cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-08
sales@cballast.com
cballast.com

Schneider LC1K Contactor - TeSys K, 9A, 4P, 4NO, 230V

Schneider Electric · Electrical Components · Contactors · France · se.com
Part Number
LC1K09004P7  ·  HS 8536.49
Schneider LC1K Contactor - TeSys K, 9A, 4P, 4NO, 230V

Schneider LC1K Contactor. Contactors and thermal relays motor control (Electrical Engineering / Components for panels and boxes). Principal data: series TeSys K, current 9 A, number of poles 4P, contact type 4NO. Supplied under manufacturer part number LC1K09004P7, EAN 3389110488470, HS code 8536.49, country of origin France.

Technical Specifications

Product typeContactors and thermal relays motor control
Product groupComponents for panels and boxes
SeriesTeSys K
Current9 A
Number of poles4P
Contact type4NO
Voltage230 V
Carbon footprint (EPD)1.1531 kg CO2e per pcs
Country of originFrance
Customs tariff code (EU CN)85364900
HS code8536.49
Manufacturer part numberLC1K09004P7
RangeTeSys
Product or component typeContactor
Device short nameLC1K
Device applicationControl
Contactor applicationResistive load
Utilisation categoryAC-1
Poles description4P
power pole contact composition4 NO
[Ue] rated operational voltagePower circuit: <= 690 V AC <= 400 Hz; Signalling circuit: <= 690 V AC <= 400 Hz
[Ie] rated operational current20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit
Control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage230 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Overvoltage categoryIII
[Ith] conventional free air thermal current20 A (at 60 °C) for power circuit; 10 A (at 50 °C) for signalling circuit
Irms rated making capacity110 A AC for power circuit conforming to IEC 60947
Rated breaking capacity110 A at 220...230 V conforming to IEC 60947; 110 A at 380...400 V conforming to IEC 60947; 110 A at 415 V conforming to IEC 60947; 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand current90 A 50 °C - 1 s for power circuit; 85 A 50 °C - 5 s for power circuit; 80 A 50 °C - 10 s for power circuit; 60 A 50 °C - 30 s for power circuit; 45 A 50 °C - 1 min for power circuit; 40 A 50 °C - 3 min for power circuit; 20 A 50 °C - >= 15 min for power circuit
Associated fuse rating25 A gG at <= 440 V for power circuit; 25 A aM for power circuit
Average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit: 600 V conforming to UL 508; Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V conforming to CSA C22.2 No 14
Inrush power in VA30 VA (at 20 °C)
Hold-in power consumption in VA4.5 VA (at 20 °C)
Heat dissipation1.3 W
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at = 0.20 Uc (at <50 °C)
Connections - terminalsScrew clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end
Maximum operating rate3600 cyc/h
Coil technologyWithout built-in suppressor module
Signalling circuit frequency<= 400 Hz
Mounting supportPlate; Rail
Tightening torque0.8…1.3 N.m - on screw clamp terminals Philips No 2; 0.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm; 0.8…1.3 N.m - on screw clamp terminals pozidriv No 2
Operating time10...20 ms coil de-energisation and NO opening; 10...20 ms coil energisation and NO closing
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability10 Mcycles
Electrical durability0.16 Mcycles 20 A AC-1 at Ue <= 690 V
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27; Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Height58 mm
Width45 mm
Depth57 mm
Product weight0.18 kg
StandardsEN/IEC 60947-4-1; GB/T 14048.4; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ
Product certificationsCB Scheme; CCC; UL; CSA; EAC; CE; UKCA
IP degree of protectionIP2X conforming to VDE 0106
Protective treatmentTC conforming to IEC 60068; TC conforming to DIN 50016
Ambient air temperature for storage-50…80 °C
Operating altitude2000 m without derating
Flame retardanceV1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102
Number of Units in Package 11
Number of Units in Package 250
Warranty (in months)18
EAN3389110488470

Properties

MOQ1

Cross-References

Attached Documents