Schneider ACTI9 iCT Contactor on/off - 63A, 4P, 4NO, 24 ACV, 54

Schneider Electric · Electrical Components · Contactors · France · se.com
Part Number
A9C21164  ·  HS 8536.41
Schneider ACTI9 iCT Contactor on/off - 63A, 4P, 4NO, 24 ACV, 54

Schneider Acti9 iCT Contactor on/off. Modular contactor (Electrical Engineering / Components for panels and boxes). Principal data: current 63 A, number of poles 4P, contact type 4NO, voltage 24 V AC. Supplied under manufacturer part number A9C21164, EAN 3606480375293, HS code 8536.41, country of origin France.

Technical Specifications

Product typeModular contactor
Product groupComponents for panels and boxes
Current63 A
Number of poles4P
Contact type4NO
Voltage24 V AC
Module size54
Sales unitPack
Carbon footprint (EPD)1.5977 kg CO2e per pcs
Country of originFrance
Customs tariff code (EU CN)85364190
HS code8536.41
Manufacturer part numberA9C21164
range of productActi9
Product nameActi9 iCT
Product or component typeContactor
Device short nameiCT
Device applicationMotor-heating-lighting
Poles4P
[Ie] rated operational current63 A AC-7A; 20 A AC-7B
Pole contact composition4 NO
Network typeAC
Control typeRemote and manual control
[Uc] control circuit voltage24 V AC 50 Hz
Network frequency50 Hz
[Ue] rated operational voltage400 V AC 50 Hz
Maximum power2.1 W at 400 V AC
[Ui] rated insulation voltage500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage4 kV
Control signal typeMaintained
Switching frequency100 switching operations/day
Local signallingAction indicator
Hold-in power consumption in VA6.5 VA
Inrush power in VA53 VA
mounting modeClip-on
Mounting support35 mm symmetrical DIN rail
9 mm pitches6
Height85 mm
Width54 mm
Depth73.5 mm
ColourWhite
Mechanical durability1000000 cycles
Electrical durability100000 cycles IEC/EN 61095 63 A 50 Hz AC-7A; 30000 cycles IEC/EN 61095 20 A 50 Hz AC-7B; 30000 cycles IEC/EN 61095 50 Hz AC-7C; 100000 cycles EN/IEC 60947-4-1 50 Hz AC-1; 30000 cycles EN/IEC 60947-4-1 50 Hz AC-3; 30000 cycles EN/IEC 60947-4-1 50 Hz AC-5a; 30000 cycles EN/IEC 60947-4-1 50 Hz AC-5b
Connections - terminalsControl circuit: tunnel type terminals2 cable(s) 1.5 mm² rigid; Control circuit: tunnel type terminals1 cable(s) 1.5…2.5 mm² rigid; Power circuit: tunnel type terminals1 cable(s) 6…16 mm² flexible; Power circuit: tunnel type terminals1 cable(s) 6…25 mm² rigid; Control circuit: tunnel type terminals2 cable(s) 1.5…2.5 mm² flexible
Tightening torqueControl circuit: 0.8 N.m; Power circuit: 3.5 N.m
Product compatibilityIACTs; IACTc; IACTp; IATEt
Compatibility codeICT
Market segmentResidential; Small commercial
StandardsIEC/EN 61095
Noise level30 dB
IP degree of protectionIP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree2
Tropicalisation2 conforming to EN 60947-4-1; 2 conforming to EN 61095; 2 conforming to IEC 1095
Relative humidity95 % at 55 °C
Operating altitude2000 m
Ambient air temperature for operation-5…60 °C
Ambient air temperature for storage-40…70 °C
Number of Units in Package 11
Number of Units in Package 24
Number of Units in Package 324
Warranty (in months)18
EAN3606480375293

Properties

MOQ1

Cross-References