cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider LP4K Contactor - TeSys K, 24 DCV 3389110498646

Schneider Electric · Electrical Components · Contactors · France · se.com
Part Number
LP4K09004BW3  ·  HS 8536.41
Schneider LP4K Contactor - TeSys K, 24 DCV 3389110498646

Schneider LP4K Contactor. Contactors and thermal relays motor control (Electrical Engineering / Components for panels and boxes). Principal data: series TeSys K, voltage 24 V DC. Supplied under manufacturer part number LP4K09004BW3, EAN 3389110498646, HS code 8536.41, country of origin France.

Technical Specifications

Product typeContactors and thermal relays motor control
Product groupComponents for panels and boxes
SeriesTeSys K
Voltage24 V DC
Carbon footprint (EPD)1.4222 kg CO2e per pcs
Country of originFrance
Customs tariff code (EU CN)85364190
HS code8536.41
Manufacturer part numberLP4K09004BW3
RangeTeSys
Product or component typeContactor
Device short nameLP4K
Contactor applicationResistive load
Utilisation categoryAC-1
Poles description4P
power pole contact composition4 NO
[Ue] rated operational voltagePower circuit: <= 690 V AC <= 400 Hz; Signalling circuit: <= 690 V AC <= 400 Hz
[Ie] rated operational current20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit
Control circuit typeDC wide range
[Uc] control circuit voltage24 V DC
[Uimp] rated impulse withstand voltage8 kV
Overvoltage categoryIII
[Ith] conventional free air thermal current20 A (at 60 °C) for power circuit; 10 A (at 50 °C) for signalling circuit
Irms rated making capacity110 A AC for power circuit conforming to IEC 60947
Rated breaking capacity110 A at 220...230 V conforming to IEC 60947; 110 A at 380...400 V conforming to IEC 60947; 110 A at 415 V conforming to IEC 60947; 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand current90 A 50 °C - 1 s for power circuit; 85 A 50 °C - 5 s for power circuit; 80 A 50 °C - 10 s for power circuit; 60 A 50 °C - 30 s for power circuit; 45 A 50 °C - 1 min for power circuit; 40 A 50 °C - 3 min for power circuit; 20 A 50 °C - >= 15 min for power circuit
Associated fuse rating25 A gG at <= 440 V for power circuit; 25 A aM for power circuit
Average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit: 600 V conforming to UL 508; Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V conforming to CSA C22.2 No 14
Inrush power in W1.8 W (at 20 °C)
Hold-in power consumption in W1.8 W at 20 °C
Heat dissipation1.8 W
Control circuit voltage limitsOperational: 0.7...1.3 Uc (at = 0.10 Uc (at <50 °C)
Connections - terminalsScrew clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end; Power circuit: screw clamp terminals 2 cable(s) 1.5 mm²flexible with cable end
Maximum operating rate3600 cyc/h
Coil technologyWith integral suppression device
Mounting supportPlate; Rail
Tightening torque0.8…1.3 N.m - on screw clamp terminals Philips No 2; 0.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm; 0.8…1.3 N.m - on screw clamp terminals pozidriv No 2
Operating time30...40 ms coil energisation and NO closing; 10 ms coil de-energisation and NO opening
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability30 Mcycles
Electrical durability0.16 Mcycles 20 A AC-1 at Ue <= 690 V
Height58 mm
Width45 mm
Depth57 mm
Product weight0.235 kg
StandardsEN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; GB/T 14048.4
Product certificationsCB Scheme; CCC; UL; CSA; EAC; CE; UKCA
IP degree of protectionIP2X
Ambient air temperature for operation-25…50 °C
Ambient air temperature for storage-50…80 °C
Operating altitude2000 m without derating
Flame retardanceV1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102
Warranty (in months)18
EAN3389110498646

Properties

MOQ1

Cross-References

Attached Documents