ms opening with LUB38 for control circuit; 60 ms closing with LUB32 for control circuit; 60 ms closing with LUB38 for control circuit
StandardsEN 60947-6-2; IEC 60947-6-2; UL 60947-4-1, with phase barrier; CSA C22.2 No 60947-4-1, with phase barrier
Product certificationsCE; EAC; ATEX
[Ui] rated insulation voltage690 V conforming to IEC 60947-6-2; 600 V conforming to UL 60947-4-1; 600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-6-2
Safe separation of circuit400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1; 400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1
Fixing modePlug-in (front face)
Width45 mm
Height66 mm
Depth60 mm
Product weight0.135 kg
Compatibility codeLUCL
IP degree of protectionIP20 front panel and wired terminals conforming to IEC 60947-1; IP20 other faces conforming to IEC 60947-1; IP40 front panel outside connection zone conforming to IEC 60947-1
Protective treatmentTH conforming to IEC 60068
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Operating altitude2000 m
Fire resistance960 °C parts supporting live components conforming to IEC 60695-2-12; 650 °C conforming to IEC 60695-2-12
Shock resistance10 gn power poles open conforming to IEC 60068-2-27; 15 gn power poles closed conforming to IEC 60068-2-27
Vibration resistance2 gn, 5…300 Hz, power poles open conforming to IEC 60068-2-6; 4 gn, 5…300 Hz, power poles closed conforming to IEC 60068-2-6
Resistance to electrostatic discharge8 kV level 3 in open air conforming to IEC 61000-4-2; 8 kV level 4 on contact conforming to IEC 61000-4-2
Non-dissipating shock wave1 kV serial mode conforming to IEC 60947-6-2; 2 kV common mode conforming to IEC 60947-6-2
Resistance to radiated fields10 V/m 3 conforming to IEC 61000-4-3
Resistance to fast transients2 kV class 3 serial link conforming to IEC 61000-4-4; 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4
Immunity to radioelectric fields10 V conforming to IEC 61000-4-6
Immunity to microbreaks3 ms
Immunity to voltage dips70 % / 500 ms conforming to IEC 61000-4-11
Warranty (in months)18
EAN3389119408004

Properties

MOQ1

Cross-References

Attached Documents