Schneider LC1D Contactor - TeSys D, 40A, 2P, 24 ACV

Schneider Electric · Electrical Components · Contactors · France · se.com
Part Number
LC1D40008B7  ·  HS 8536.41
Schneider LC1D Contactor - TeSys D, 40A, 2P, 24 ACV

Schneider LC1D Contactor. Contactors and thermal relays (Electrical Engineering / Components for panels and boxes). Principal data: series TeSys D, current 40 A, number of poles 2P, voltage 24 V AC. Supplied under manufacturer part number LC1D40008B7, EAN 3389110231571, HS code 8536.41, country of origin Czechia.

Technical Specifications

Product typeContactors and thermal relays
Product groupComponents for panels and boxes
SeriesTeSys D
Current40 A
Number of poles2P
Voltage24 V AC
Carbon footprint (EPD)6.4305 kg CO2e per pcs
Country of originCzechia
Customs tariff code (EU CN)85364190
HS code8536.41
Manufacturer part numberLC1D40008B7
RangeTeSys
Range of productTeSys Deca
Product or component typeContactor
Device short nameLC1D
Contactor applicationResistive load
Utilisation categoryAC-1
Poles description4P
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz; Power circuit: <= 300 V DC
[Ie] rated operational current60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage24 V AC 50/60 Hz
Compatibility codeLC1D
Pole contact composition2 NO + 2 NC
Protective coverWith
[Ith] conventional free air thermal current60 A (at 60 °C) for power circuit
Irms rated making capacity800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity800 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current320 A 40 °C - 10 s for power circuit; 720 A 40 °C - 1 s for power circuit; 72 A 40 °C - 10 min for power circuit; 165 A 40 °C - 1 min for power circuit
Associated fuse rating80 A gG at <= 690 V coordination type 1 for power circuit; 80 A gG at <= 690 V coordination type 2 for power circuit
Average impedance1.5 mOhm - Ith 60 A 50 Hz for power circuit
Power dissipation per pole5.4 W AC-1
[Ui] rated insulation voltagePower circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage categoryIII
Pollution degree3
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability6 Mcycles
Electrical durability1.4 Mcycles 60 A AC-1 at Ue <= 440 V
Control circuit typeAC at 50/60 Hz
Coil technologyWithout built-in suppressor module
Control circuit voltage limits0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Inrush power in VA140 VA 60 Hz cos phi 0.75 (at 20 °C); 160 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA13 VA 60 Hz cos phi 0.3 (at 20 °C); 15 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation4…5 W at 50/60 Hz
Operating time4...19 ms opening; 12...26 ms closing
Maximum operating rate3600 cyc/h at 60 °C
Connections - terminalsControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end; Power circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: solid without cable end; Power circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: solid without cable end
Tightening torqueControl circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 8 N.m - on screw clamp terminals - cable 25…35 mm² hexagonal screw head 4 mm; Power circuit: 5 N.m - on screw clamp terminals - cable 1…25 mm² hexagonal screw head 4 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Mounting supportRail; Plate
StandardsCSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1
Product certificationsDNV; LROS (Lloyds register of shipping); GL; UL; BV; CCC; CSA; GOST; RINA
IP degree of protectionIP20 front face conforming to IEC 60529
Protective treatmentTH conforming to IEC 60068-2-30
Climatic withstandconforming to IACS E10 exposure to damp heat
Permissible ambient air temperature around the device-40…60 °C; 60…70 °C with derating
Operating altitude0...3000 m
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
Mechanical robustnessShocks contactor open (8 Gn for 11 ms) ; Shocks contactor closed (10 Gn for 11 ms) ; Vibrations contactor opened (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz)
Height127 mm
Width85 mm
Depth125 mm
Product weight1.44 kg
Warranty (in months)18
EAN3389110231571

Properties

MOQ1

Cross-References

Attached Documents