cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider LUCD Power Module - TeSys Ultra, 48 AC / 48-72 DCV 3389110365016

Schneider Electric · Drives & Controllers · Motor Starters · France · se.com
Part Number
LUCD32ES  ·  HS 8536.30
Schneider LUCD Power Module - TeSys Ultra, 48 AC / 48-72 DCV 3389110365016

Schneider LUCD Power Module. Motor protection and accessories (Electrical Engineering / Components for panels and boxes). Principal data: series TeSys Ultra, voltage 48 AC / 48-72 V DC. Supplied under manufacturer part number LUCD32ES, EAN 3389110365016, HS code 8536.30, country of origin France.

Technical Specifications

Product typeMotor protection and accessories
Product groupComponents for panels and boxes
SeriesTeSys Ultra
Voltage48 AC / 48-72 V DC
REACH SVHC substance above 0.1%Lead, Lead-monoxide
Carbon footprint (EPD)9.4500 kg CO2e per pcs
Environmental declarationPEP ECO Passport
Country of originFrance
Customs tariff code (EU CN)85363030
HS code8536.30
Manufacturer part numberLUCD32ES
RangeTeSys
Range of productTeSys Ultra
Product nameTeSys Ultra
Device short nameLUCD
Product or component typeAdvanced control unit
Device applicationMotor control; Motor protection
Product specific applicationBasic protection and advanced functions, communication
main function availableManual reset; Protection against overload and short-circuit; Earth fault protection; Protection against phase failure and phase imbalance
Product compatibilityPower base LUB32; Power base LUB38; Power base LUB320; Power base LUB380; Reversing contactor breaker LU2B32ES
[Ue] rated operational voltage690 V AC
Network frequency40...60 Hz
Load type3-phase motor - cooling: self-cooled
Utilisation categoryAC-43; AC-41; AC-44
Motor power kW15 kW at 400...440 V AC 50/60 Hz; 15 kW at 500 V AC 50/60 Hz; 18.5 kW at 690 V AC 50/60 Hz
rated motor current adjustment range8…32 A
Thermal overload classClass 20 - frequency limit: 40…60 Hz - temperature compensation: -25…70 °C conforming to IEC 60947-6-2; Class 20 - frequency limit: 40…60 Hz - temperature compensation: -25…70 °C conforming to UL 508
Tripping threshold14.2 x Ir +/- 20 %
Phase failure sensitivityYes
[Uc] control circuit voltage48 V AC; 48...72 V DC
Control circuit voltage limits38.5...72 V for AC circuit 48 V in operation; 38.5...93 V for DC circuit 48...72 V in operation; 29 V for AC circuit 48 V drop-out; 29 V for DC circuit 48...72 V drop-out
Typical current consumption280 mA at 48 V AC I maximum while closing with LUB32; 280 mA at 48 V AC I maximum while closing with LUB38; 280 mA at 48...72 V DC I maximum while closing with LUB32; 280 mA at 48...72 V DC I maximum while closing with LUB38; 45 mA at 48 V AC I rms sealed with LUB32; 45 mA at 48 V AC I rms sealed with LUB38; 45 mA at 48...72 V DC I rms sealed with LUB32; 45 mA at 48...72 V DC I rms sealed with LUB38
Heat dissipation3 W for control circuit with LUB32; 3 W for control circuit with LUB38
Operating time35 ms opening with LUB32 for control circuit; 35 ms opening with LUB38 for control circuit; 60 ms closing with LUB32 for control circuit; 60 ms closing with LUB38 for control circuit
ResetManual reset
StandardsEN 60947-6-2; IEC 60947-6-2; UL 60947-4-1, with phase barrier; CSA C22.2 No 60947-4-1, with phase barrier
Product certificationsCE; UL; CSA; CCC; EAC; ASEFA; ATEX; Marine
[Ui] rated insulation voltage690 V conforming to IEC 60947-6-2; 600 V conforming to UL 60947-4-1; 600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-6-2
Safe separation of circuit400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1; 400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1
Fixing modePlug-in (front face)
Width45 mm
Height66 mm
Depth60 mm
Compatibility codeLUCD
IP degree of protectionIP20 front panel and wired terminals conforming to IEC 60947-1; IP20 other faces conforming to IEC 60947-1; IP40 front panel outside connection zone conforming to IEC 60947-1
Protective treatmentTH conforming to IEC 60068
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Operating altitude2000 m
Fire resistance960 °C parts supporting live components conforming to IEC 60695-2-12; 650 °C conforming to IEC 60695-2-12
Shock resistance10 gn power poles open conforming to IEC 60068-2-27; 15 gn power poles closed conforming to IEC 60068-2-27
Vibration resistance2 gn, 5…300 Hz, power poles open conforming to IEC 60068-2-6; 4 gn, 5…300 Hz, power poles closed conforming to IEC 60068-2-6
Resistance to electrostatic discharge8 kV level 3 in open air conforming to IEC 61000-4-2; 8 kV level 4 on contact conforming to IEC 61000-4-2
Non-dissipating shock wave1 kV serial mode conforming to IEC 60947-6-2; 2 kV common mode conforming to IEC 60947-6-2
Resistance to radiated fields10 V/m 3 conforming to IEC 61000-4-3
Resistance to fast transients2 kV class 3 serial link conforming to IEC 61000-4-4; 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4
Immunity to radioelectric fields10 V conforming to IEC 61000-4-6
Immunity to microbreaks3 ms
Immunity to voltage dips70 % / 500 ms conforming to IEC 61000-4-11
Warranty (in months)18
EAN3389110365016

Properties

MOQ1

Cross-References