cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider GV4PEM Motor Protection - TeSys D, 7A

Schneider Electric · Electrical Components · Motor Protection Circuit Breakers · France · se.com
Part Number
GV4PEM07N6  ·  HS 8536.20
Schneider GV4PEM Motor Protection - TeSys D, 7A

Schneider GV4PEM Motor Protection. Motor protection and accessories (Electrical Engineering / Components for panels and boxes). Principal data: series TeSys D, setting range 7 A. Supplied under manufacturer part number GV4PEM07N6, EAN 3606481310897, HS code 8536.20, country of origin Poland.

Technical Specifications

Product typeMotor protection and accessories
Product groupComponents for panels and boxes
SeriesTeSys D
Setting range7 A
REACH SVHC substance above 0.1%Lead, Diboron-trioxide, Lead-monoxide
Carbon footprint (EPD)8.8014 kg CO2e per pcs
Country of originPoland
Customs tariff code (EU CN)85362010
HS code8536.20
Manufacturer part numberGV4PEM07N6
RangeTeSys Deca
Range of productTeSys GV4
Device short nameGV4PEM
Product nameTeSys GV4
Product or component typeMotor circuit breaker
Device applicationMotor protection
Trip unit technologyThermal-magnetic; Electronic
Poles description3P
Utilisation categoryCategory A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1
Operating positionAny position
Motor power kW1.5 kW at 400...415 V AC 50/60 Hz; 2.2 kW at 400...415 V AC 50/60 Hz; 2.5 kW at 400...415 V AC 50/60 Hz; 3 kW at 400...415 V AC 50/60 Hz; 2.2 kW at 500 V AC 50/60 Hz; 2.5 kW at 500 V AC 50/60 Hz; 3 kW at 500 V AC 50/60 Hz; 4 kW at 500 V AC 50/60 Hz; 3 kW at 660...690 V AC 50/60 Hz; 4 kW at 660...690 V AC 50/60 Hz; 5.5 kW at 660...690 V AC 50/60 Hz; 7.5 kW at 660...690 V AC 50/60 Hz
Breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA at 208Y/120 V AC 50/60 Hz conforming to UL 60947; 65 kA at 240 V AC 50/60 Hz conforming to UL 60947; 35 kA at 480Y/277 V AC 50/60 Hz conforming to UL 60947; 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 18 kA at 600Y/347 V AC 50/60 Hz conforming to UL 60947
Control typeToggle
[In] rated current7 A
Magnetic tripping current119 A
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage800 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current115 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
Power dissipation per pole4.6 W
Mechanical durability40000 cycles
Electrical durability5000 cycles for AC-3 at 415 V opening; 5000 cycles for AC-3 at 440 V closing
maximum operating rate25 cyc/h
Rated dutyContinuous conforming to IEC 60947-4-1
Connection pitch27 mm without spreaders; 35 mm with spreaders
Connections - terminalsLugs-ring terminals
Tightening torque9 N.m for cable 16…95 mm²; 5 N.m for cable 1.5…10 mm²
Mechanical robustnessVibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6; Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6; Shocks: 15 gn 11 ms conforming to IEC 60068-2-27
Phase failure sensitivityYes conforming to IEC 60947-4-1
Height155 mm
Width81 mm
Depth116 mm
Product weight1.45 kg
ColourGrey (RAL 7016)
Suitability for isolationYes conforming to IEC 60947-1
StandardsCSA C22.2 No 60947-4-1; UL 60947-4-1; EN/IEC 60947-4-1; EN/IEC 60947-2
Product certificationsIEC; UL; CSA; CCC; EAC; ATEX; EU-RO MR
Climatic withstandconforming to IACS E10
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3
IP degree of protectionIP40 conforming to IEC 60529
Ambient air temperature for storage-50…85 °C
Fire resistance960 °C conforming to IEC 60695-2-11
Operating altitude5000 m
Ambient air temperature for operation-25…70 °C
Warranty (in months)18
EAN3606481310897

Properties

MOQ1

Cross-References